Français
Page: Last modified: 2024-02-20
Code Reference(s):
NBC20 Div.B 9.36. (first printing)
Subject:
Energy Use Intensity
Title:
Energy Use Intensity Compliance Path
Description:
This proposed change introduces an energy performance compliance path based on the energy use intensity target of the building to Section 9.36.
This change could potentially affect the following topic areas:

Problem

Section 9.36. of Division B of the National Building Code of Canada (NBC) 2020 does not account for the energy savings that Code users can achieve through compact architectural design. Smaller attached houses are subject to the same insulation requirements as larger detached houses with extensive floorplans, even though the smaller houses require much less energy. This approach is not only inconsistent with the environment objective of the NBC (which includes limiting the probability of excessive use of energy), but also unnecessarily burdens Code users who build very efficient houses.

The current energy performance path in Section 9.36. requires Code users to demonstrate that the proposed house uses an equal or smaller amount of energy than an equivalent reference house. In accordance with the modeling rules prescribed by Subsection 9.36.5., the reference house comprises a hypothetical house with similar geometry to that of the proposed design, but it is constructed to the minimum prescriptive requirements of Subsections 9.36.2. to 9.36.4. Accordingly, a proposed house’s energy budget reflects the minimum efficiency requirements of Section 9.36., but varies according to the shape and size of the house. As a result, larger houses benefit from larger energy budgets, while smaller houses must meet smaller energy budgets.

The reference house energy budget also varies with building shape; “compact” designs that minimize heat loss area (e.g., row houses, stacked houses, houses with simple shapes or low ceilings) receive more stringent budgets than extensive designs with greater building envelope area per unit of floor area (e.g., ranch-style detached bungalows). While this framework ensures that all buildings complying with Section 9.36. reflect similar levels of energy efficiency (e.g., through use of insulation, glazing, equipment efficiency), it permits the construction of buildings with varying energy use.

This outcome is inconsistent with the environment objective, which seeks to limit energy use. In addition, the existing performance path needlessly burdens Code users who choose more compact and efficient forms by obliging these Code users to construct very well insulated buildings even though the chosen design form inherently uses much less energy than other Code-compliant houses. These requirements may increase housing costs in affordable and entry-level housing markets, which largely comprise compact housing forms (including attached, row and stacked housing units).

Justification

Introducing an alternate energy performance compliance path based on energy use intensity (EUI) would allow Code users to demonstrate compliance through compact architectural design. This proposed change enables authorities having jurisdiction to recognize the inherent efficiency of attached, row and stacked housing forms and to credit these houses for energy savings relative to other Code-compliant houses.

The proposed EUI compliance path will also enable Code users to benefit from two inherent advantages of absolute energy targets:

  • To better reflect a building’s expected energy consumption.
  • To reduce the administrative burden of the code by eliminating the reference house modelling requirements.

For these reasons, other jurisdictions in Canada (e.g., British Columbia, City of Toronto) and abroad have introduced compliance paths based on absolute energy use metrics. Experiences from those jurisdictions also attest to specific challenges associated with EUI compliance for small dwellings and in local climates. Reflecting those lessons, the proposed EUI approach includes requirements that adapt EUI targets to local heating degree-days and to relax EUI limits for smaller houses.

Overall, this EUI compliance path will provide more flexibility for Code users when designing to the tiered energy requirements of Section 9.36. Under this compliance path, Code users can demonstrate energy savings achieved through smaller, simpler and attached compact architectural forms in addition to insulation and mechanical systems efficiency. The introduction of this compliance path could lead to reduced housing costs in affordable and entry-level housing markets.

Finally, this proposed change does not limit the use of existing compliance paths, including the reference and proposed modeling requirements of Subsections 9.36.5. and 9.36.7. Code users who construct houses with high envelope-to-floor area ratios (including houses on narrow lots, prefabricated houses and houses on piles above permafrost) may still use the enhanced energy efficiency measures prescribed elsewhere in Section 9.36. to meet the energy performance requirements.

PROPOSED CHANGE

[9.36.] 9.36. Energy Efficiency

[9.36.1.] 9.36.1. General

[9.36.1.1.] 9.36.1.1.Scope
[9.36.1.2.] 9.36.1.2.Definitions
[9.36.1.3.] 9.36.1.3.Compliance and Application
(See Note A-9.36.1.3.PROPOSED CHANGE A-9.36.1.3.)
[1] 1)Except as provided in Sentences (2) to (6), buildings shall comply with
[a] a)the prescriptive or trade-off requirements in Subsections 9.36.2. to 9.36.4.,
[b] b)the performance requirements in Subsection 9.36.5.,
[c] c)the tiered performance requirements in Subsection 9.36.7.,
[d] --)the tiered energy use intensity requirements in Subsection 9.36.8.-2025,
[e] d)the tiered prescriptive requirements in Subsection 9.36.8., or
[f] e)the NECB.
[2] 2)Subsections 9.36.2. to 9.36.4. apply to
[a] a)buildings of residential occupancy to which Part 9 applies,
[b] b)buildings containing business and personal services, mercantile or low-hazard industrial occupancies to which Part 9 applies whose combined total floor area does not exceed 300 m2, excluding parking garages that serve residential occupancies, and
[c] c)buildings containing a mix of the residential and non-residential occupancies described in Clauses (a) and (b).
[3] 3)Subsections  9.36.5., and  9.36.7. and 9.36.8.-2025 apply only to
[a] a)houses with or without a secondary suite, and
[b] b)buildings containing only dwelling units and common spaces whose total floor area does not exceed 20% of the total floor area of the building.
(See Note A-9.36.1.3.(3)PROPOSED CHANGE A-9.36.1.3.(3).)
[4] 4)Subsection 9.36.8. applies only to buildings of residential occupancy to which Part 9 applies.
[5] 5)Buildings containing non-residential occupancies whose combined total floor area exceeds 300 m2 or medium-hazard industrial occupancies shall comply with the NECB.
[6] 6)Buildings or portions of buildings that are not required to be conditioned spaces are exempted from the requirements of this Section. (See Note A-9.36.1.3.(6)PROPOSED CHANGE A-9.36.1.3.(6).)

[9.36.2.] 9.36.2. Building Envelope

[9.36.2.1.] 9.36.2.1.Scope and Application
[9.36.2.2.] 9.36.2.2.Determination of Thermal Characteristics of Materials, Components and Assemblies
[9.36.2.3.] 9.36.2.3.Calculation of Ceiling, Wall, Fenestration and Door Areas
[9.36.2.4.] 9.36.2.4.Calculation of Effective Thermal Resistance of Assemblies
[9.36.2.5.] 9.36.2.5.Continuity of Insulation
[9.36.2.6.] 9.36.2.6.Thermal Characteristics of Above-ground Opaque Building Assemblies
[9.36.2.7.] 9.36.2.7.Thermal Characteristics of Fenestration, Doors and Skylights
[9.36.2.8.] 9.36.2.8.Thermal Characteristics of Building Assemblies Below-Grade or in Contact with the Ground
[9.36.2.9.] 9.36.2.9.Airtightness
[9.36.2.10.] 9.36.2.10.Construction of Air Barrier Details
[9.36.2.11.] 9.36.2.11.Trade-off Options for Above-ground Building Envelope Components and Assemblies

[9.36.3.] 9.36.3. HVAC Requirements

[9.36.3.1.] 9.36.3.1.Scope and Application
[9.36.3.2.] 9.36.3.2.Equipment and Ducts
[9.36.3.3.] 9.36.3.3.Air Intake and Outlet Dampers
[9.36.3.4.] 9.36.3.4.Piping for Heating and Cooling Systems
[9.36.3.5.] 9.36.3.5.Equipment for Heating and Air-conditioning Systems
[9.36.3.6.] 9.36.3.6.Temperature Controls
[9.36.3.7.] 9.36.3.7.Humidification
[9.36.3.8.] 9.36.3.8.Heat Recovery from Dehumidification in Spaces with an Indoor Pool or Hot Tub
[9.36.3.9.] 9.36.3.9.Heat Recovery from Ventilation Systems
[9.36.3.10.] 9.36.3.10.Equipment Efficiency
[9.36.3.11.] 9.36.3.11.Solar Thermal Systems

[9.36.4.] 9.36.4. Service Water Heating Systems

[9.36.4.1.] 9.36.4.1.Scope and Application
[9.36.4.2.] 9.36.4.2.Equipment Efficiency
[9.36.4.3.] 9.36.4.3.Solar Domestic Hot Water Systems
[9.36.4.4.] 9.36.4.4.Piping
[9.36.4.5.] 9.36.4.5.Controls
[9.36.4.6.] 9.36.4.6.Indoor Swimming Pool Equipment Controls

[9.36.5.] 9.36.5. Energy Performance Compliance

[9.36.5.1.] 9.36.5.1.Scope and Application
[9.36.5.2.] 9.36.5.2.Definitions
[9.36.5.3.] 9.36.5.3.Compliance
[9.36.5.4.] 9.36.5.4.Calculation Methods
[9.36.5.5.] 9.36.5.5.Climatic Data
[9.36.5.6.] 9.36.5.6.Building Envelope Calculations
[9.36.5.7.] 9.36.5.7.HVAC System Calculations
[9.36.5.8.] 9.36.5.8.Service Water Heating System Calculations
[9.36.5.9.] 9.36.5.9.General Requirements for Modeling the Proposed House
[9.36.5.10.] 9.36.5.10.Modeling Building Envelope of Proposed House
[9.36.5.11.] 9.36.5.11.Modeling HVAC System of Proposed House
[9.36.5.12.] 9.36.5.12.Modeling Service Water Heating System of Proposed House
[9.36.5.13.] 9.36.5.13.General Requirements for Modeling the Reference House
[9.36.5.14.] 9.36.5.14.Modeling Building Envelope of Reference House
[9.36.5.15.] 9.36.5.15.Modeling HVAC System of Reference House
[9.36.5.16.] 9.36.5.16.Modeling Service Water Heating System of Reference House

[9.36.6.] 9.36.6. Airtightness of Building Envelope

[9.36.6.1.] 9.36.6.1.Scope and Application
[9.36.6.2.] 9.36.6.2.Definitions
[9.36.6.3.] 9.36.6.3.Determination of Airtightness
[9.36.6.4.] 9.36.6.4.Determination of Airtightness Level

[9.36.7.] 9.36.7. Tiered Energy Performance Compliance: Performance Path

[9.36.7.1.] 9.36.7.1.Scope and Application
[9.36.7.2.] 9.36.7.2.Compliance
[9.36.7.3.] 9.36.7.3.Energy Performance Improvement Compliance Calculations

[9.36.8.] -- Tiered Energy Performance Compliance: Energy Use Intensity Path

[9.36.8.1.] ---Scope and Application
[1] --)This Subsection is concerned with determining compliance with one of the energy performance tiers through modeling of the energy performance of components, systems and assemblies that are installed in buildings and houses with or without a secondary suite described in Sentence 9.36.1.3.(3).
[2] --)For the purpose of this Subsection, the term “house” shall mean all houses, with or without a secondary suite, that
[a] --)have HVAC systems that serve only the house, only the secondary suite, or both the house and the secondary suite,
[b] --)have service water heating systems that serve only the house, only the secondary suite, or both the house and the secondary suite, and
[c] --)do not share common spaces intended for occupancy with other dwelling units or houses, except for a secondary suite.
[3] --)For the purpose of this Subsection, the term “heated floor area” shall mean the sum of all floor areas served by heating equipment throughout the year, in m².
[4] --)For the purpose of this Subsection, the term “local heat loss factor” shall mean the reference heat loss intensity for local climatic conditions at the building location, in kWh/m² per year, calculated as follows:
Local heat loss factor = (0.02 × HDD) + 32.6
where

 

HDD
= degree-days below 18°C of the building location, determined in accordance with Article 1.1.3.1.
[5] --)For the purpose of this Subsection, the term “local energy use factor” shall mean the reference energy use for local climatic conditions, inkWh/m² per year, calculated as follows:
Local energy use factor = (0.02 × HDD) – 12.3
[9.36.8.2.] ---Compliance
[1] --)Compliance with this Subsection shall be achieved by demonstrating that
[a] --)the annual gross space heat loss of the proposed house calculated in accordance with Sentence 9.36.7.3.(5) does not exceed the annual gross space heat loss target calculated in accordance with Sentence 9.36.8.3.(1)-2025 (see Note A-9.36.7.3.(1)),
[b] --)the design cooling load of the proposed house calculated in accordance with Sentence 9.36.8.4.(1)-2025 does not exceed the design cooling load budget calculated in accordance with Sentence 9.36.8.4.(2)-2025, and
[c] --)the annual energy consumption of the proposed house calculated in accordance with Sentence 9.36.5.4.(1) does not exceed the annual energy consumption target calculated in accordance with Sentence 9.36.8.5.(1)-2025.
[2] --)Except where otherwise stated in this Subsection, the proposed house shall be modeled in accordance with Subsection 9.36.5.
[9.36.8.3.] ---Annual Gross Space Heat Loss
[1] --)The annual gross space heat loss target shall be calculated by multiplying the annual gross space heat loss budget, calculated in accordance with Sentence (2), by the gross space heat loss adjustment factor, as provided in Table 9.36.8.3.-A for the applicable energy performance tier, in kWh per year.
Table [9.36.8.3.-A]
Gross Space Heat Loss Adjustment Factor
Forming Part of Sentence 9.36.8.3.(1)
Energy Performance Tier Gross Space Heat Loss Adjustment Factor
1 1
2 0.95
3 0.90
4 0.80
5 0.60
[2] --)The annual gross space heat loss budget for the applicable heated floor area shall be determined in accordance with Table 9.36.8.3.-B, in kWh per year.
Table [9.36.8.3.-B]
Annual Gross Space Heat Loss Budget
Forming Part of Sentence 9.36.8.3.(2)
Heated Floor Area, m2 Annual Gross Space Heat Loss Budget, kWh per year
Heated floor area < 115 Local heat loss factor × 115
115 < heated floor area < 350 Local heat loss factor × heated floor area
Heated floor area > 350 Local heat loss factor × 350
[9.36.8.4.] ---Design Cooling Load
[1] --)The design cooling load shall be calculated in accordance with CSA F280, “Determining the required capacity of residential space heating and cooling appliances.”
[2] --)The design cooling load budget shall be calculated by multiplying the heated floor area by 15 W/m².
[3] --)Buildings and houses with a design cooling load greater than the design cooling load budget shall be equipped with cooling equipment that
[a] --)is sized in accordance with CSA F280, “Determining the required capacity of residential space heating and cooling appliances,” and
[b] --)complies with Subsection 9.36.3.
[9.36.8.5.] ---Annual Energy Consumption Target
[1] --)The annual energy consumption target shall be calculated by multiplying the reference energy use budget, calculated in accordance with Sentence (2), by the energy consumption target adjustment factor as provided in Table 9.36.8.5.-A for the applicable energy performance tier.
Table [9.36.8.5.-A]
Energy Consumption Target Adjustment Factor
Forming Part of Sentence 9.36.8.5.(1)
Energy Performance Tier Energy Consumption Target Adjustment Factor
1 1
2 0.90
3 0.80
4 0.60
5 0.30
[2] --)The reference energy use budget for the applicable heated floor area shall be determined in accordance with Table 9.36.8.5.-B.
Table [9.36.8.5.-B]
Reference Energy Use Budget
Forming Part of Sentence 9.36.8.5.(2)
Heated Floor Area, m2 Reference Energy Use Budget, kWh per year
Heated floor area < 115  (Local energy use factor × 115) + 6 500
115 < heated floor area < 350 (Local energy use factor × heated floor area) + 6 500
Heated floor area > 350 (Local energy use factor × 350) + 6 500

[9.36.9.] 9.36.8. Tiered Energy Performance Compliance: Prescriptive Path

[9.36.9.1.] 9.36.8.1.Scope
[9.36.9.2.] 9.36.8.2.Compliance
[9.36.9.3.] 9.36.8.3.Definitions
[9.36.9.4.] 9.36.8.4.Building Envelope – General
[9.36.9.5.] 9.36.8.5.Energy Conservation Measures for Above-Ground Opaque Building Assemblies
[9.36.9.6.] 9.36.8.6.Energy Conservation Measures for Fenestration and Doors
[9.36.9.7.] 9.36.8.7.Energy Conservation Measures for Opaque Building Assemblies Below-Grade or in Contact with the Ground
[9.36.9.8.] 9.36.8.8.Energy Conservation Measures Relating to Airtightness
[9.36.9.9.] 9.36.8.9.Energy Conservation Measures for HVAC Systems
[9.36.9.10.] 9.36.8.10.Energy Conservation Measures for Service Water Heating Equipment
[9.36.9.11.] 9.36.8.11.Energy Conservation Points for Building Volume

Impact analysis

This proposed change provides an alternate compliance path for meeting the energy-efficiency requirements of Section 9.36., including the energy performance tiers provided in Subsection 9.36.7. This proposed change does not limit or restrict the continued use of the existing compliance paths provided in Section 9.36; Code users who deem the energy use intensity (EUI) compliance path to be more onerous than the existing prescriptive or performance paths may continue to comply via those other paths. Accordingly, this proposed change is not expected to increase the cost or effort required to comply with the Code.

However, many Code users will likely find that complying via the EUI compliance path is simpler and more cost-effective than compliance via the existing prescriptive or performance paths. This outcome is expected because the EUI compliance path recognizes the energy savings inherent in more compact architectural forms. Where Subsection 9.36.7. limits compliance measures to improved building envelopes and enhanced equipment efficiencies, the EUI compliance path offers Code users another tool (i.e., reducing building envelope area) to achieve the same objective.

Research by Natural Resources Canada (NRCan) supports this conclusion. NRCan analyzed the various energy compliance paths using 240 building archetypes representing contemporary residential construction in different locations across Canada. Each of these building archetypes was configured to reflect the minimum prescriptive requirements described in Subsections 9.36.2. to 9.36.4. 

When the compliance of these same building archetypes was assessed via the proposed EUI compliance path, NRCan found that 25% of the building archetypes achieved at least Energy Performance Tier 1 without further modification. An additional 25% of the building archetypes would achieve Energy Performance Tier 1 if equipped with cooling equipment to satisfy the requirement of proposed Article 9.36.8.4.-2025 on design cooling load. The remaining 50% of the building archetypes would not benefit from using the proposed EUI compliance path and would be best served by the existing compliance paths.

Of the 25% of building archetypes that would achieve at least Energy Performance Tier 1, many would be able to achieve higher tier performance under the EUI compliance path without employing additional energy conservation measures. Table 1 provides the percentage of building archetypes that would comply with each of the energy performance tiers when constructed to the minimum requirements of Subsections 9.36.2. to 9.36.4.

Table 1: Building Archetype Compliance via EUI Compliance Path(1) by Compliance Tier and Housing Form

Form Non-compliant with Subsection 9.36.8.-2025(2) Tier 1 Tier 2 Tier 3 Tier 4 Tier 5
Attached 40% 5% 12% 28% 15% 1%
Detached 69% 13% 9% 7% 2% 0%

Notes to Table:

(1) When constructed to the prescriptive requirements of NBC Section 9.36.

(2) These archetypes would still comply with the prescriptive requirements of Subsections 9.36.2. to 9.36.4. as well as Energy Performance Tier 1 described in Subsection 9.36.7.

Although all of these building archetypes reflect Code-compliant construction, the EUI compliance path would allow Code users to benefit from demonstrating compliance with higher energy tiers because the architectural form of the building reduces heat loss and overall energy use. The extent to which the EUI compliance path would enable building archetypes to meet the performance levels of higher tiers when constructed to the minimum prescriptive requirements of Subsections 9.36.2. to 9.36.4. depends on the architectural form. Stacked dwelling units that share walls as well as ceilings and/or floors with adjacent units would receive the greatest benefit.

In practice, this result means that the Code users who select compact building designs could comply with a higher energy tier at a lower cost. Highly compact and attached buildings might comply with a higher tier at no additional cost. Additionally, Code users would benefit from considering different architectural forms as an option to reduce the cost of compliance with higher energy performance tiers.

Enforcement implications

The EUI compliance path would have similar administrative requirements as the existing performance compliance paths. Both approaches rely on modeling and simulation to estimate energy consumption and then compare the results to a benchmark. Some authorities having jurisdiction that use EUI metrics report that administration of this path is somewhat simpler because the reference benchmark is readily computed using heating degree-day and floor area parameters.

Authorities having jurisdiction that adopt this EUI compliance path should note that the local heat loss factor and local energy use factor described in this proposed change reflect current NBC prescriptive requirements (Subsections 9.36.2. to 9.36.4.) and modeling rules (Subsection 9.36.5.). Changes to these requirements and rules in future Code editions would require adjustment to the factors used in the EUI compliance path.

Who is affected

This proposed change would affect designers, building owners, and energy consultants who might choose to use the proposed EUI path to demonstrate compliance.

Code users might find that administration of performance compliance via the EUI path is somewhat easier, as only one energy model would have to be completed instead of two.

In addition, Code users would have the ability to use changes to architectural form as a means of meeting energy conservation requirements.

OBJECTIVE-BASED ANALYSIS OF NEW OR CHANGED PROVISIONS

[9.36.1.1.] 9.36.1.1. ([1] 1) no attributions
[9.36.1.2.] 9.36.1.2. ([1] 1) no attributions
[9.36.1.2.] 9.36.1.2. ([2] 2) no attributions
[9.36.1.2.] 9.36.1.2. ([3] 3) no attributions
[9.36.1.2.] 9.36.1.2. ([4] 4) no attributions
[9.36.1.2.] 9.36.1.2. ([5] 5) no attributions
[9.36.1.2.] 9.36.1.2. ([6] 6) no attributions
[9.36.1.2.] 9.36.1.2. ([7] 7) no attributions
[9.36.1.2.] 9.36.1.2. ([8] 8) no attributions
[9.36.1.3.] 9.36.1.3. ([1] 1) no attributions
[9.36.1.3.] 9.36.1.3. ([1] 1) ([f] e)
[9.36.1.3.] 9.36.1.3. ([2] 2) no attributions
[9.36.1.3.] 9.36.1.3. ([2] 2) no attributions
[9.36.1.3.] 9.36.1.3. ([3] 3) no attributions
[9.36.1.3.] 9.36.1.3. ([4] 4) no attributions
[9.36.1.3.] 9.36.1.3. ([5] 5) no attributions
[9.36.1.3.] 9.36.1.3. ([6] 6) no attributions
[9.36.2.1.] 9.36.2.1. ([1] 1) no attributions
[9.36.2.1.] 9.36.2.1. ([2] 2) no attributions
[9.36.2.1.] 9.36.2.1. ([3] 3) no attributions
[9.36.2.1.] 9.36.2.1. ([4] 4) no attributions
[9.36.2.1.] 9.36.2.1. ([5] 5) no attributions
[9.36.2.2.] 9.36.2.2. ([1] 1) [F92-OE1.1]
[9.36.2.2.] 9.36.2.2. ([2] 2) [F92-OE1.1]
[9.36.2.2.] 9.36.2.2. ([3] 3) [F92-OE1.1]
[9.36.2.2.] 9.36.2.2. ([4] 4) [F92-OE1.1]
[9.36.2.2.] 9.36.2.2. ([5] 5) [F92-OE1.1]
[9.36.2.3.] 9.36.2.3. ([1] 1) no attributions
[9.36.2.3.] 9.36.2.3. ([2] 2) no attributions
[9.36.2.3.] 9.36.2.3. ([3] 3) no attributions
[9.36.2.3.] 9.36.2.3. ([4] 4) no attributions
[9.36.2.3.] 9.36.2.3. ([5] 5) no attributions
[9.36.2.4.] 9.36.2.4. ([1] 1) [F92-OE1.1]
[9.36.2.4.] 9.36.2.4. ([2] 2) no attributions
[9.36.2.4.] 9.36.2.4. ([3] 3) [F92-OE1.1]
[9.36.2.4.] 9.36.2.4. ([4] 4) no attributions
[9.36.2.5.] 9.36.2.5. ([1] 1) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([2] 2) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([3] 3) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([4] 4) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([5] 5) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([6] 6) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([7] 7) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([8] 8) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([9] 9) [F92-OE1.1]
[9.36.2.5.] 9.36.2.5. ([10] 10) no attributions
[9.36.2.6.] 9.36.2.6. ([1] 1) [F92-OE1.1]
[9.36.2.6.] 9.36.2.6. ([2] 2) [F92-OE1.1]
[9.36.2.6.] 9.36.2.6. ([3] 3) [F92-OE1.1]
[9.36.2.6.] 9.36.2.6. ([4] 4) [F92-OE1.1]
[9.36.2.7.] 9.36.2.7. ([1] 1) [F92-OE1.1]
[9.36.2.7.] 9.36.2.7. ([2] 2) [F92-OE1.1]
[9.36.2.7.] 9.36.2.7. ([3] 3) no attributions
[9.36.2.7.] 9.36.2.7. ([3] 3) [F92-OE1.1]
[9.36.2.7.] 9.36.2.7. ([4] 4) [F92-OE1.1]
[9.36.2.7.] 9.36.2.7. ([5] 5) [F92-OE1.1]
[9.36.2.7.] 9.36.2.7. ([6] 6) no attributions
[9.36.2.7.] 9.36.2.7. ([7] 7) [F92-OE1.1]
[9.36.2.7.] 9.36.2.7. ([8] 8) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([1] 1) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([2] 2) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([3] 3) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([4] 4) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([5] 5) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([6] 6) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([7] 7) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([8] 8) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([9] 9) [F92-OE1.1]
[9.36.2.8.] 9.36.2.8. ([10] 10) no attributions
[9.36.2.9.] 9.36.2.9. ([1] 1) [F90-OE1.1]
[9.36.2.9.] 9.36.2.9. ([2] 2) [F90-OE1.1]
[9.36.2.9.] 9.36.2.9. ([3] 3) [F90-OE1.1]
[9.36.2.9.] 9.36.2.9. ([4] 4) [F90-OE1.1]
[9.36.2.9.] 9.36.2.9. ([5] 5) [F90-OE1.1]
[9.36.2.9.] 9.36.2.9. ([6] 6) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([1] 1) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([2] 2) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([3] 3) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([4] 4) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([5] 5) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([6] 6) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([7] 7) [F90,F91,F92,F93,F95,F100-OE1.1]
[9.36.2.10.] 9.36.2.10. ([8] 8) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([9] 9) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([10] 10) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([11] 11) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([12] 12) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([13] 13) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([14] 14) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([15] 15) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([16] 16) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([17] 17) [F90-OE1.1]
[9.36.2.10.] 9.36.2.10. ([18] 18) [F90-OE1.1]
[9.36.2.11.] 9.36.2.11. ([1] 1) no attributions
[9.36.2.11.] 9.36.2.11. ([2] 2) [F92-OE1.1]
[9.36.2.11.] 9.36.2.11. ([2] 2) no attributions
[9.36.2.11.] 9.36.2.11. ([3] 3) [F92-OE1.1]
[9.36.2.11.] 9.36.2.11. ([3] 3) no attributions
[9.36.2.11.] 9.36.2.11. ([4] 4) [F92-OE1.1]
[9.36.2.11.] 9.36.2.11. ([5] 5) [F92-OE1.1]
[9.36.2.11.] 9.36.2.11. ([6] 6) [F92-OE1.1]
[9.36.2.11.] 9.36.2.11. ([7] 7) [F92-OE1.1]
[9.36.2.11.] 9.36.2.11. ([8] 8) [F92-OE1.1]
[9.36.3.1.] 9.36.3.1. ([1] 1) no attributions
[9.36.3.1.] 9.36.3.1. ([2] 2) no attributions
[9.36.3.2.] 9.36.3.2. ([1] 1) [F95-OE1.1]
[9.36.3.2.] 9.36.3.2. ([2] 2) no attributions
[9.36.3.2.] 9.36.3.2. ([3] 3) [F91,F93-OE1.1]
[9.36.3.2.] 9.36.3.2. ([4] 4) [F91,F93-OE1.1]
[9.36.3.2.] 9.36.3.2. ([5] 5) no attributions
[9.36.3.2.] 9.36.3.2. ([5] 5) [F91,F93-OE1.1]
[9.36.3.3.] 9.36.3.3. ([1] 1) [F91,F95-OE1.1]
[9.36.3.3.] 9.36.3.3. ([2] 2) [F91,F95-OE1.1]
[9.36.3.3.] 9.36.3.3. ([3] 3) no attributions
[9.36.3.3.] 9.36.3.3. ([4] 4) no attributions
[9.36.3.4.] 9.36.3.4. ([1] 1) no attributions
[9.36.3.4.] 9.36.3.4. ([2] 2) [F93-OE1.1]
[9.36.3.5.] 9.36.3.5. ([1] 1) [F98-OE1.1]
[9.36.3.6.] 9.36.3.6. ([1] 1) [F95-OE1.1]
[9.36.3.6.] 9.36.3.6. ([1] 1) no attributions
[9.36.3.6.] 9.36.3.6. ([2] 2) [F95,F98-OE1.1]
[9.36.3.6.] 9.36.3.6. ([3] 3) [F95-OE1.1]
[9.36.3.6.] 9.36.3.6. ([4] 4) [F95-OE1.1]
[9.36.3.6.] 9.36.3.6. ([5] 5) [F95-OE1.1]
[9.36.3.6.] 9.36.3.6. ([6] 6) [F95-OE1.1]
[9.36.3.6.] 9.36.3.6. ([7] 7) [F95-OE1.1]
[9.36.3.7.] 9.36.3.7. ([1] 1) [F95-OE1.1]
[9.36.3.8.] 9.36.3.8. ([1] 1) [F95,F100-OE1.1]
[9.36.3.8.] 9.36.3.8. ([2] 2) no attributions
[9.36.3.8.] 9.36.3.8. ([3] 3) no attributions
[9.36.3.8.] 9.36.3.8. ([4] 4) [F98,F100-OE1.1]
[9.36.3.8.] 9.36.3.8. ([5] 5) [F98,F100-OE1.1]
[9.36.3.9.] 9.36.3.9. ([1] 1) no attributions
[9.36.3.9.] 9.36.3.9. ([2] 2) [F95,F100-OE1.1]
[9.36.3.9.] 9.36.3.9. ([3] 3) [F95,F100-OE1.1]
[9.36.3.9.] 9.36.3.9. ([4] 4) [F95,F98,F100-OE1.1]
[9.36.3.10.] 9.36.3.10. ([1] 1) [F95,F98,F99-OE1.1]
[9.36.3.10.] 9.36.3.10. ([2] 2) [F95,F98,F99-OE1.1]
[9.36.3.10.] 9.36.3.10. ([3] 3) no attributions
[9.36.3.11.] 9.36.3.11. ([1] 1) [F95,F98,F99-OE1.1]
[9.36.3.11.] 9.36.3.11. ([2] 2) no attributions
[9.36.3.11.] 9.36.3.11. ([3] 3) [F93,F96-OE1.1]
[9.36.4.1.] 9.36.4.1. ([1] 1) no attributions
[9.36.4.1.] 9.36.4.1. ([2] 2) no attributions
[9.36.4.2.] 9.36.4.2. ([1] 1) [F96,F98-OE1.1]
[9.36.4.2.] 9.36.4.2. ([2] 2) [F93,F96-OE1.1]
[9.36.4.2.] 9.36.4.2. ([3] 3) [F98-OE1.1]
[9.36.4.3.] 9.36.4.3. ([1] 1) [F96,F98-OE1.1]
[9.36.4.3.] 9.36.4.3. ([2] 2) no attributions
[9.36.4.3.] 9.36.4.3. ([3] 3) [F93,F96-OE1.1]
[9.36.4.4.] 9.36.4.4. ([1] 1) [F93,F96-OE1.1]
[9.36.4.4.] 9.36.4.4. ([2] 2) [F93,F96-OE1.1]
[9.36.4.4.] 9.36.4.4. ([3] 3) [F93,F96-OE1.1]
[9.36.4.5.] 9.36.4.5. ([1] 1) [F96-OE1.1]
[9.36.4.6.] 9.36.4.6. ([1] 1) [F96-OE1.1]
[9.36.4.6.] 9.36.4.6. ([2] 2) [F96-OE1.1]
[9.36.5.1.] 9.36.5.1. ([1] 1) no attributions
[9.36.5.1.] 9.36.5.1. ([2] 2) no attributions
[9.36.5.2.] 9.36.5.2. ([1] 1) no attributions
[9.36.5.2.] 9.36.5.2. ([2] 2) no attributions
[9.36.5.3.] 9.36.5.3. ([1] 1) no attributions
[9.36.5.3.] 9.36.5.3. ([2] 2) [F92,F93,F95,F96,F98,F99,F100-OE1.1]
[9.36.5.3.] 9.36.5.3. ([3] 3) [F92,F93,F95,F96,F98,F99,F100-OE1.1]
[9.36.5.3.] 9.36.5.3. ([4] 4) [F92,F93,F95,F96,F98,F99,F100-OE1.1]
[9.36.5.3.] 9.36.5.3. ([5] 5) [F92,F93,F95,F96,F98,F99,F100-OE1.1]
[9.36.5.3.] 9.36.5.3. ([6] 6) [F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([1] 1) no attributions
[9.36.5.4.] 9.36.5.4. ([2] 2) no attributions
[9.36.5.4.] 9.36.5.4. ([3] 3) [F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([4] 4) [F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([5] 5) [F95,F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([6] 6) [F95,F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([7] 7) [F95,F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([8] 8) [F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([9] 9) [F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([10] 10) [F90,F99-OE1.1]
[9.36.5.4.] 9.36.5.4. ([11] 11) [F90,F99-OE1.1]
[9.36.5.5.] 9.36.5.5. ([1] 1) [F99-OE1.1]
[9.36.5.5.] 9.36.5.5. ([2] 2) [F99-OE1.1]
[9.36.5.5.] 9.36.5.5. ([3] 3) [F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([1] 1) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([2] 2) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([3] 3) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([4] 4) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([5] 5) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([6] 6) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([7] 7) [F92,F93,F95,F96,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([8] 8) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([9] 9) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([10] 10) [F92,F99-OE1.1]
[9.36.5.6.] 9.36.5.6. ([11] 11) [F92,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([1] 1) [F95,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([2] 2) [F95,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([3] 3) [F95,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([4] 4) [F95,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([5] 5) [F95,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([6] 6) [F95,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([7] 7) [F95,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([8] 8) [F95,F99-OE1.1]
[9.36.5.7.] 9.36.5.7. ([9] 9) [F95,F99-OE1.1]
[9.36.5.8.] 9.36.5.8. ([1] 1) [F96,F99-OE1.1]
[9.36.5.8.] 9.36.5.8. ([2] 2) [F96,F99-OE1.1]
[9.36.5.8.] 9.36.5.8. ([3] 3) [F96,F99-OE1.1]
[9.36.5.8.] 9.36.5.8. ([4] 4) [F96,F99-OE1.1]
[9.36.5.8.] 9.36.5.8. ([5] 5) [F96,F99-OE1.1]
[9.36.5.8.] 9.36.5.8. ([6] 6) [F96,F99-OE1.1]
[9.36.5.8.] 9.36.5.8. ([7] 7) [F96,F99-OE1.1]
[9.36.5.8.] 9.36.5.8. ([8] 8) [F96,F99-OE1.1]
[9.36.5.9.] 9.36.5.9. ([1] 1) [F99-OE1.1]
[9.36.5.10.] 9.36.5.10. ([1] 1) [F92,F95,F99-OE1.1]
[9.36.5.10.] 9.36.5.10. ([2] 2) no attributions
[9.36.5.10.] 9.36.5.10. ([3] 3) no attributions
[9.36.5.10.] 9.36.5.10. ([4] 4) [F92,F95,F99-OE1.1]
[9.36.5.10.] 9.36.5.10. ([5] 5) [F92,F95,F99-OE1.1]
[9.36.5.10.] 9.36.5.10. ([6] 6) [F92,F95,F99-OE1.1]
[9.36.5.10.] 9.36.5.10. ([7] 7) [F92,F95,F99-OE1.1]
[9.36.5.10.] 9.36.5.10. ([8] 8) no attributions
[9.36.5.10.] 9.36.5.10. ([9] 9) [F90,F91,F92,F95,F99-OE1.1]
[9.36.5.10.] 9.36.5.10. ([10] 10) [F90,F91,F92,F93,F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([1] 1) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([2] 2) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([3] 3) [F92,F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([4] 4) [F95,F99,F100-OE1.1]
[9.36.5.11.] 9.36.5.11. ([5] 5) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([6] 6) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([7] 7) no attributions
[9.36.5.11.] 9.36.5.11. ([8] 8) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([9] 9) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([10] 10) [F95,F99,F100-OE1.1]
[9.36.5.11.] 9.36.5.11. ([11] 11) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([12] 12) [F95,F99,F100-OE1.1]
[9.36.5.11.] 9.36.5.11. ([13] 13) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([14] 14) [F95,F99,F100-OE1.1]
[9.36.5.11.] 9.36.5.11. ([15] 15) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([16] 16) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([17] 17) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([18] 18) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([19] 19) [F95,F99-OE1.1]
[9.36.5.11.] 9.36.5.11. ([20] 20) [F95,F99-OE1.1]
[9.36.5.12.] 9.36.5.12. ([1] 1) [F96,F99-OE1.1]
[9.36.5.12.] 9.36.5.12. ([2] 2) no attributions
[9.36.5.13.] 9.36.5.13. ([1] 1) [F99-OE1.1]
[9.36.5.13.] 9.36.5.13. ([2] 2) [F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([1] 1) [F92,F95,F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([2] 2) [F90,F91,F92,F95,F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([3] 3) [F92,F95,F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([4] 4) [F92,F95,F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([5] 5) [F92,F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([6] 6) [F92,F95,F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([7] 7) [F92,F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([8] 8) [F92,F99-OE1.1]
[9.36.5.14.] 9.36.5.14. ([9] 9) [F92,F99,F95-OE1.1]
[9.36.5.14.] 9.36.5.14. ([10] 10) [F92,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([1] 1) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([2] 2) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([3] 3) [F95,F99,F100-OE1.1]
[9.36.5.15.] 9.36.5.15. ([4] 4) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([5] 5) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([6] 6) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([7] 7) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([8] 8) [F95,F99,F100-OE1.1]
[9.36.5.15.] 9.36.5.15. ([9] 9) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([10] 10) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([11] 11) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([12] 12) [F95,F99,F100-OE1.1]
[9.36.5.15.] 9.36.5.15. ([13] 13) [F95,F99,F100-OE1.1]
[9.36.5.15.] 9.36.5.15. ([14] 14) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([15] 15) [F95,F99-OE1.1]
[9.36.5.15.] 9.36.5.15. ([16] 16) [F95,F99-OE1.1]
[9.36.5.16.] 9.36.5.16. ([1] 1) [F95,F99-OE1.1]
[9.36.5.16.] 9.36.5.16. ([2] 2) [F95,F99-OE1.1]
[9.36.5.16.] 9.36.5.16. ([3] 3) [F95,F99-OE1.1]
[9.36.6.1.] 9.36.6.1. ([1] 1) no attributions
[9.36.6.2.] 9.36.6.2. ([1] 1) no attributions
[9.36.6.3.] 9.36.6.3. ([1] 1) no attributions
[9.36.6.3.] 9.36.6.3. ([1] 1) [F90-OE1.1]
[9.36.6.3.] 9.36.6.3. ([2] 2) no attributions
[9.36.6.3.] 9.36.6.3. ([3] 3) no attributions
[9.36.6.4.] 9.36.6.4. ([1] 1) no attributions
[9.36.6.4.] 9.36.6.4. ([1] 1) [F90,F91,F92,F93,F95,F100-OE1.1]
[9.36.6.4.] 9.36.6.4. ([2] 2) [F90,F91,F92,F93,F95,F100-OE1.1]
[9.36.6.4.] 9.36.6.4. ([3] 3) [F90,F91,F92,F93,F95,F100-OE1.1]
[9.36.6.4.] 9.36.6.4. ([4] 4) [F90,F91,F92,F93,F95,F100-OE1.1]
[9.36.7.1.] 9.36.7.1. ([1] 1) no attributions
[9.36.7.1.] 9.36.7.1. ([2] 2) no attributions
[9.36.7.2.] 9.36.7.2. ([1] 1) no attributions
[9.36.7.2.] 9.36.7.2. ([1] 1) [F90,F91,F92,F93,F95,F96,F98,F99,F100-OE1.1]
[9.36.7.3.] 9.36.7.3. ([1] 1) no attributions
[9.36.7.3.] 9.36.7.3. ([2] 2) [F95-OE1.1]
[9.36.7.3.] 9.36.7.3. ([3] 3) no attributions
[9.36.7.3.] 9.36.7.3. ([3] 3) [F90,F91,F92,F93,F95,F96,F98,F99,F100-OE1.1]
[9.36.7.3.] 9.36.7.3. ([4] 4) no attributions
[9.36.7.3.] 9.36.7.3. ([5] 5) [F90,F91,F92,F93,F95,F100-OE1.1]
[9.36.7.3.] 9.36.7.3. ([6] 6) no attributions
[9.36.7.3.] 9.36.7.3. ([6] 6) [F99-OE1.1]
[9.36.7.3.] 9.36.7.3. ([7] 7) [F99-OE1.1]
[9.36.7.3.] 9.36.7.3. ([8] 8) [F90,F91,F92,F93,F95,F96,F98,F99,F100-OE1.1]
[9.36.7.3.] 9.36.7.3. ([9] 9) [F90,F91,F92,F93,F95,F100-OE1.1]
[9.36.8.1.] -- ([1] --) no attributions
[9.36.8.1.] -- ([2] --) no attributions
[9.36.8.1.] -- ([3] --) no attributions
[9.36.8.1.] -- ([4] --) no attributions
[9.36.8.1.] -- ([5] --) no attributions
[9.36.8.2.] -- ([1] --) no attributions
[9.36.8.2.] -- ([2] --) no attributions
[9.36.8.3.] -- ([1] --) [F99-OE1.1]
[9.36.8.3.] -- ([2] --) [F99-OE1.1]
[9.36.8.4.] -- ([1] --) [F99-OE1.1]
[9.36.8.4.] -- ([2] --) [F99-OE1.1]
[9.36.8.4.] -- ([3] --) no attributions
[9.36.8.4.] -- ([3] --) [F98-OE1.1]
[9.36.8.5.] -- ([1] --) [F99-OE1.1]
[9.36.8.5.] -- ([2] --) [F99-OE1.1]
[9.36.9.1.] 9.36.8.1. ([1] 1) no attributions
[9.36.9.2.] 9.36.8.2. ([1] 1) no attributions
[9.36.9.2.] 9.36.8.2. ([1] 1) [F90,F91,F92,F93,F95,F96,F98,F99,F100-OE1.1]
[9.36.9.4.] 9.36.8.4. ([1] 1) no attributions
[9.36.9.5.] 9.36.8.5. ([1] 1) no attributions
[9.36.9.5.] 9.36.8.5. ([2] 2) [F92-OE1.1]
[9.36.9.5.] 9.36.8.5. ([3] 3) [F92-OE1.1]
[9.36.9.5.] 9.36.8.5. ([4] 4) no attributions
[9.36.9.5.] 9.36.8.5. ([4] 4) [F92-OE1.1]
[9.36.9.5.] 9.36.8.5. ([5] 5) no attributions
[9.36.9.5.] 9.36.8.5. ([5] 5) [F92-OE1.1]
[9.36.9.5.] 9.36.8.5. ([6] 6) [F92-OE1.1]
[9.36.9.5.] 9.36.8.5. ([7] 7) [F92-OE1.1]
[9.36.9.6.] 9.36.8.6. ([1] 1) [F92-OE1.1]
[9.36.9.6.] 9.36.8.6. ([2] 2) no attributions
[9.36.9.6.] 9.36.8.6. ([3] 3) no attributions
[9.36.9.6.] 9.36.8.6. ([3] 3) [F92-OE1.1]
[9.36.9.6.] 9.36.8.6. ([4] 4) [F92-OE1.1]
[9.36.9.7.] 9.36.8.7. ([1] 1) no attributions
[9.36.9.7.] 9.36.8.7. ([2] 2) [F92-OE1.1]
[9.36.9.7.] 9.36.8.7. ([3] 3) [F92-OE1.1]
[9.36.9.7.] 9.36.8.7. ([4] 4) no attributions
[9.36.9.8.] 9.36.8.8. ([1] 1) no attributions
[9.36.9.8.] 9.36.8.8. ([2] 2) [F90-OE1.1]
[9.36.9.9.] 9.36.8.9. ([1] 1) no attributions
[9.36.9.9.] 9.36.8.9. ([2] 2) no attributions
[9.36.9.9.] 9.36.8.9. ([3] 3) no attributions
[9.36.9.9.] 9.36.8.9. ([3] 3) [F95,F100-OE1.1]
[9.36.9.9.] 9.36.8.9. ([4] 4) [F95-OE1.1]
[9.36.9.10.] 9.36.8.10. ([1] 1) no attributions
[9.36.9.10.] 9.36.8.10. ([2] 2) no attributions
[9.36.9.10.] 9.36.8.10. ([3] 3) [F96-OE1.1]
[9.36.9.11.] 9.36.8.11. ([1] 1) [F95-OE1.1]
[9.36.9.11.] 9.36.8.11. ([2] 2) [F95-OE1.1]
Date modified: