The 2020 edition of the National Building Code of Canada (NBC) introduced energy-efficiency performance tiers in Section 9.36. of Division B, with increasing levels of improvement for buildings and houses, to provide jurisdictions with the option to adopt the most suitable energy performance level or their needs.
Although performance modeling is a common practice, many Code users have requested that prescriptive compliance paths remain in the National Model Codes to simplify achieving energy compliance. However, there are currently only performance requirements and prescriptive trade-off requirements for Energy Performance Tier 2 in Section 9.36. of the NBC.
Failure to develop a Tier 2 prescriptive compliance path would limit Code users to having to choose between following the trade-off compliance path or relying on performance-based requirements that use energy modeling to achieve the Tier 2 energy-efficiency targets.
The proposed prescriptive requirements for Energy Performance Tier 2 would provide acceptable solutions to improve the total energy performance of the building. With the tiered energy performance path in Subsection 9.36.7. and the tiered points-based prescriptive trade-off path in Subsection 9.36.8., the prescriptive path is one of the compliance options that provide an acceptable means of achieving the performance goal of reducing energy consumption by at least 10% and reducing the percentage heat loss by at least 5% for buildings with conditioned volumes over 300 m3. Buildings with conditioned volumes less than or equal to 300 m3 have a performance goal of 0% improvement compared to Energy Performance Tier 1, as shown in Table 9.36.7.2. of the NBC 2025, and would therefore comply with the minimum prescriptive requirements.
In developing the acceptable solutions in the Tier 2 prescriptive path, many different possible solutions were considered and compared against the points-based prescriptive trade-off path to ensure compliance.
1. Building Envelope
A Tier 2 building envelope package was developed for each climate zone for buildings having a conditioned volume greater than 300 m3. The 240 modeled building archetypes were separated by volume, with 219 building archetypes having a conditioned volume greater than 300 m3 and 21 having a conditioned volume of less than or equal to 300 m3.
Two criteria were used to define acceptable Tier 2 building envelope package solutions:
(1) At least 80% of the building archetypes had to comply with the Tier 2 requirement for percentage heat loss reduction of 5% for volumes greater than 300 m3; and
(2) On average, the building archetypes had to have a peak heating load less than their reference building.
Numerous combinations of building envelope measures met the criteria noted above. Therefore, additional selection criteria needed to be defined to reduce the number of prescriptive building envelope package solutions to one for each climate zone and building volume.
The two additional criteria were:
(1) incremental costs had to be minimized to make a solution desirable, and
(2) component performance of the building envelope had to consistently increase across climate zones.
A fourth criterion was defined to exclude solutions having reduced thermal performance of the building envelope component (e.g., insulation) in colder climate zones. For example, a solution that uses 4.88 RSI for the effective thermal resistance of above-grade walls in climate zone 6 would not be used if the solution for climate zone 5 used 5.69 RSI for above-grade walls.
2. Airtightness
There is no mandatory airtightness level needed to achieve Tier 2.
3. Heat/Energy Recovery Ventilators (HRVs/ERVs)
The use of HRVs/ERVs was considered an easy and economical way to save energy; therefore, it was proposed that all Tier 2 houses should be equipped with HRVs/ERVs with minimum 60% sensible recovery efficiency for climate zones 4 and 5, and minimum 70% sensible recovery efficiency for climate zones 6 to 8. Since HRVs/ERVs are required for the Tier 1 building envelope package, they are maintained in the Tier 2 building envelope package.
4. Service Water Heating Systems
No upgrades above Code-minimum service water heating systems are required to achieve Tier 2.
| Above-Ground Opaque Building Assembly | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (1) in Celsius Degree-Days | |||||
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
|
| Minimum Effective Thermal Resistance (RSI), (m2×K)/W | ||||||
| Ceilings below attics | 6.91 | 8.67 | 10.43 | 10.43 | 10.43 | 10.43 |
| Cathedral ceilings and flat roofs | 4.67 | 4.67 | 5.02 | 5.02 | 5.02 | 5.02 |
| Walls | 3.08 | 3.08 | 3.08 | 3.08 | 3.85 | 3.85 |
| Floors over unheated spaces | 4.67 | 4.67 | 4.67 | 5.02 | 5.02 | 5.02 |
| Component | Thermal CharacteristicsPROPOSED CHANGE Table Footnote (1) | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days | |||||
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
||
| Windows and sliding glass doors | Max. U-value, W/(m2×K) | 1.61 | 1.22 | 1.22 | 1.22 | 1.05 | 1.05 |
| Min. Energy Rating | 25 | 34 | 34 | 34 | 40 | 40 | |
| Building Assembly Below-Grade or in Contact with the GroundPROPOSED CHANGE Table Footnote (1) | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days | |||||
|---|---|---|---|---|---|---|
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
|
| Minimum Effective Thermal Resistance (RSI), (m2×K)/W | ||||||
| Foundation walls | 2.98 | 2.98 | 3.46 | 3.97 | 3.97 | 3.97 |
| Unheated floorsPROPOSED CHANGE Table Footnote (3) below frost linePROPOSED CHANGE Table Footnote (4)PROPOSED CHANGE Table Footnote (5) | uninsulated | uninsulated | uninsulated | uninsulated | uninsulated | uninsulated |
| Unheated floorsPROPOSED CHANGE Table Footnote (3) above frost linePROPOSED CHANGE Table Footnote (5) | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 |
| Heated and unheated floors on permafrost | – | – | – | – | 4.44 | 4.44 |
| Heated floorsPROPOSED CHANGE Table Footnote (6) | 2.32 | 2.32 | 2.32 | 2.84 | 2.84 | 2.84 |
| Slabs-on-grade with an integral footingPROPOSED CHANGE Table Footnote (6) | 1.96 | 1.96 | 2.84 | 2.84 | 2.84 | 3.72 |
This proposed change would improve energy performance by following the prescriptive requirements for building envelopes and HVAC systems to achieve Energy Performance Tier 2. Detailed costing data can be found in the supporting document. The total incremental cost to achieve Tier 2 is a very small percentage of the total construction cost.
Buildings with a total volume of conditioned space of less than or equal to 300 m3 have the following energy performance: a percent improvement of ≥ 0%, a percent energy target of ≤ 100% and a percent heat loss reduction of ≥ 0%.
Buildings with a total volume of conditioned space of greater than 300 m3 have the following energy performance: a percent improvement of ≥ 10%, a percent energy target of ≤ 90% and a percent heat loss reduction of ≥ 5%.
Table 1. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A1
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 13.93 |
| Floor area | 46.30 |
| Insulated attic area | 46.30 |
| Window area | 2.36 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 105.45 |
There is no incremental cost compared to Tier 1 for Archetype A1 as the building volume is less than 300 m3.
Table 2. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A2
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 126.05 |
| Ground floor area | 95.00 |
| Slabs-on-grade | 101.7 |
| Insulated attic area | 95.00 |
| Window area | 10.75 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 217.44 |
There is no incremental cost compared to Tier 1 for Archetype A2 as the building volume is less than 300 m3.
Table 3. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A3
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 69.49 |
| Foundation walls | 46.10 |
| Ground floor area | 90.45 |
| Insulated attic area | 90.45 |
| Window area | 19.74 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 411.36 |
Table 4. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A3
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceilings below attics | 0.00 | 0.00 | 760.68 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –301.59* | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Foundation walls | 1,141.44 | 0.00 | 23.05 | 24.43 | 24.43 | 0.00 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 759.79 | 1,765.35 | 1,005.56 | 1,005.56 | 911.99 | 911.99 |
| HRV/ERV | 0.00 | 0.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| TOTAL | 1,599.64 | 1,765.35 | 1,989.29 | 1,229.99 | 1,136.42 | 1,111.99 |
*See supplemental document Section 3.4.
Table 5. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A4
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 142.78 |
| Foundation walls | 22.69 |
| Ground floor area | 57.25 |
| Insulated attic area | 70.56 |
| Window area | 15.74 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 427.46 |
Table 6. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A4
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceilings below attics | 0.00 | 0.00 | 593.41 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –619.67* | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Foundation walls | 561.80 | 0.00 | 11.35 | 12.03 | 12.03 | 0.00 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 605.83 | 1,407.63 | 801.80 | 801.80 | 727.19 | 727.19 |
| HRV/ERV | 0.00 | 0.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| TOTAL | 547.97 | 1,407.63 | 1,606.55 | 1,013.82 | 939.21 | 927.19 |
*See supplemental document Section 3.4.
Table 7. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A5 (Mid-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 38.44 |
| Foundation walls | 7.14 |
| Ground floor area | 54.50 |
| Insulated attic area | 74.05 |
| Window area | 12.12 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 425.35 |
Table 8. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A5 (Mid-Unit)
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceilings below attics | 0.00 | 0.00 | 622.76 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –166.83* | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Foundation walls | 176.79 | 0.00 | 3.57 | 3.78 | 3.78 | 0.00 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 466.50 | 1,083.89 | 617.39 | 617.39 | 559.94 | 559.94 |
| HRV/ERV | 0.00 | 0.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| TOTAL COST | 476.46 | 1,083.89 | 1,443.72 | 821.18 | 763.73 | 759.94 |
*See supplemental document Section 3.4.
Table 9. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A5 (End-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 90.34 |
| Foundation walls | 16.14 |
| Ground floor area | 54.50 |
| Insulated attic area | 74.05 |
| Window area | 13.59 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 425.35 |
Table 10. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A5 (End-Unit)
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceilings below attics | 0.00 | 0.00 | 622.76 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –392.08* | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Foundation walls | 399.63 | 0.00 | 8.07 | 8.55 | 8.55 | 0.00 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 523.08 | 1,215.35 | 692.27 | 692.27 | 627.86 | 627.86 |
| HRV/ERV | 0.00 | 0.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| TOTAL COST | 530.63 | 1,215.35 | 1,523.11 | 900.83 | 836.41 | 827.86 |
*See supplemental document Section 3.4.
Table 11. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Mid-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 65.51 |
| Foundation walls | 11.28 |
| Ground floor area | 58.07 |
| Insulated attic area | 59.85 |
| Window area | 20.92 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 563.67 |
Table 12. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A6 (Mid-Unit)
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceilings below attics | 0.00 | 0.00 | 503.34 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –284.31* | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Foundation walls | 279.29 | 0.00 | 5.64 | 5.98 | 5.98 | 0.00 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 597.36 | 1,870.88 | 1,065.66 | 1,065.66 | 966.50 | 966.50 |
| HRV/ERV | 0.00 | 0.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| TOTAL COST | 592.34 | 1,870.88 | 1,774.64 | 1,271.64 | 1,172.48 | 1,166.50 |
*See supplemental document Section 3.4.
Table 13. Total Area of the Building Envelope Components and Total Volume of Conditioned Space of Archetype A6(End-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 160.39 |
| Foundation walls | 29.43 |
| Ground floor area | 58.07 |
| Insulated attic area | 59.85 |
| Window area | 24.50 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 563.67 |
Table 14. Incremental Cost to Achieve Tier 2 Compared to Tier 1 in Archetype A6(End-Unit)
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceilings below attics | 0.00 | 0.00 | 503.34 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –696.09* | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Foundation walls | 728.69 | 0.00 | 14.72 | 15.60 | 15.60 | 0.00 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 943.01 | 2,191.04 | 1,248.03 | 1,248.03 | 1,131.90 | 1,131.90 |
| HRV/ERV | 0.00 | 0.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| TOTAL COST | 975.60 | 2,191.04 | 1,966.08 | 1,463.63 | 1,347.50 | 1,331.90 |
*See supplemental document Section 3.4.
Table 15. Climate Zones by Region
| Degree-Days Below 18°C | BC | Alberta | Saskatchewan and Manitoba | Ontario | Quebec | Atlantic Canada | Northern Canada |
| Zone 4: HDD < 3000 | Yes | No | No | No | No | No | No |
| Zone 5: HDD 3000 to 3999 | Yes | No | No | Yes | No | Yes | No |
| Zone 6: HDD 4000 to 4999 | Yes | Yes | Yes | Yes | Yes | Yes | No |
| Zone 7A: HDD 5000 to 5999 | Yes | Yes | Yes | Yes | Yes | Yes | No |
| Zone 7B: HDD 6000 to 6999 | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
| Zone 8: HDD ≥ 7000 | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Table 16. Incremental Cost to Achieve Tier 2 Compared to Tier 1 for Each Archetype by Region
| Archetype | Incremental Cost, $ | |||||||
| BC | Alberta | Saskatchewan and Manitoba | Ontario | Quebec | Atlantic Canada |
Northern Canada | ||
| Archetype A1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Archetype A2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Archetype A3 | 1,111.99–1,989.29 | 1,111.99–1,989.29 | 1,111.99–1,989.29 | 1,111.99–1,989.29 | 1,111.99–1,989.29 | 1,111.99–1,989.29 | 1,111.99–1,136.42 | |
| Archetype A4 | 547.97–1,606.55 | 927.19–1,606.55 | 927.19–1,606.55 | 927.19–1,606.55 | 927.19–1,606.55 | 927.19–1,606.55 | 927.19–939.21 | |
| Archetype A5 | Mid-unit | 476.46–1,443.72 | 759.94–1,443.72 | 759.94–1,443.72 | 759.94–1,443.72 | 759.94–1,443.72 | 759.94–1,443.72 | 759.94–763.73 |
| End-unit | 530.63–1,523.11 | 827.86–1,523.11 | 827.86–1,523.11 | 827.86–1,523.11 | 827.86–1,523.11 | 827.86–1,523.11 | 827.86–836.41 | |
| Archetype A6 | Mid-unit | 592.34–1,870.88 | 1,166.50–1,774.64 | 1,166.50–1,774.64 | 1,166.50–1,870.88 | 1,166.50–1,774.64 | 1,166.50–1,870.88 | 1,166.50–1,172.48 |
| End-unit | 975.60–2,191.04 | 1,331.90–1,966.08 | 1,331.90–1,966.08 | 1,331.90–2,191.04 | 1,331.90–1,966.08 | 1,331.90–2,191.04 | 1,331.90–1,347.50 | |
This proposed change could be enforced by the infrastructure currently available to enforce the Code.
This proposed change would facilitate the effective enforcement of high-performance energy solutions in jurisdictions where complying with the performance path presents challenges.
Regulators, builders, designers, engineers, architects, contractors and consultants in provinces and territories where Energy Performance Tier 2 has been adopted for housing and small buildings.