Page: Last modified: 2023-10-11
Code Reference(s):
NECB20 Div.B 5.2.12.1. (first printing)
Subject:
HVAC Equipment Efficiency Table
Title:
New Performance Metrics for Small Single-Phase Air Conditioners and Heat Pumps
Description:
This proposed change introduces new energy metrics for small single-phase air conditioners and heat pumps.
This change could potentially affect the following topic areas:

Problem

Effective January 1, 2023, the US Department of Energy (DOE) introduced a series of new energy performance metrics (EER2, SEER2 and HSPF2) in DOE 10 CFR, Part 430-2022, "Energy, Energy Conservation Program for Consumer Products," that is applicable to small single-phase air-cooled air conditioners and air-source heat pumps. These metrics are similar to the previous ones (EER, SEER and HSPF), but use different test conditions that are considered to be more realistic. Larger units and three-phase models are not affected by this amendment.

With the publication of the Regulations Amending the Energy Efficiency Regulations, 2016 (Amendment 17), SOR/2022-265, on December 7, 2022, the Canadian Energy Efficiency Regulations, 2016 (EER), SOR/2016-311, were aligned with DOE 10 CFR, Part 430-2022 by requiring the minimum performance levels to be expressed with the new metrics. As a result, a discrepancy is caused between the NECB and the EER. If manufacturers provided product labels only using the new metrics, the products available on the market could potentially have issues with their conformance to the NECB.

Moreover, it is anticipated that single-phase variable refrigerant flow systems will also be tested to the new test conditions. 

This discrepancy will lead to gaps in the Code, and Code users will be unable to evaluate whether HVAC equipment performance complies with the NECB requirements. This, in turn, will lead to difficulties for enforcement officials when determining compliance.

Justification

This proposed change to the NECB updates the reference to the 2022 amendment to DOE 10 CFR, Part 430 and introduces the new energy performance metrics. To facilitate compliance with the NECB, this proposed change maintains the alignment of the NECB with the Energy Efficiency Regulations, 2016 (EER), as amended by SOR/2022-265 (Amendment 17), and ASHRAE 90.1, “Energy Standard for Buildings Except Low-Rise Residential Buildings,” as well as industry practice by US manufacturers.

Amendment 17 generally presents two sets of performance requirements to the EER: the first came into force on January 1, 2023, and the second comes into force on January 1, 2025.

Considering that the NECB 2025 will be published and adopted after January 1, 2025, these requirements, where applicable, should be included in the 2025 edition of the NECB. Amendment 17 also updates the required minimum performance levels for small variable refrigerant flow systems using the same test conditions.

Furthermore, where the NECB has requirements that were and remain more stringent than the EER, the performance levels of the NECB have been retained and converted to the new metrics using the following references:

PROPOSED CHANGE

NECB20 Div.B 5.2.12.1. (first printing)

[5.2.12.1.] 5.2.12.1.Unitary and Packaged HVAC Equipment

[1] 1)Unitary and packaged HVAC equipment and components with the capacities listed in Tables 5.2.12.1.-A to 5.2.12.1.-P shall comply with the performance requirements stated therein. (See Notes A-5.2.12.1.(1)PROPOSED CHANGE A-5.2.12.1.(1) and A-5.2.12.1.(1) and 6.2.2.1.(1)PROPOSED CHANGE A-5.2.12.1.(1) and 6.2.2.1.(1).) (See also Article 6.2.2.4.)
Table [5.2.12.1.-A] 5.2.12.1.-A
Performance Requirements for Air-Cooled Unitary Air Conditioners and Heat Pumps – Electrically OperatedPROPOSED CHANGE Table 5.2.12.1.A. Footnote (1)
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.A. Footnote (2)
Single-phase air conditioners and heat pumps, single-package, space-constrained < 19 DOE 10 CFR, Part 430-2022, Subpart B, Appendix M1 See standard SEER2 = 12.4 / HSPF2 V = 5.4 PROPOSED CHANGE Table 5.2.12.1.A. Footnote (3)PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Single-phase air conditioners and heat pumps, single-package, others SEER2 = 14.3 / HSPF2 V = 6.3 PROPOSED CHANGE Table 5.2.12.1.A. Footnote (3)PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Single-phase air conditioners and heat pumps, split-system, others SEER2 = 12.4 / HSPF2 V = 5.4 PROPOSED CHANGE Table 5.2.12.1.A. Footnote (3)PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Single-phase air conditioners and heat pumps, split-system, space-constrained SEER2 = 14.3 / HSPF2 V = 6.6 PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Single-phase air conditioners and heat pumps, split-system, small-duct and high-velocity SEER2 = 12.4 / HSPF2 V = 5.0 PROPOSED CHANGE Table 5.2.12.1.A. Footnote (3)PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Air conditioners and heat pumps, Ssingle-package, space-constrained < 19 CSA C656 See standard SEER = 13 / HSPF V = 6.4PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Air conditioners and heat pumps, Ssingle-package, others SEER = 15 / HSPF V = 7.4PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Air conditioners and heat pumps, Ssplit-system, space-constrained SEER = 13 / HSPF V = 6.4PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Air conditioners and heat pumps, Ssplit-system, others SEER = 15 / HSPF V = 7.47.8PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Air conditioners and heat pumps, split-system, Ssmall-duct, and high-velocity SEER = 13 / HSPF V = 5.9PROPOSED CHANGE Table 5.2.12.1.A. Footnote (4)
Large air conditioners and heat pumps, split-system and single-package, all electrical phases, in cooling mode ≥ 19 and < 40 CAN/CSA-C746 Electric resistance heating section or no heating section EER = 11.2
IEER = 12.9
Other types of heating sections EER = 11.0
IEER = 12.7
≥ 40 and < 70 Electric resistance heating section or no heating section EER = 11.0
IEER = 12.4
Other types of heating sections EER = 10.8
IEER = 12.2
≥ 70 and < 223 Electric resistance heating section or no heating section EER = 10.0
IEER = 11.6
Other types of heating sections EER = 9.8
IEER = 11.4
≥ 223 ANSI/AHRI 340/360 Electric resistance heating section or no heating section EER = 9.7
IEER = 11.2
Other types of heating sections EER = 9.5
IEER = 11.0
Large heat pumps, split-system and single-package, all electrical phases, in heating mode ≥ 19 and < 40 CAN/CSA-C746 at 8.3ºC COPh = 3.30
at –8.3ºC COPh = 2.25
≥ 40 and < 70 at 8.3ºC COPh = 3.20
at –8.3ºC COPh = 2.05
≥ 70 and < 223 at 8.3ºC COPh = 3.20
at –8.3ºC COPh = 2.05
≥ 223 ANSI/AHRI 340/360 at 8.3ºC COPh = 3.20
at –8.3ºC COPh = 2.05
Table [5.2.12.1.-B] 5.2.12.1.-B
Performance Requirements for Single-Package Vertical Air Conditioners (SPVAC) and Heat Pumps (SPVHP)PROPOSED CHANGE Table 5.2.12.1.B. Footnote (1)
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.B. Footnote (2)
SPVAC and SPVHP in cooling mode < 70 CAN/CSA-C746 < 19 kW EER = 11
≥ 19 kW and < 40 kW EER = 10
≥ 40 kW and < 70 kW EER = 10
SPVHP in heating mode < 19 kW COPh = 3.3
≥ 19 kW and < 40 kW COPh = 3.0
≥ 40 kW and < 70 kW COPh = 3.0
Table [5.2.12.1.-C] 5.2.12.1.-C
Performance Requirements for Water-Cooled and Evaporatively Cooled Unitary Air Conditioners – Electrically Operated
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.C. Footnote (1)
Water-cooled and evaporatively cooled, split-system and single-package < 19 ANSI/AHRI 210/240 < 19 kW EER = 12.1
IEER = 12.3
Water-cooled, split-system and single-packagePROPOSED CHANGE Table 5.2.12.1.C. Footnote (2) ≥ 19 and < 40 CAN/CSA-C746 Electric resistance heating section or no heating section EER = 12.1
IEER = 13.9
Other types of heating sections EER = 11.9
IEER = 13.7
≥ 40 and < 70 Electric resistance heating section or no heating section EER = 12.5
IEER = 13.9
Other types of heating sections EER = 12.3
IEER = 13.7
≥ 70 and < 223 Electric resistance heating section or no heating section EER = 12.4
IEER = 13.6
Other types of heating sections EER = 12.2
IEER = 13.4
Evaporatively cooled, split and single-packagePROPOSED CHANGE Table 5.2.12.1.C. Footnote (2) ≥ 19 and < 40 CAN/CSA-C746 Electric resistance heating section or no heating section EER = 12.1
IEER = 12.3
Other types of heating sections EER = 11.9
IEER = 12.1
≥ 40 and < 70 Electric resistance heating section or no heating section EER = 12.0
IEER = 12.2
Other types of heating sections EER = 11.8
IEER = 12.0
≥ 70 and < 223 Electric resistance heating section or no heating section EER = 11.9
IEER = 12.1
Other types of heating sections EER = 11.7
IEER = 11.9
Water-cooled, split and single-package ≥ 223 ANSI/AHRI 340/360 Electric resistance heating section or no heating section EER = 12.2
IEER = 13.5
Other types of heating sections EER = 12.0
IEER = 13.3
Evaporatively cooled, split and single-package Electric resistance heating section or no heating section EER = 11.7
IEER = 11.9
Other types of heating sections EER = 11.5
IEER = 11.7
Table [5.2.12.1.-D] 5.2.12.1.-D
Performance Requirements for Condensing Units
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.D. Footnote (1)
Air-cooledPROPOSED CHANGE Table 5.2.12.1.D. Footnote (2) ≥ 40 and < 70 CAN/CSA-C746 See standard EER = 11.2
Water-cooled and evaporatively cooledPROPOSED CHANGE Table 5.2.12.1.D. Footnote (2) EER = 13.1
Air-cooled ≥ 70 ANSI/AHRI 366 (SI) ≥ 70 kW EER = 10.5
IEER = 11.8
Water-cooled and evaporatively cooled EER = 13.5
IEER = 14.0
Table [5.2.12.1.-E] 5.2.12.1.-E
Performance Requirements for Water-Source Unitary Heat Pumps
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.E. Footnote (1)
Water-to-airPROPOSED CHANGE Table 5.2.12.1.E. Footnote (2) < 5 CAN/CSA-C13256-1 Water loop COPc = 3.58
COPh = 4.3
≥ 5 and < 40 COPc = 3.81
COPh = 4.3
< 40 Groundwater COPc = 5.28
COPh = 3.7
Ground loop COPc = 4.13
COPh = 3.2
Water-to-water < 40 CAN/CSA-C13256-2 Water loop COPc = 3.11
COPh = 3.7
Groundwater COPc = 5.60
COPh = 3.4
Ground loop COPc = 4.21
COPh = 2.8
Table [5.2.12.1.-F] 5.2.12.1.-F
Performance Requirements for Direct-Expansion Ground-Source Heat Pumps – Electrically Operated
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.F. Footnote (1)
Direct-expansion ground-source heat pumps ≤ 21 CSA C748 See standard COPc = 3.81
COPh = 3.1
> 21 No requirements
Table [5.2.12.1.-G] 5.2.12.1.-G
Performance Requirements for Packaged Terminal Air Conditioners (PTAC) and Heat Pumps (PTHP), and Room Air Conditioners and Heat PumpsPROPOSED CHANGE Table 5.2.12.1.G. Footnote (1)
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.G. Footnote (2)
PTAC and PTHP in cooling mode, standard and non-standard sizes < 2.1 AHRI 310/380/CSA C744 See standard EER = 11.9
≥ 2.1 and < 4.4 EER = 14.1 – (1.0435 × CapkW)
≥ 4.4 EER = 9.5
PTHP in heating mode, standard and non-standard sizes < 2.1 COPh = 3.3
≥ 2.1 and < 4.4 COPh = 3.67 – (0.1739 × CapkW)
≥ 4.4 COPh = 2.9
Louvered, without reverse cycle < 5.9 CSA C368.1 See standard CEER = 10.7
≥ 5.9 and ≤ 10.6 CEER = 9.0
Louvered, with reverse cycle < 5.9 CEER = 9.8
≥ 5.9 and ≤ 10.6 CEER = 9.3
Non-louvered, without reverse cycle < 4.1 CEER = 9.6
≥ 4.1 and ≤ 10.6 CEER = 9.4
Non-louvered, with reverse cycle < 4.1 CEER = 9.3
≥ 4.1 and ≤ 10.6 CEER = 8.7
Room air conditioners, casement only All capacities CEER = 9.5
Room air conditioners, casement slider CEER = 10.4
Table [5.2.12.1.-H] 5.2.12.1.-H
Performance Requirements for Computer Room Air Conditioners
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.H. Footnote (1)
Air-cooled, floor-mounted, with or without fluid economizer < 23 AHRI 1361 (SI) Downflow or upflow, ducted SCOP = 2.67
≥ 23 and < 86 SCOP = 2.55
≥ 86 SCOP = 2.33
< 23 Upflow, non-ducted SCOP = 2.09
Horizontal SCOP = 2.65
≥ 23 and < 70 Upflow, non-ducted SCOP = 1.99
Horizontal SCOP = 2.55
≥ 70 Upflow, non-ducted SCOP = 1.81
Horizontal SCOP = 2.47
Water-cooled, floor-mounted, with or without fluid economizer < 23 Downflow or upflow, ducted SCOP = 2.74
≥ 23 and < 86 SCOP = 2.65
≥ 86 SCOP = 2.61
< 23 Upflow, non-ducted SCOP = 2.44
Horizontal SCOP = 2.71
≥ 23 and < 70 Upflow, non-ducted SCOP = 2.34
Horizontal SCOP = 2.60
≥ 70 Upflow, non-ducted SCOP = 2.24
Horizontal SCOP = 2.54
Glycol-cooled, floor-mounted, with or without fluid economizer < 23 Downflow or upflow, ducted SCOP = 2.48
≥ 23 and < 86 SCOP = 2.16
≥ 86 SCOP = 2.12
< 23 Upflow, non-ducted SCOP = 2.34
Horizontal SCOP = 2.44
≥ 23 and < 70 Upflow, non-ducted SCOP = 1.99
Horizontal SCOP = 2.10
≥ 70 Upflow, non-ducted SCOP = 1.94
Horizontal SCOP = 2.10
Air-cooled, ceiling-mounted, free air discharge condenser, with or without fluid economizer < 8.5 Ducted SCOP = 2.01
Non-ducted SCOP = 2.04
≥ 8.5 and < 19 Ducted SCOP = 1.97
Non-ducted SCOP = 2.00
≥ 19 Ducted SCOP = 1.87
Non-ducted SCOP = 1.89
Air-cooled, ceiling-mounted, ducted condenser, with or without fluid economizer < 8.5 Ducted SCOP = 1.82
Non-ducted SCOP = 1.68
≥ 8.5 and < 19 Ducted SCOP = 1.78
Non-ducted SCOP = 1.81
≥ 19 Ducted SCOP = 1.68
Non-ducted SCOP = 1.70
Water-cooled, ceiling-mounted, with or without fluid economizer < 8.5 Ducted SCOP = 2.33
Non-ducted SCOP = 2.36
≥ 8.5 and < 19 Ducted SCOP = 2.23
Non-ducted SCOP = 2.26
≥ 19 Ducted SCOP = 2.13
Non-ducted SCOP = 2.16
Glycol-cooled, ceiling-mounted, with or without fluid economizer < 8.5 Ducted SCOP = 1.92
Non-ducted SCOP = 1.95
≥ 8.5 and < 19 Ducted SCOP = 1.88
Non-ducted SCOP = 1.93
≥ 19 Ducted SCOP = 1.73
Non-ducted SCOP = 1.76
Table [5.2.12.1.-I] 5.2.12.1.-I
Performance Requirements for Variable Refrigerant Flow Systems
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.I. Footnote (1)
Single-phase air-cooled air conditioners and heat pumps, with or without heat recoveryPROPOSED CHANGE Table 5.2.12.1.I. Footnote (2) < 19 DOE 10 CFR, Part 430-2022, Subpart B, Appendix M1 See standard SEER2 = 14.3 / HSPF2 V = 6.6 PROPOSED CHANGE Table 5.2.12.1.I. Footnote (3)PROPOSED CHANGE Table 5.2.12.1.I. Footnote (4)
Air-cooled air conditioners and heat pumps, with or without heat recoveryPROPOSED CHANGE Table 5.2.12.1.I. Footnote (2) < 19 CSA C656 See standard SEER = 15 / HSPF V = 7.8PROPOSED CHANGE Table 5.2.12.1.I. Footnote (3)
Air-cooled air conditioners ≥ 19 and < 40 AHRI 1230 See standard EER = 11.2
IEER = 15.5
≥ 40 and < 70 EER = 11.0
IEER = 14.9
≥ 70 EER = 10.0
IEER = 13.9
Air-source heat pumps, with or without heat recovery ≥ 19 and < 40 EER = 10.8
IEER = 14.4
COPh = 3.30 evaluated at 8.3ºC db / 6.1ºC wb
COPh = 2.25 evaluated at –8.3ºC db / –9.4ºC wb
≥ 40 and < 70 EER = 10.4
IEER = 13.7
COPh = 3.20 evaluated at 8.3ºC db / 6.1ºC wb
COPh = 2.05 evaluated at –8.3ºC db / –9.4ºC wb
≥ 70 EER = 9.3
IEER = 12.5
COPh = 3.20 evaluated at 8.3ºC db / 6.1ºC wb
COPh = 2.05 evaluated at –8.3ºC db / –9.4ºC wb
Water-source heat pumps, with or without heat recovery < 40 EER = 11.8
IEER = 15.8
COPh = 4.3
≥ 40 EER = 9.8
IEER = 12.0
COPh = 4.0
Groundwater source heat pumps, with or without heat recovery < 40 EER = 16.2
COPh = 3.6
≥ 40 EER = 13.8
COPh = 3.3
Ground-source heat pumps, with or without heat recovery < 40 EER = 13.2
COPh = 3.1
≥ 40 EER = 10.8
COPh = 2.8
Table [5.2.12.1.-J] 5.2.12.1.-J
Performance Requirements for Direct-Expansion Dedicated Outdoor Air Systems
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.J. Footnote (1)
Air-cooled All capacities ANSI/AHRI 921 (SI) See standard ISMRE = 1.8
Air-source heat pumps See standard ISMRE = 1.8
ISCOP = 1.2
Water-cooled Cooling tower / condenser water ISMRE = 2.2
Chilled water ISMRE = 2.7
Water-source heat pumps Water source ISMRE = 1.8
ISCOP = 3.5
Groundwater source ISMRE = 2.3
ISCOP = 3.2
Ground-source, closed loop ISMRE = 2.2
ISCOP = 2.0
Air-cooled, with energy recovery See standard ISMRE = 2.4
Air-source heat pumps, with energy recovery See standard ISMRE = 2.4
ISCOP = 3.3
Water-cooled, with energy recovery Cooling tower / condenser water ISMRE = 2.4
Chilled water ISMRE = 3.0
Water-source heat pumps, with energy recovery Water source ISMRE = 2.2
ISCOP = 4.8
Groundwater source ISMRE = 2.6
ISCOP = 4.0
Ground-source, closed loop ISMRE = 2.4
ISCOP = 3.8
Table [5.2.12.1.-K] 5.2.12.1.-K
Performance Requirements for Packaged Water ChillersPROPOSED CHANGE Table 5.2.12.1.K. Footnote (1)
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.K. Footnote (2)
Path APROPOSED CHANGE Table 5.2.12.1.K. Footnote (3) Path BPROPOSED CHANGE Table 5.2.12.1.K. Footnote (3)
Air-cooled, with or without remote condensers, all types of compressors < 528 CAN/CSA-C743 See standard COPc = 2.985
IPLV = 4.048
COPc = 2.866
IPLV = 4.669
≥ 528 COPc = 2.985
IPLV = 4.137
COPc = 2.866
IPLV = 4.758
Water-cooled, rotary screw, scroll, or reciprocating compressor < 264 COPc = 4.694
IPLV = 5.867
COPc = 4.513
IPLV = 7.041
≥ 264 and < 528 COPc = 4.889
IPLV = 6.286
COPc = 4.694
IPLV = 7.184
≥ 528 and < 1 055 COPc = 5.334
IPLV = 6.519
COPc = 5.177
IPLV = 8.001
≥ 1 055 and < 2 110 COPc = 5.771
IPLV = 6.770
COPc = 5.633
IPLV = 8.586
≥ 2 110 COPc = 6.286
IPLV = 7.041
COPc = 6.018
IPLV = 9.264
Water-cooled, centrifugal compressor < 528 COPc = 5.771
IPLV = 6.401
COPc = 5.065
IPLV = 8.001
≥ 528 and < 1 055 COPc = 5.771
IPLV = 6.401
COPc = 5.544
IPLV = 8.801
≥ 1 055 and < 1 407 COPc = 6.286
IPLV = 6.770
COPc = 5.917
IPLV = 9.027
≥ 1 407 COPc = 6.286
IPLV = 7.041
COPc = 6.018
IPLV = 9.264
Single-effect absorption, air-cooled All capacities COPc = 0.600
Single-effect absorption, water-cooled COPc = 0.700
Double-effect absorption, indirect fire COPc = 1.000
IPLV = 1.050
Double-effect absorption, direct fire COPc = 1.000
IPLV = 1.000
Table [5.2.12.1.-L] 5.2.12.1.-L
Performance Requirements for Heat Pumps and Heat Recovery Chiller Packages
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.L. Footnote (1)
Path APROPOSED CHANGE Table 5.2.12.1.L. Footnote (2) Path BPROPOSED CHANGE Table 5.2.12.1.L. Footnote (2)
Air-source heat pumps, in cooling mode < 528 ANSI/AHRI 551/591 (SI) See standard COPc = 2.836
IPLV = 3.846
COPc = 2.723
IPLV = 4.436
≥ 528 COPc = 2.836
IPLV = 3.930
COPc = 2.723
IPLV = 4.520
Water-source heat pumps and heat recovery chillers, rotary screw, scroll, or reciprocating compressor, in cooling mode < 264 COPc = 4.659
IPLV = 5.574
COPc = 4.287
IPLV = 6.689
≥ 264 and < 528 COPc = 4.645
IPLV = 5.972
COPc = 4.459
IPLV = 6.825
≥ 528 and < 1 055 COPc = 5.067
IPLV = 6.193
COPc = 4.918
IPLV = 7.601
≥ 1 055 and < 2 110 COPc = 5.482
IPLV = 6.432
COPc = 5.351
IPLV = 8.157
≥ 2 110 COPc = 5.072
IPLV = 6.689
COPc = 5.717
IPLV = 8.801
Water-source heat pumps and heat recovery chillers, centrifugal compressor, in cooling mode < 264 COPc = 5.482
IPLV = 6.081
COPc = 4.812
IPLV = 7.601
≥ 264 and < 528 COPc = 5.482
IPLV = 6.081
COPc = 5.267
IPLV = 6.361
≥ 528 and < 1 055 COPc = 5.972
IPLV = 6.432
COPc = 5.621
IPLV = 8.567
≥ 1 055 COPc = 5.972
IPLV = 6.689
COPc = 5.717
IPLV = 8.801
Table [5.2.12.1.-M] 5.2.12.1.-M
Performance Requirements for Heat Pumps and Heat-Recovery Chiller Packages Based on Leaving Water Temperature
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating ConditionsPROPOSED CHANGE Table 5.2.12.1.M. Footnote (1) Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.M. Footnote (2)
If LWT = 40ºC If LWT = 50ºC If LWT = 60ºC
Air-source heat pumps, in heating mode All capacities ANSI/AHRI 551/591 (SI) EAT = 8ºC db / 6ºC wb COPh = 3.350 COPh = 2.720 COPh = 2.330
EAT = –8ºC db / –9ºC wb COPh = 2.250 COPh = 1.920 COPh = 1.640
Water-source heat pumps, rotary screw, scroll, reciprocating or centrifugal compressor, in heating mode < 1 055 EST / LST = 12ºC / 7ºC COPh = 4.760 COPh = 3.610 COPh = 2.660
EST / LST = 24ºC / 19ºC COPh = 3.530
≥ 1 055 EST / LST = 12ºC / 7ºC COPh = 5.060 COPh = 3.880 COPh = 2.950
EST / LST = 24ºC / 19ºC COPh = 3.870
Heat-recovery chillers, rotary screw, scroll, reciprocating or centrifugal compressor, simultaneous heating and cooling modes < 1 055 EST / LST = 12ºC / 7ºC COPhr = 8.550 COPhr = 6.290 COPhr = 4.390
EST / LST = 24ºC / 19ºC COPhr = 6.100
≥ 1 055 EST / LST = 12ºC / 7ºC COPhr = 9.140 COPhr = 6.850 COPhr = 4.960
EST / LST = 24ºC / 19ºC COPhr = 6.800
Table [5.2.12.1.-N] 5.2.12.1.-N
Performance Requirements for Boilers
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.N. Footnote (1)
Electric < 88 PROPOSED CHANGE Table 5.2.12.1.N. Footnote (2) Must be equipped with automatic water temperature controlPROPOSED CHANGE Table 5.2.12.1.N. Footnote (3)
≥ 88
Gas-firedPROPOSED CHANGE Table 5.2.12.1.N. Footnote (4) < 88 CAN/CSA-P.2 See standard AFUE = 90% (water)PROPOSED CHANGE Table 5.2.12.1.N. Footnote (3)
AFUE = 82% (steam)PROPOSED CHANGE Table 5.2.12.1.N. Footnote (3)
≥ 88 and < 733 DOE 10 CFR, Part 431, Subpart E, Appendix A See standard Et ≥ 90% (water)
Et ≥ 81% (steam)
≥ 733 and < 2 930 See standard Ec ≥ 90% (water)
Et ≥ 82% (steam)
Oil-fired < 88 CAN/CSA-P.2 See standard AFUE = 86% (water)
AFUE = 85% (steam)
≥ 88 and < 733 DOE 10 CFR, Part 431, Subpart E, Appendix A See standard Et = 87% (water)
Et = 84% (steam)
≥ 733 and < 2 930 See standard Ec = 88% (water)
Et = 85% (steam)
Table [5.2.12.1.-O] 5.2.12.1.-O
Performance Requirements for Warm-Air Furnaces, Combination Warm-Air Furnace/Air-conditioning Units,
Duct Furnaces and Unit Heaters

Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.O. Footnote (1)
Electric furnaces < 66 DOE 10 CFR, Part 430, Subpart B, Appendix AaPROPOSED CHANGE Table 5.2.12.1.O. Footnote (2) FER = 0.044 × Qmax + 165PROPOSED CHANGE Table 5.2.12.1.O. Footnote (3)PROPOSED CHANGE Table 5.2.12.1.O. Footnote (4)
≥ 66 PROPOSED CHANGE Table 5.2.12.1.O. Footnote (2)
Gas-fired warm-air furnacesPROPOSED CHANGE Table 5.2.12.1.O. Footnote (5)PROPOSED CHANGE Table 5.2.12.1.O. Footnote (6) ≤ 66 CAN/CSA-P.2 and DOE 10 CFR, Part 430, Subpart B, Appendix Aa Without integrated cooling AFUE = 95%PROPOSED CHANGE Table 5.2.12.1.O. Footnote (3)
FER = 0.044 × Qmax + 195
Outdoor furnaces with integrated cooling AFUE = 78%PROPOSED CHANGE Table 5.2.12.1.O. Footnote (3)
FER = 0.044 × Qmax + 199
Through-the-wall, with integrated cooling AFUE = 90%PROPOSED CHANGE Table 5.2.12.1.O. Footnote (3)
FER = 0.044 × Qmax + 195
ANSI Z21.47/CSA 2.3 Three-phase electric supply AFUE = 78% or Et = 80%
> 66 and ≤ 117 See standard Et = 81%
Gas-fired packaged furnacesPROPOSED CHANGE Table 5.2.12.1.O. Footnote (5) ≤ 2 931 CAN/CSA-P.8, Annex C See standard Et = 80%
Gas-fired duct furnacesPROPOSED CHANGE Table 5.2.12.1.O. Footnote (5)PROPOSED CHANGE Table 5.2.12.1.O. Footnote (6) ≤ 2 931 ANSI Z83.8/CSA 2.6 See standard Et = 81%
Gas-fired unit heatersPROPOSED CHANGE Table 5.2.12.1.O. Footnote (3)PROPOSED CHANGE Table 5.2.12.1.O. Footnote (5) ≤ 2 931 CAN/CSA-P.11 See standard Et = 82%
Oil-fired warm-air furnaces ≤ 66 CAN/CSA-P.2 See standard Et = 84.5%
AFUE = 85%PROPOSED CHANGE Table 5.2.12.1.O. Footnote (3)
> 66 CSA B140.4 See standard Et = 82%
Oil-fired duct furnaces and unit heaters All capacities CSA B140.4 See standard Et = 81%
Table [5.2.12.1.-P] 5.2.12.1.-P
Performance Requirements for Other Fuel-Burning Equipment and Appliances
Forming Part of Sentences [5.2.12.1.] 5.2.12.1.([1] 1), 6.2.2.4.(2), 6.2.2.5.(1) and 8.4.4.18.(6)
Type of Equipment Cooling or Heating Capacity, kW Performance Testing Standard Rating Conditions Minimum PerformancePROPOSED CHANGE Table 5.2.12.1.P. Footnote (1)
Gas-fired fireplaces and stoves, non-decorative All capacities CAN/CSA-P.4.1 See standard FE = 50%, with direct vent and without standing pilot light
Solid-fuel-burning stoves All capacities EPA 40 CFR, Part 60, Subpart AAA and Subpart QQQQ, and CSA B415.1 See standard
Solid-fuel-burning boilers < 2 000 DIN EN 303-5 See standard
Gas-fired infrared heaters, high-intensityPROPOSED CHANGE Table 5.2.12.1.P. Footnote (2)PROPOSED CHANGE Table 5.2.12.1.P. Footnote (3) ≤ 117 per burner DIN EN 419 See standard NRE ≥ 55%
Gas-fired infrared heaters, tubular and low-intensityPROPOSED CHANGE Table 5.2.12.1.P. Footnote (2)PROPOSED CHANGE Table 5.2.12.1.P. Footnote (3) DIN EN 416 See standard NRE ≥ 45%

Impact analysis

This proposed change would help Code users and authorities having jurisdiction to assess whether equipment conforms to the Code.

This proposed change is expected to be cost neutral because it simply aligns the NECB requirements with the Canadian Energy Efficiency Regulations, 2016.

Enforcement implications

This proposed change would facilitate enforcement since the metrics used in the NECB would align with those of the Canadian Energy Efficiency Regulations, 2016 and the US Department of Energy, Energy Conservation Program for Consumer Products.

Who is affected

Designers, engineers, architects, manufacturers, builders, specification writers and building officials.

OBJECTIVE-BASED ANALYSIS OF NEW OR CHANGED PROVISIONS

NECB20 Div.B 5.2.12.1. (first printing)

[5.2.12.1.] 5.2.12.1. ([1] 1) [F95,F98,F99-OE1.1]
Date modified: