Page: Last modified: 2024-01-02
Code Reference(s):
NBC20 Div.C 2.2.8.2.(1) (first printing)
Subject:
Airtightness
Title:
Using NLR50 in Administrative Documents
Description:
This proposed change modifies the airtightness metric required on drawings and specifications for the proposed house.
This change could potentially affect the following topic areas:

Problem

Where an airtightness test is used to determine the airtightness of a proposed house, the measured airtightness of the building envelope must be reported in ACH50 (air changes per hour at 50 Pa pressure differential) on the drawings and specifications for the proposed house as required by the National Building Code of Canada (NBC) 2020. A related proposed change (PCF 1819) uses NLR50 (normalized leakage rate at 50 Pa pressure differential) as the regulated airtightness metric in the NBC.

To prevent confusion and enforcement issues associated with PCF 1819, the administrative provisions of the Code should also be revised to require the NLR50 metric to be provided on the drawings and specifications for the proposed house.

Justification

NLR50 (in L/(s×m2)) is an airtightness metric that is based on the airtightness of assemblies and surfaces, which is in turn directly aligned with the materials used and the assemblies built by the builders during construction. The prescriptive requirements in Subsection 9.25.3. address the airtightness of materials and assemblies as a means of achieving a continuous air barrier system that is a part of the building envelope. The required airtightness of this system should not vary with the size or geometry of the house being constructed, yet relying on a volumetric target such as ACH50 effectively does just that. ACH50 is a volumetric measurement that is calculated as an output of the measured effectiveness of the air barrier assemblies and varies by house size, even where assembly airtightness is consistent. Conversely, NLR50 is a normalized metric, meaning that it is more consistently applicable to a wide variety of housing geometries.

PCF 1819 proposes maintaining the use of ACH50 in Section 9.36. as a calculated value for input into energy models, but ACH50 would be calculated as an output value based on an NLR50 input value and building geometry rather than an assumed value. PCF 1819 would also remove ACH50 from all tables in Section 9.36., which would simplify the requirements.

Using NLR50 instead of ACH50 as the metric to report the measured airtightness on the drawings and specifications for the proposed house would align the administrative requirements with the proposed revision to the technical requirements found in PCF 1819.

PROPOSED CHANGE

[2.2.8.2.] 2.2.8.2.Information Required on Drawings and Specifications

[1] 1)Except as provided in Sentences (2) to (4), the drawings and specifications for the proposed house shall include
[a] a)the effective thermal resistance values and respective areas of all opaque building envelope assemblies, including all above-ground and below-ground roof/ceiling, wall, and floor assemblies,
[b] b)the overall thermal transmittance (U-value), solar heat gain coefficient and respective areas of all fenestration and door components,
[c] c)the ratio of total vertical fenestration and door area to gross wall area,
[d] d)the performance rating, energy source, and types of all equipment required for space-heating and -cooling and service water heating,
[e] e)the design basis for the ventilation rates,
[f] f)the design normalized leakage rate of the building envelope at 50 Pa pressure differential (NLR50) in L/(s×m2), with a pressure exponent of 0.67, where a test is to be used to determine the airtightness of athe house, the measured airtightness of the building envelope in air changes per hour, and
[g] g)any additional features used in the energy model calculations that account for a significant difference in house energy performance.

Impact analysis

PCF 1819 revises Section 9.36. to use NLR50 as the regulated airtightness metric, which provides a more representative assessment of the performance of the air barrier system. Making this change (PCF 1954) would align the requirements for drawings and specifications with airtightness testing practices. Since the Code requires builders to construct assemblies that are airtight, it makes sense to measure the airtightness of these assemblies, aligning technical requirements and enforcement requirements through the use of the NLR50 metric.

Because the conversion between ACH50 and NLR50 requires only the exposed area and volume as inputs (both known quantities when performing a blower door test), and the NLR50 metric is already specified in existing Code requirements, this proposed change would have no additional implementation costs for Code users. The authority having jurisdiction would need to be familiar with the airtightness requirements using the NLR50 metric (i.e., the targeted NLR50 values for different airtightness levels) when reviewing the drawings and specifications for proposed projects.

Using the NLR50 metric instead of the ACH50 metric as a measure of airtightness performance on the drawings and specifications for a proposed house would align the administrative requirements in Division C of the NBC with the revised technical requirements (as proposed in PCF 1819) in Division B.

Enforcement implications

This proposed change could be enforced using existing Code enforcement infrastructure.

Authorities having jurisdiction would need to become familiar with the NLR50 metric if they are not already using it regularly.

Who is affected

Designers, engineers, architects, building officials, manufacturers, suppliers and energy advisors.

 
Date modified: