Page: Last modified: 2026-04-20
Code Reference(s):
NBC25 Div.B 9.36.11. (first printing)
Subject:
Energy Efficiency for Houses
Title:
Tiered Energy Compliance: Tier 2 Prescriptive Path
Description:
This proposed change provides energy-efficiency requirements for compliance with Energy Performance Tier 2 of the energy performance compliance prescriptive path.
This change could potentially affect the following topic areas:

Problem

The 2020 edition of the National Building Code of Canada (NBC) introduced energy-efficiency performance tiers in Section 9.36. of Division B, with increasing levels of improvement for buildings and houses, to provide jurisdictions with the option to adopt the most suitable energy performance level or their needs.

Although performance modeling is a common practice, many Code users have requested that prescriptive compliance paths remain in the National Model Codes to simplify achieving energy compliance. However, there are currently only performance requirements and prescriptive trade-off requirements for Energy Performance Tier 2 in Section 9.36. of the NBC.

Failure to develop a Tier 2 prescriptive compliance path would limit Code users to having to choose between following the trade-off compliance path or relying on performance-based requirements that use energy modeling to achieve the Tier 2 energy-efficiency targets.

Justification

The proposed prescriptive requirements for Energy Performance Tier 2 would provide acceptable solutions to improve the total energy performance of the building. With the tiered energy performance path in Subsection 9.36.7. and the tiered points-based prescriptive trade-off path in Subsection 9.36.8., the prescriptive path is one of the compliance options that provide an acceptable means of achieving the performance goal of reducing energy consumption by at least 10% and reducing the percentage heat loss by at least 5% for buildings with conditioned volumes over 300 m3. Buildings with conditioned volumes less than or equal to 300 m3 have a performance goal of 0% improvement compared to Energy Performance Tier 1, as shown in Table 9.36.7.2. of the NBC 2025, and would therefore comply with the minimum prescriptive requirements.

In developing the acceptable solutions in the Tier 2 prescriptive path, many different possible solutions were considered and compared against the points-based prescriptive trade-off path to ensure compliance.

 

1.  Building Envelope

A Tier 2 building envelope package was developed for each climate zone for buildings having a conditioned volume greater than 300 m3. The 240 modeled building archetypes were separated by volume, with 219 building archetypes having a conditioned volume greater than 300 m3 and 21 having a conditioned volume of less than or equal to 300 m3.

Two criteria were used to define acceptable Tier 2 building envelope package solutions:

(1)  At least 80% of the building archetypes had to comply with the Tier 2 requirement for percentage heat loss reduction of 5% for volumes greater than 300 m3; and

(2)  On average, the building archetypes had to have a peak heating load less than their reference building.

Numerous combinations of building envelope measures met the criteria noted above. Therefore, additional selection criteria needed to be defined to reduce the number of prescriptive building envelope package solutions to one for each climate zone and building volume.

The two additional criteria were:

(1)  incremental costs had to be minimized to make a solution desirable, and

(2)  component performance of the building envelope had to consistently increase across climate zones.

A fourth criterion was defined to exclude solutions having reduced thermal performance of the building envelope component (e.g., insulation) in colder climate zones. For example, a solution that uses 4.88 RSI for the effective thermal resistance of above-grade walls in climate zone 6 would not be used if the solution for climate zone 5 used 5.69 RSI for above-grade walls.

 

2.  Airtightness

There is no mandatory airtightness level needed to achieve Tier 2.

 

3.  Heat/Energy Recovery Ventilators (HRVs/ERVs)

The use of HRVs/ERVs was considered an easy and economical way to save energy; therefore, it was proposed that all Tier 2 houses should be equipped with HRVs/ERVs with minimum 60% sensible recovery efficiency for climate zones 4 and 5, and minimum 70% sensible recovery efficiency for climate zones 6 to 8. Since HRVs/ERVs are required for the Tier 1 building envelope package, they are maintained in the Tier 2 building envelope package.

 

4.  Service Water Heating Systems

No upgrades above Code-minimum service water heating systems are required to achieve Tier 2.

PROPOSED CHANGE

[9.36.11.] -- Tiered Energy Compliance: Tier 2 Prescriptive Path

[9.36.11.1.] ---Scope and Application

[1] --)This Subsection is concerned with achieving compliance with Energy Performance Tier 2, as specified in Table 9.36.7.2., through prescriptive requirements.
[2] --)This Subsection applies only to buildings that are equipped with a heat/energy recovery ventilator conforming to Article 9.36.3.9. (See Note-A-9.36.11.1.(2).)

[9.36.11.2.] ---Compliance

[1] --)Compliance with this Subsection shall be achieved by
[a] --)designing and constructing the building envelope in accordance with Articles 9.36.2.1. to 9.36.2.5. and 9.36.11.3. to 9.36.11.5.,
[b] --)designing and constructing systems and equipment for heating, ventilating or air-conditioning in accordance with Article 9.36.11.6., and
[c] --)designing and constructing systems and equipment for service water heating in accordance with Subsection 9.36.4.

[9.36.11.3.] --- Above-Ground Opaque Building Assemblies

[1] --)Except as provided in Article 9.36.2.5. and Sentence 9.36.2.6.(3), the effective thermal resistance of above-ground opaque building assemblies or portions thereof shall be not less than that shown for the applicable heating-degree day category of the building location in
[a] --)Table 9.36.11.3., where the total volume of conditioned space within the building is greater than 300 m3 or not determined, or
[b] --)Article 9.36.2.6., where the total volume of conditioned space within the building is less than or equal to 300 m3.
Table [9.36.11.3.]
Tier 2 Effective Thermal Resistance of Above-Ground Opaque Assemblies in Buildings with a Total Volume of Conditioned Space > 300 m3
Forming Part of Clause 9.36.11.3.(1)(a)
Above-Ground Opaque Building Assembly Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (1) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Minimum Effective Thermal Resistance (RSI), (m2×K)/W
Ceilings below attics 6.91 8.67 10.43 10.43 10.43 10.43
Cathedral ceilings and flat roofs 4.67 4.67 5.02 5.02 5.02 5.02
Walls 3.08 3.08 3.08 3.08 3.85 3.85
Floors over unheated spaces 4.67 4.67 4.67 5.02 5.02 5.02
[2] --)Where the top of a section of foundation wall is on average greater than or equal to 600 mm abovethe adjoining ground level, the effective thermal resistance of theabove-ground portion of that section of wall shall be not less thanthat of the above-ground walls.
[3] --)Except for tubular daylighting devices, the effective thermalresistance of skylight shafts shall be not less than that of the above-groundwalls.

[9.36.11.4.] ---Fenestration, Doors and Skylights

[1] --)Except as provided in Sentences (2) to (8), fenestration anddoors shall have an overall thermal transmittance (U-value) not greaterthan, or an Energy Rating not less than, that shown in Table 9.36.11.4.for the applicable heating degree-days of the building location. (See Note A-9.36.2.7.(1) and (3).)
Table [9.36.11.4.]
Tier 2 Thermal Characteristics of Fenestration and Doors
Forming Part of Sentence 9.36.11.4.(1)
Component Thermal CharacteristicsPROPOSED CHANGE Table Footnote (1) Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Windows and sliding glass doors Max. U-value, W/(m2×K) 1.61 1.22 1.22 1.22 1.05 1.05
Min. Energy Rating 25 34 34 34 40 40
[2] --)The solar heat gain coefficient of fenestration and doors shallcomply with Sentence 9.36.2.7.(2).
[3] --)Skylights shall have an overall thermal transmittance not greaterthan the values listed in Table 9.36.2.7.-C for the applicable heating-degreeday category. (See Note A-9.36.2.7.(1) and (3).)
[4] --)Glass block assemblies separating conditionedspace from unconditioned space or the exterior shall have
[a] --)a U-value of not more than 2.9 W/(m2×K), and
[b] --)a total aggregate area of not more than 1.85 m2.
[5] --)One door separating a conditioned space from an unconditioned space or the exterior is permitted to havea U-value up to 2.6 W/(m2×K).
[6] --)Storm windows and doors need not comply with Sentence (1).
[7] --)Vehicular access doors separating a conditionedspace from an unconditioned space or the exterior shall havea nominal thermal resistance of not less than 1.1 (m2×K)/W.
[8] --)Access hatches separating a conditionedspace from an unconditioned space shall be insulated to a nominalthermal resistance of not less than 2.6 (m2×K)/W.

[9.36.11.5.] ---Opaque Building Assemblies Below-Grade or in Contact with theGround

[1] --)Opaque building assemblies below-grade or in contact with the ground shall bedesigned and constructed in accordance with Sentence 9.36.2.8.(3)and this Article.
[2] --)Except as provided in Article 9.36.2.5., the effective thermalresistance of foundation walls shall benot less than that shown for the applicable heating degree-days ofthe building location in
[a] --)Table 9.36.11.5., where the total volume of conditioned space within the building is greater than 300 m3 or not determined,or
[b] --)Article 9.36.2.8., where the total volume of conditioned space within the building is less than or equal to 300 m3.
Table [9.36.11.5.]
Tier 2 Effective Thermal Resistance of Assemblies Below-Grade or in Contact with the Ground in Buildings with a Total Volume of Conditioned Space > 300 m3
Forming Part of Clause 9.36.11.5.(2)(a)
Building Assembly Below-Grade or in Contact with the GroundPROPOSED CHANGE Table Footnote (1) Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Minimum Effective Thermal Resistance (RSI), (m2×K)/W
Foundation walls 2.98 2.98 3.46 3.97 3.97 3.97
Unheated floorsPROPOSED CHANGE Table Footnote (3) below frost linePROPOSED CHANGE Table Footnote (4)PROPOSED CHANGE Table Footnote (5) uninsulated uninsulated uninsulated uninsulated uninsulated uninsulated
Unheated floorsPROPOSED CHANGE Table Footnote (3) above frost linePROPOSED CHANGE Table Footnote (5) 1.96 1.96 1.96 1.96 1.96 1.96
Heated and unheated floors on permafrost 4.44 4.44
Heated floorsPROPOSED CHANGE Table Footnote (6) 2.32 2.32 2.32 2.84 2.84 2.84
Slabs-on-grade with an integral footingPROPOSED CHANGE Table Footnote (6) 1.96 1.96 2.84 2.84 2.84 3.72

[9.36.11.6.] ---HVAC Systems

[1] --)HVAC systems, equipment and installations shall be designedand constructed in accordance with Articles 9.36.3.2. to 9.36.3.8.and 9.36.3.11. and this Article.
[2] --)Where HVAC systems, equipment or techniques other than thosedescribed in Articles 9.36.3.2. to 9.36.3.8. and 9.36.3.11. and thisArticle are used, the building shall bedesigned and constructed in accordance with the energy efficiencyrequirements of the NECB.
[3] --)Ventilation systems serving buildings to which this Subsection applies shall be equipped with a heat/energyrecovery ventilator conforming to Article 9.36.3.9.
[4] --)The sensible recovery efficiency (SRE) measured at an outsideair test temperature of 0°C of the heat/energy recovery ventilatordescribed in Sentence (3) shall be not less than
[a] --)60% for climate zones 4 and 5, or
[b] --)70% for climate zones 6, 7A, 7B and 8.

Note A-9.36.11.1.(2)Other Compliance Options.

Buildings that do not comply with requirements of the Tier2 prescriptive path set out in Subsection 9.36.11. are permitted tomeet the requirements of the performance path (Subsection 9.36.7.or 9.36.8.)or the points-based prescriptive trade-off path (Subsection 9.36.9.)to achieve the Tier 2 energy performance target provided in Table9.36.7.2.

Impact analysis

This proposed change would improve energy performance by following the prescriptive requirements for building envelopes and HVAC systems to achieve Energy Performance Tier 2. Detailed costing data can be found in the supporting document. The total incremental cost to achieve Tier 2 is a very small percentage of the total construction cost.

Buildings with a total volume of conditioned space of less than or equal to 300 m3 have the following energy performance: a percent improvement of ≥ 0%, a percent energy target of ≤ 100% and a percent heat loss reduction of ≥ 0%.

Buildings with a total volume of conditioned space of greater than 300 m3 have the following energy performance: a percent improvement of ≥ 10%, a percent energy target of ≤ 90% and a percent heat loss reduction of ≥ 5%.

Archetype A1 - Apartment/condominium unit, one bedroom

Table 1. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A1

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 13.93
Floor area 46.30
Insulated attic area 46.30
Window area 2.36
Conditioned Space Total Volume, m3
Conditioned space 105.45

There is no incremental cost compared to Tier 1 for Archetype A1 as the building volume is less than 300 m3.

Archetype A2 - Bungalow, detached without basement or garage

Table 2. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A2

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 126.05
Ground floor area 95.00
Slabs-on-grade 101.7
Insulated attic area 95.00
Window area 10.75
Conditioned Space Total Volume, m3
Conditioned space 217.44

There is no incremental cost compared to Tier 1 for Archetype A2 as the building volume is less than 300 m3.

Archetype A3 - Bungalow, detached with basement and garage

Table 3. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A3

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 69.49
Foundation walls 46.10
Ground floor area 90.45
Insulated attic area 90.45
Window area 19.74
Conditioned Space Total Volume, m3
Conditioned space 411.36

Table 4. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A3

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceilings below attics 0.00 0.00 760.68 0.00 0.00 0.00
Above-grade walls –301.59* 0.00 0.00 0.00 0.00 0.00
Foundation walls 1,141.44 0.00 23.05 24.43 24.43 0.00
Unheated floors above frost line 0.00 0.00 0.00 0.00 0.00 0.00
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 759.79 1,765.35 1,005.56 1,005.56 911.99 911.99
HRV/ERV 0.00 0.00 200.00 200.00 200.00 200.00
TOTAL 1,599.64 1,765.35 1,989.29 1,229.99 1,136.42 1,111.99

*See supplemental document Section 3.4.

Archetype A4 - 2-storey, detached

Table 5. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A4

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 142.78
Foundation walls 22.69
Ground floor area 57.25
Insulated attic area 70.56
Window area 15.74
Conditioned Space Total Volume, m3
Conditioned space 427.46

Table 6. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A4

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceilings below attics 0.00 0.00 593.41 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –619.67* 0.00 0.00 0.00 0.00 0.00
Foundation walls 561.80 0.00 11.35 12.03 12.03 0.00
Unheated floors below frost line 0.00 0.00 0.00 0.00 0.00 0.00
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 605.83 1,407.63 801.80 801.80 727.19 727.19
HRV/ERV 0.00 0.00 200.00 200.00 200.00 200.00
TOTAL 547.97 1,407.63 1,606.55 1,013.82 939.21 927.19

 *See supplemental document Section 3.4.

Archetype A5 - Row house, 2-storey

Table 7. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A5 (Mid-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 38.44
Foundation walls 7.14
Ground floor area 54.50
Insulated attic area 74.05
Window area 12.12
Conditioned Space Total Volume, m3
Conditioned space 425.35

Table 8. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A5 (Mid-Unit)

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceilings below attics 0.00 0.00 622.76 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –166.83* 0.00 0.00 0.00 0.00 0.00
Foundation walls 176.79 0.00 3.57 3.78 3.78 0.00
Unheated floors below frost line 0.00 0.00 0.00 0.00 0.00 0.00
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 466.50 1,083.89 617.39 617.39 559.94 559.94
HRV/ERV 0.00 0.00 200.00 200.00 200.00 200.00
TOTAL COST 476.46 1,083.89 1,443.72 821.18 763.73 759.94

 *See supplemental document Section 3.4.


Table 9. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A5 (End-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 90.34
Foundation walls 16.14
Ground floor area 54.50
Insulated attic area 74.05
Window area 13.59
Conditioned Space Total Volume, m3
Conditioned space 425.35

Table 10. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A5 (End-Unit)

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceilings below attics 0.00 0.00 622.76 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –392.08* 0.00 0.00 0.00 0.00 0.00
Foundation walls 399.63 0.00 8.07 8.55 8.55 0.00
Unheated floors below frost line 0.00 0.00 0.00 0.00 0.00 0.00
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 523.08 1,215.35 692.27 692.27 627.86 627.86
HRV/ERV 0.00 0.00 200.00 200.00 200.00 200.00
TOTAL COST 530.63 1,215.35 1,523.11 900.83 836.41 827.86

 *See supplemental document Section 3.4.

Archetype A6 - Row house, stacked 3-storey

Table 11. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Mid-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 65.51
Foundation walls 11.28
Ground floor area 58.07
Insulated attic area 59.85
Window area 20.92
Conditioned Space Total Volume, m3
Conditioned space 563.67

Table 12. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A6 (Mid-Unit)

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceilings below attics 0.00 0.00 503.34 0.00 0.00 0.00
Above-grade walls –284.31* 0.00 0.00 0.00 0.00 0.00
Foundation walls 279.29 0.00 5.64 5.98 5.98 0.00
Unheated floors above frost line 0.00 0.00 0.00 0.00 0.00 0.00
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 597.36 1,870.88 1,065.66 1,065.66 966.50 966.50
HRV/ERV 0.00 0.00 200.00 200.00 200.00 200.00
TOTAL COST 592.34 1,870.88 1,774.64 1,271.64 1,172.48 1,166.50

 *See supplemental document Section 3.4.


Table 13. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A6(End-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 160.39
Foundation walls 29.43
Ground floor area 58.07
Insulated attic area 59.85
Window area 24.50
Conditioned Space Total Volume, m3
Conditioned space 563.67

Table 14. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A6(End-Unit)

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceilings below attics 0.00 0.00 503.34 0.00 0.00 0.00
Above-grade walls –696.09* 0.00 0.00 0.00 0.00 0.00
Foundation walls 728.69 0.00 14.72 15.60 15.60 0.00
Unheated floors above frost line 0.00 0.00 0.00 0.00 0.00 0.00
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 943.01 2,191.04 1,248.03 1,248.03 1,131.90 1,131.90
HRV/ERV 0.00 0.00 200.00 200.00 200.00 200.00
TOTAL COST 975.60 2,191.04 1,966.08 1,463.63 1,347.50 1,331.90

 *See supplemental document Section 3.4.

Table 15. Climate Zones by Region

Degree-Days Below 18°C BC Alberta Saskatchewan and Manitoba Ontario Quebec Atlantic Canada Northern Canada
Zone 4: HDD < 3000 Yes No No No No No No
Zone 5: HDD 3000 to 3999 Yes No No Yes No Yes No
Zone 6: HDD 4000 to 4999 Yes Yes Yes Yes Yes Yes No
Zone 7A: HDD 5000 to 5999 Yes Yes Yes Yes Yes Yes No
Zone 7B: HDD 6000 to 6999 Yes Yes Yes Yes Yes Yes Yes
Zone 8: HDD ≥ 7000 Yes Yes Yes Yes Yes Yes Yes

Table 16. Incremental Cost to Achieve Tier 2 Compared to Tier 1 for Each Archetype by Region

Archetype Incremental Cost, $
BC Alberta Saskatchewan and Manitoba Ontario Quebec Atlantic
Canada
Northern Canada
Archetype A1 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Archetype A2 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Archetype A3 1,111.99–1,989.29 1,111.99–1,989.29 1,111.99–1,989.29 1,111.99–1,989.29 1,111.99–1,989.29 1,111.99–1,989.29 1,111.99–1,136.42
Archetype A4 547.97–1,606.55 927.19–1,606.55 927.19–1,606.55 927.19–1,606.55 927.19–1,606.55 927.19–1,606.55 927.19–939.21
Archetype A5 Mid-unit 476.46–1,443.72 759.94–1,443.72 759.94–1,443.72 759.94–1,443.72 759.94–1,443.72 759.94–1,443.72 759.94–763.73
End-unit 530.63–1,523.11 827.86–1,523.11 827.86–1,523.11 827.86–1,523.11 827.86–1,523.11 827.86–1,523.11 827.86–836.41
Archetype A6 Mid-unit 592.34–1,870.88 1,166.50–1,774.64 1,166.50–1,774.64 1,166.50–1,870.88 1,166.50–1,774.64 1,166.50–1,870.88 1,166.50–1,172.48
End-unit 975.60–2,191.04 1,331.90–1,966.08 1,331.90–1,966.08 1,331.90–2,191.04 1,331.90–1,966.08 1,331.90–2,191.04 1,331.90–1,347.50

Enforcement implications

This proposed change could be enforced by the infrastructure currently available to enforce the Code. 

This proposed change would facilitate the effective enforcement of high-performance energy solutions in jurisdictions where complying with the performance path presents challenges.

Who is affected

Regulators, builders, designers, engineers, architects, contractors and consultants in provinces and territories where Energy Performance Tier 2 has been adopted for housing and small buildings.

Supporting Document(s)

OBJECTIVE-BASED ANALYSIS OF NEW OR CHANGED PROVISIONS

[9.36.11.1.] -- ([1] --)no attributions
[9.36.11.1.] -- ([2] --)no attributions
[9.36.11.1.] -- ([2] --)[F95,F100-OE1.1]
[9.36.11.2.] -- ([1] --)no attributions
[9.36.11.3.] -- ([1] --)no attributions
[9.36.11.3.] -- ([1] --)no attributions
[9.36.11.3.] -- ([1] --)[F92-OE1.1]
[9.36.11.3.] -- ([2] --)[F92-OE1.1]
[9.36.11.3.] -- ([3] --)[F92-OE1.1]
[9.36.11.4.] -- ([1] --)[F92-OE1.1]
[9.36.11.4.] -- ([2] --)no attributions
[9.36.11.4.] -- ([3] --)[F92-OE1.1]
[9.36.11.4.] -- ([4] --)[F92-OE1.1]
[9.36.11.4.] -- ([5] --)[F92-OE1.1]
[9.36.11.4.] -- ([6] --)no attributions
[9.36.11.4.] -- ([7] --)[F92-OE1.1]
[9.36.11.4.] -- ([8] --)[F92-OE1.1]
[9.36.11.5.] -- ([1] --)no attributions
[9.36.11.5.] -- ([1] --)no attributions
[9.36.11.5.] -- ([2] --)no attributions
[9.36.11.5.] -- ([2] --)[F92-OE1.1]
[9.36.11.6.] -- ([1] --)no attributions
[9.36.11.6.] -- ([2] --)no attributions
[9.36.11.6.] -- ([3] --)no attributions
[9.36.11.6.] -- ([3] --)[F95,F100-OE1.1]
[9.36.11.6.] -- ([4] --)[F95,F98,F100-OE1.1]
Date modified: