The 2020 edition of the National Building Code of Canada (NBC) introduced energy efficiency performance tiers in Section 9.36. of Division B, with increasing levels of improvement for buildings and houses, to provide authorities having jurisdiction with the option to adopt the energy performance levels most suitable to their needs.
Although performance modeling is common in the industry, many Code users have requested that prescriptive compliance paths remain in the National Model Codes to provide simplicity in achieving energy compliance.
Failure to develop a prescriptive compliance path for Tier 3 could force Code users to rely on more complicated compliance paths.
The proposed prescriptive requirements for Tier 3 would provide acceptable solutions for different components of the building to improve the total energy performance. Together with the tiered energy performance path in Subsection 9.36.7. and the tiered points-based prescriptive trade-off path in Subsection 9.36.9., the prescriptive path is one of the compliance options that provide an acceptable means of achieving the performance goal of reducing energy consumption by at least 20% and percent heat loss by at least 10% for buildings with a volume of conditioned space (or “conditioned volume”) greater than 300 m3, and by reducing energy consumption by at least 10% and percent heat loss by at least 5% for buildings with a conditioned volume less than or equal to 300 m3.
In developing the Tier 3 prescriptive solutions, many different possible solutions were considered. These possible solutions were compared against the points-based trade-off path to ensure compliance.
Building Envelope
A Tier 3 envelope package was developed for each climate zone. 240 building archetypes were modeled and categorized by volume, with 219 having a conditioned volume greater than 300 m3 and 21 having a volume of less than or equal to 300 m3.
For the applicable building volume and climate zone, two criteria were used to define acceptable Tier 3 building envelope package solutions:
There are numerous combinations of envelope measures that meet the above criteria. Therefore, additional selection criteria needed to be defined to reduce the number of prescriptive envelope package solutions to one for each climate and building volume.
The two additional criteria were as follows:
A fourth criterion was defined to ensure that, when going from a warmer to colder climate zone, the thermal performance of a building envelope component was not reduced. For example, a solution that uses 4.88 RSI for the effective thermal resistance of above-grade walls in climate zone 6 would not be used if the solution for climate zone 5 used 5.69 RSI for above-grade walls.
Airtightness
There is no mandatory airtightness level that must be met to achieve Tier 3.
HVAC and Service Water Heating System
Heat/energy recovery ventilators (HRVs/ERVs) are considered an economical way to save energy; it was proposed that all Tier 3 houses be equipped with HRVs/ERVs with a minimum 70% sensible recovery efficiency. As HRVs/ERVs are required for the Tier 1 and Tier 2 packages, the requirement is maintained in the Tier 3 package.
For buildings with a conditioned volume less than or equal to 300 m3, no upgrades beyond Code-minimum space heating systems are required to achieve Tier 3. For buildings with a conditioned volume greater than 300 m3, upgrades are required when heating with a gas- or oil-fired furnace.
For buildings with a conditioned volume less than or equal to 300 m3, no upgrades beyond Code-minimum service water heating systems are required to achieve Tier 3. For buildings with a conditioned volume greater than 300 m3, upgrades are required when the water heater is gas- or oil-fired.
| Above-Ground Opaque Building Assembly | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (1) in Celsius Degree-Days | |||||
|---|---|---|---|---|---|---|
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
|
| Minimum Effective Thermal Resistance (RSI), (m2×K)/W | ||||||
| Ceilings below attics | 6.91 | 8.67 | 8.67 | 10.43 | 10.43 | 10.43 |
| Cathedral ceilings and flat roofs | 4.67 | 4.67 | 4.67 | 5.02 | 5.02 | 5.02 |
| Walls | 3.08 | 3.08 | 3.28 | 3.28 | 3.85 | 3.85 |
| Floors over unheated spaces | 4.67 | 4.67 | 4.67 | 5.02 | 5.02 | 5.02 |
| Above-Ground Opaque Building Assembly | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (1) in Celsius Degree-Days | |||||
|---|---|---|---|---|---|---|
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
|
| Minimum Effective Thermal Resistance (RSI), (m2×K)/W | ||||||
| Ceilings below attics | 6.91 | 8.67 | 10.43 | 10.43 | 10.43 | 10.43 |
| Cathedral ceilings and flat roofs | 4.67 | 4.67 | 5.02 | 5.02 | 5.02 | 5.02 |
| Walls | 3.28 | 3.28 | 3.58 | 3.69 | 4.29 | 4.57 |
| Floors over unheated spaces | 4.67 | 4.67 | 4.67 | 5.02 | 5.02 | 5.02 |
| Above-Ground Opaque Building Assembly | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (1) in Celsius Degree-Days | |||||
|---|---|---|---|---|---|---|
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
|
| Minimum Effective Thermal Resistance (RSI), (m2×K)/W | ||||||
| Ceilings below attics | 6.91 | 10.43 | 12.19 | 12.19 | 12.19 | 12.19 |
| Cathedral ceilings and flat roofs | 4.67 | 4.67 | 5.02 | 5.02 | 5.02 | 5.02 |
| Walls | 4.40 | 4.40 | 4.57 | 4.57 | 5.45 | 5.45 |
| Floors over unheated spaces | 4.67 | 4.67 | 4.67 | 5.02 | 5.02 | 5.02 |
| Component | Thermal CharacteristicsPROPOSED CHANGE Table Footnote (1) | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days | |||||
|---|---|---|---|---|---|---|---|
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
||
| Windows and doors | Max. U-value, W/(m2×K) | 1.44 | 1.22 | 1.22 | 1.22 | 1.05 | 1.05 |
| Min. Energy Rating | 29 | 34 | 34 | 34 | 40 | 40 | |
| Building Assembly Below-Grade or in Contact with the GroundPROPOSED CHANGE Table Footnote (1) | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days | |||||
|---|---|---|---|---|---|---|
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
|
| Minimum Effective Thermal Resistance (RSI), (m2×K)/W | ||||||
| Foundation walls | 1.99 | 2.98 | 2.98 | 3.46 | 3.46 | 3.97 |
| Unheated floorsPROPOSED CHANGE Table Footnote (3)below frost linePROPOSED CHANGE Table Footnote (4)PROPOSED CHANGE Table Footnote (5) | uninsulated | uninsulated | uninsulated | uninsulated | uninsulated | uninsulated |
| Unheated floorsPROPOSED CHANGE Table Footnote (3)above frost linePROPOSED CHANGE Table Footnote (5) | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 4.44 | 4.44 |
| Heated floorsPROPOSED CHANGE Table Footnote (6) | 2.32 | 2.32 | 2.32 | 2.84 | 2.84 | 2.84 |
| Slabs-on-grade with an integral footingPROPOSED CHANGE Table Footnote (6) | 1.96 | 1.96 | 1.96 | 3.72 | 3.72 | 4.59 |
| Building Assembly Below-Grade or in Contact with the GroundPROPOSED CHANGE Table Footnote (1) | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days | |||||
|---|---|---|---|---|---|---|
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
|
| Minimum Effective Thermal Resistance (RSI), (m2×K)/W | ||||||
| Foundation walls | 2.98 | 3.46 | 3.46 | 4.78 | 4.78 | 4.78 |
| Unheated floorsPROPOSED CHANGE Table Footnote (3)below frost linePROPOSED CHANGE Table Footnote (4)PROPOSED CHANGE Table Footnote (5) | uninsulated | uninsulated | uninsulated | uninsulated | uninsulated | uninsulated |
| Unheated floorsPROPOSED CHANGE Table Footnote (3)above frost linePROPOSED CHANGE Table Footnote (5) | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 4.44 | 4.44 |
| Heated floorsPROPOSED CHANGE Table Footnote (6) | 2.32 | 2.32 | 2.32 | 2.84 | 2.84 | 2.84 |
| Slabs-on-grade with an integral footingPROPOSED CHANGE Table Footnote (6) | 1.96 | 1.96 | 2.84 | 3.72 | 3.72 | 4.59 |
| Building Assembly Below-Grade or in Contact with the GroundPROPOSED CHANGE Table Footnote (1) | Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days | |||||
|---|---|---|---|---|---|---|
| Zone 4 < 3000 |
Zone 5 3000 to 3999 |
Zone 6 4000 to 4999 |
Zone 7A 5000 to 5999 |
Zone 7B 6000 to 6999 |
Zone 8 ≥ 7000 |
|
| Minimum Effective Thermal Resistance (RSI), (m2×K)/W | ||||||
| Foundation walls | 3.46 | 3.46 | 3.90 | 4.78 | 4.78 | 5.22 |
| Unheated floorsPROPOSED CHANGE Table Footnote (3)below frost linePROPOSED CHANGE Table Footnote (4)PROPOSED CHANGE Table Footnote (5) | uninsulated | uninsulated | uninsulated | uninsulated | uninsulated | uninsulated |
| Unheated floorsPROPOSED CHANGE Table Footnote (3)above frost linePROPOSED CHANGE Table Footnote (5) | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 4.44 | 4.44 |
| Heated floorsPROPOSED CHANGE Table Footnote (6) | 2.32 | 2.32 | 2.32 | 2.84 | 2.84 | 2.84 |
| Slabs-on-grade with an integral footingPROPOSED CHANGE Table Footnote (6) | 1.96 | 1.96 | 3.72 | 3.72 | 4.59 | 4.59 |
| Principal Heating SystemPROPOSED CHANGE Table Footnote (1) | Performance RequirementPROPOSED CHANGE Table Footnote (2) |
| Gas-fired combined space- and service water heating systems (combos)PROPOSED CHANGE Table Footnote (3) | TPF ≥ 0.85 |
| Gas-fired warm-air furnacesPROPOSED CHANGE Table Footnote (3) | AFUE ≥ 98% |
| Oil-fired appliances | AFUE ≥ 87% |
| Heat pumps | See Table 9.36.3.10. |
| Other space-heating appliances | See Table 9.36.3.10. |
| Type of EquipmentPROPOSED CHANGE Table Footnote (1) | Performance RequirementPROPOSED CHANGE Table Footnote (2) |
| Storage type service water heaters | |
|
Gas-firedPROPOSED CHANGE Table Footnote (3)
|
UEF ≥ 0.83 or EF ≥ 0.8 |
|
Oil-fired
|
UEF ≥ 0.83 or EF ≥ 0.8 |
| Gas-fired combined space- and service water heating systems (combos)PROPOSED CHANGE Table Footnote (3) | TPF ≥ 0.85 |
| Other service water heating equipment | See Table 9.36.4.2. |
This proposed change would improve energy performance by providing the prescriptive requirements for building envelopes, service water heating systems and HVAC systems to achieve Energy Performance Tier 3.
Buildings with a total volume of conditioned space of less than or equal to 300 m³ have the following energy performance targets: a percent improvement of ≥10%, a percent energy target of ≤90% and a percent heat loss reduction of ≥5%.
Buildings with a total volume of conditioned space of greater than 300 m³ have the following energy performance targets: a percent improvement of ≥20%, a percent energy target of ≤80% and a percent heat loss reduction of ≥10%.
The incremental costing below is derived from the specifications and detailed costing data found in the supporting document. Total costs by archetype have been rounded to the nearest $10.
Archetype A1 — Apartment/condominium unit, one bedroom
Table 1. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A1
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 13.93 |
| Floor area | 46.30 |
| Insulated attic area | 46.30 |
| Window area | 2.36 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 105.45 |
Tier 1 and Tier 2 are identical for Archetype A1, as its conditioned volume is ≤ 300m3.
Table 2. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A1
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Above-grade walls | –51.35* | –51.35* | –34.44* | –34.44* | 136.14 | 136.14 |
| Windows and sliding glass doors | 172.76 | 243.79 | 243.79 | 138.86 | 125.95 | 125.95 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| HVAC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SWH | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 320 | 390 | 410 | 300 | 460 | 460 |
*See supplemental document Section 3.4.
Archetype A2 — Bungalow, detached without basement or garage
Table 3. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A2
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 126.05 |
| Ground floor area | 95.00 |
| Slab in contact with the ground | 101.7 |
| Insulated attic area | 95.00 |
| Window area | 10.75 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 217.44 |
Tier 1 and Tier 2 are identical for Archetype A2, as its conditioned volume is ≤ 300m3.
Table 4. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A2
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 754.30 | 754.18 | 922.45 | 0.00 | 0.00 |
| Above-grade walls | –464.66* | –464.66* | –311.61* | –311.61* | 1,231.92 | 1,231.92 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Windows and sliding glass doors | 786.95 | 1,110.48 | 1,110.48 | 632.53 | 573.73 | 573.73 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| HVAC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| SWH | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 520 | 1,600 | 1,750 | 1,440 | 2,010 | 2,010 |
*See supplemental document Section 3.4.
Archetype A3 — Bungalow, detached with basement and garage
Table 5. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A3
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 69.49 |
| Foundation walls | 46.10 |
| Ground floor area | 90.45 |
| Insulated attic area | 90.45 |
| Window area | 19.74 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 411.36 |
Table 6. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A3 – Gas-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 718.06 | 1,596.34 | 878.28 | 0.00 | 0.00 |
| Above-grade walls | –171.79* | –171.79* | 5.59 | 422.98 | 1,069.67 | 1,335.99 |
| Foundation walls | 1,318.41 | 239.78 | 1,558.19 | 2,005.82 | 2,005.82 | 2,005.82 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 1,445.05 | 2,039.16 | 2,039.16 | 1,161.51 | 1,053.43 | 1,053.43 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Gas-fired furnace | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 |
| Gas-fired storage-type water heater | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 |
| Total | 7,410 | 7,850 | 10,220 | 9,490 | 9,150 | 9,420 |
*See supplemental document Section 3.4.
Table 7. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A3 – Gas-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,596.44 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 84.37 | 84.37 | 340.71 | 679.14 | 390.53 | 656.85 |
| Foundation walls | 0.00 | 239.72 | 239.78 | 527.81 | 527.81 | 527.81 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 567.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Gas-fired furnace | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 |
| Gas-fired storage-type water heater | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 |
| Total | 5,470 | 5,350 | 7,000 | 6,030 | 5,740 | 6,010 |
Table 8. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A3 – Oil-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 718.06 | 1,596.34 | 878.28 | 0.00 | 0.00 |
| Above-grade walls | –171.79* | –171.79* | 5.59 | 422.98 | 1,069.67 | 1,335.99 |
| Foundation walls | 1,318.41 | 239.78 | 1,558.19 | 2,005.82 | 2,005.82 | 2,005.82 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 1,445.05 | 2,039.16 | 2,039.16 | 1,161.51 | 1,053.43 | 1,053.43 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Oil-fired furnace | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 |
| Oil-fired storage-type water heater | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 |
| Total | 4,670 | 4,910 | 7,280 | 6,550 | 6,210 | 6,480 |
*See supplemental document Section 3.4.
Table 9. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A3 – Oil-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,596.44 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 84.37 | 84.37 | 340.71 | 679.14 | 390.53 | 656.85 |
| Foundation walls | 0.00 | 239.72 | 239.78 | 527.81 | 527.81 | 527.81 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 567.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Oil-fired furnace | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 |
| Oil-fired storage-type water heater | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 |
| Total | 2,730 | 2,400 | 4,060 | 3,090 | 2,800 | 3,070 |
Table 10. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A3 – Heat Pump
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 718.06 | 1,596.34 | 878.28 | 0.00 | 0.00 |
| Above-grade walls | –171.79* | –171.79* | 5.59 | 422.98 | 1,069.67 | 1,335.99 |
| Foundation walls | 1,318.41 | 239.78 | 1,558.19 | 2,005.82 | 2,005.82 | 2,005.82 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 1,445.05 | 2,039.16 | 2,039.16 | 1,161.51 | 1,053.43 | 1,053.43 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Heat pump | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Code minimum storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 2,790 | 3,020 | 5,400 | 4,670 | 4,330 | 4,600 |
*See supplemental document Section 3.4.
Table 11. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A3 – Heat Pump
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,596.44 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 84.37 | 84.37 | 340.71 | 679.14 | 390.53 | 656.85 |
| Foundation walls | 0.00 | 239.72 | 239.78 | 527.81 | 527.81 | 527.81 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 567.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat pump | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Code minimum storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 2,790 | 3,020 | 5,200 | 4,470 | 4,130 | 4,400 |
Table 12. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A3 – Electric Resistance
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 1,596.34 | 2,394.51 | 1,676.45 | 798.17 | 798.17 |
| Above-grade walls | 1,079.83 | 1,079.83 | 1,079.83 | 1,079.83 | 2,937.28 | 2,937.28 |
| Foundation walls | 2,867.95 | 239.72 | 2,796.43 | 2,005.82 | 2,005.82 | 2,277.52 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 1,445.05 | 2,039.14 | 2,039.16 | 1,161.50 | 1,053.52 | 1,053.52 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Electric resistance furnace | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 5,590 | 5,150 | 8,510 | 6,120 | 6,990 | 7,270 |
Table 13. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A3 – Electric Resistance
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 730.85 | 2,394.21 | 798.17 | 797.77 | 797.77 |
| Above-grade walls | 1,335.99 | 1,335.99 | 1,335.99 | 1,335.99 | 2,258.14 | 2,258.14 |
| Foundation walls | 239.78 | 239.72 | 1,478.01 | 527.81 | 527.81 | 799.51 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | $0.00 | 0.00 |
| Windows and sliding glass doors | 567.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance furnace | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 2,340 | 2,510 | 5,210 | 2,660 | 3,580 | 3,850 |
Table 14. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A4
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 142.78 |
| Foundation walls | 22.69 |
| Ground floor area | 57.25 |
| Insulated attic area | 70.56 |
| Window area | 15.74 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 427.46 |
Table 15. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A4 – Gas-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 560.16 | 1,245.31 | 685.15 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –352.97* | –352.97* | 11.50 | 869.09 | 2,197.84 | 2,745.05 |
| Foundation walls | 648.91 | 118.02 | 766.93 | 987.25 | 987.25 | 987.25 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 1,152.23 | 1,625.95 | 1,625.95 | 926.15 | 839.97 | 839.97 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Gas-fired furnace | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 |
| Gas-fired storage-type water heater | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 |
| Total | 6,470 | 6,970 | 8,670 | 8,490 | 9,050 | 9,590 |
*See supplemental document Section 3.4.
Table 16. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A4 – Gas-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,245.38 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 173.36 | 173.36 | 537.83 | 1,395.42 | 802.42 | 1,349.62 |
| Foundation walls | 0.00 | 117.99 | 118.02 | 259.78 | 259.78 | 259.78 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 452.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Gas-fired furnace | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 |
| Gas-fired storage-type water heater | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 |
| Total | 5,650 | 5,310 | 6,720 | 6,480 | 5,880 | 6,430 |
Table 17. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A4 – Oil-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 560.16 | 1,245.31 | 685.15 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –352.97* | –352.97* | 11.50 | 869.09 | 2,197.84 | 2,745.05 |
| Foundation walls | 648.91 | 118.02 | 766.93 | 987.25 | 987.25 | 987.25 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 1,152.23 | 1,625.95 | 1,625.95 | 926.15 | 839.97 | 839.97 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Oil-fired furnace | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 |
| Oil-fired storage-type water heater | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 |
| Total | 3,530 | 4,030 | 5,730 | 5,550 | 6,110 | 6,650 |
*See supplemental document Section 3.4.
Table 18. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A4 – Oil-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,245.38 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 173.36 | 173.36 | 537.83 | 1,395.42 | 802.42 | 1,349.62 |
| Foundation walls | 0.00 | 117.99 | 118.02 | 259.78 | 259.78 | 259.78 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 452.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Oil-fired furnace | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 |
| Oil-fired storage-type water heater | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 |
| Total | 2,710 | 2,370 | 3,780 | 3,540 | 2,940 | 3,490 |
Table 19. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A4 – Heat Pump
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 560.16 | 1,245.31 | 685.15 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –352.97* | –352.97* | 11.50 | 869.09 | 2,197.84 | 2,745.05 |
| Foundation walls | 648.91 | 118.02 | 766.93 | 987.25 | 987.25 | 987.25 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 1,152.23 | 1,625.95 | 1,625.95 | 926.15 | 839.97 | 839.97 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Heat pump | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Code minimum storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 1,650 | 2,150 | 3,850 | 3,670 | 4,220 | 4,770 |
*See supplemental document Section 3.4.
Table 20. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A4 – Heat Pump
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,245.38 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 173.36 | 173.36 | 537.83 | 1,395.42 | 802.42 | 1,349.62 |
| Foundation walls | 0.00 | 117.99 | 118.02 | 259.78 | 259.78 | 259.78 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 452.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat pump | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Code minimum storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 830 | 490 | 1,900 | 1,650 | 1,060 | 1,610 |
Table 21. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A4 – Electric Resistance
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 1,245.31 | 1,867.96 | 1,307.80 | 622.65 | 622.65 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 2,218.71 | 2,218.71 | 2,218.71 | 2,218.71 | 6,035.18 | 6,035.18 |
| Foundation walls | 766.93 | 117.99 | 1,376.37 | 987.25 | 987.25 | 1,120.98 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 1,152.23 | 1,625.94 | 1,625.95 | 926.14 | 840.04 | 840.04 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Electric resistance furnace | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 4,340 | 5,410 | 7,290 | 5,640 | 8,690 | 8,820 |
Table 22. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A4 – Electric Resistance
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 570.14 | 1,867.72 | 622.65 | 622.34 | 622.34 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 2,745.05 | 2,745.05 | 2,745.05 | 2,745.05 | 4,639.76 | 4,639.76 |
| Foundation walls | 118.02 | 117.99 | 727.47 | 259.78 | 259.78 | 393.51 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and glass doors | 452.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance furnace | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 3,510 | 3,630 | 5,340 | 3,630 | 5,520 | 5,660 |
Table 23. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A5 (Mid-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 38.44 |
| Foundation walls | 7.14 |
| Ground floor area | 54.50 |
| Insulated attic area | 74.05 |
| Window area | 12.12 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 425.35 |
Table 24. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (Mid-Unit) – Gas-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 587.87 | 1,306.90 | 719.03 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –95.03* | –95.03* | 3.09 | 233.98 | 591.71 | 739.04 |
| Foundation walls | 204.20 | 37.14 | 241.33 | 310.66 | 310.66 | 310.66 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 887.24 | 1,252.00 | 1,252.00 | 713.14 | 646.79 | 646.79 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Gas-fired furnace | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 |
| Gas-fired storage-type water heater | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 |
| Total | 6,020 | 6,810 | 7,830 | 7,000 | 6,570 | 6,730 |
*See supplemental document Section 3.4.
Table 25. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (Mid-Unit) – Gas-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,306.98 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 46.67 | 46.67 | 144.80 | 375.68 | 216.03 | 363.35 |
| Foundation walls | 0.00 | 37.13 | 37.14 | 81.75 | 81.75 | 81.75 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 348.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Gas-fired furnace | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 |
| Gas-fired storage-type water heater | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 |
| Total | 5,420 | 5,110 | 6,310 | 5,280 | 5,120 | 5,270 |
Table 26. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (Mid-Unit) – Oil-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 587.87 | 1,306.90 | 719.03 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –95.03* | –95.03* | 3.09 | 233.98 | 591.71 | 739.04 |
| Foundation walls | 204.20 | 37.14 | 241.33 | 310.66 | 310.66 | 310.66 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 887.24 | 1,252.00 | 1,252.00 | 713.14 | 646.79 | 646.79 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Oil-fired furnace | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 |
| Oil-fired storage-type water heater | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 |
| Total | 3,080 | 3,870 | 4,890 | 4,060 | 3,630 | 3,780 |
*See supplemental document Section 3.4.
Table 27. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (Mid-Unit) – Oil-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,306.98 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 46.67 | 46.67 | 144.80 | 375.68 | 216.03 | 363.35 |
| Foundation walls | 0.00 | 37.13 | 37.14 | 81.75 | 81.75 | 81.75 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 348.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Oil-fired furnace | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 |
| Oil-fired storage-type water heater | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 |
| Total | 2,480 | 2,160 | 3,370 | 2,340 | 2,180 | 2,330 |
Table 28. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (Mid-Unit) – Heat Pump
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 587.87 | 1,306.90 | 719.03 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –95.03* | –95.03* | 3.09 | 233.98 | 591.71 | 739.04 |
| Foundation walls | 204.20 | 37.14 | 241.33 | 310.66 | 310.66 | 310.66 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 887.24 | 1,252.00 | 1,252.00 | 713.14 | 646.79 | 646.79 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Heat pump | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Code minimum storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 1,200 | 1,990 | 3,010 | 2,180 | 1,750 | 1,900 |
*See supplemental document Section 3.4.
Table 29. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (Mid-Unit) – Heat Pump
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,306.98 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 46.67 | 46.67 | 144.80 | 375.68 | 216.03 | 363.35 |
| Foundation walls | 0.00 | 37.13 | 37.14 | 81.75 | 81.75 | 81.75 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 348.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat pump | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Code minimum storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 590 | 280 | 1,490 | 460 | 300 | 440 |
Table 30. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (Mid-Unit) – Electric Resistance
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 1,306.90 | 1,960.35 | 1,372.48 | 653.45 | 653.45 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 597.33 | 597.33 | 597.33 | 597.33 | 1,624.82 | 1,624.82 |
| Foundation walls | 241.33 | 37.13 | 433.11 | 310.66 | 310.66 | 352.74 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 887.24 | 1,252.00 | 1,252.00 | 713.14 | 646.84 | 646.84 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Electric resistance furnace | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 1,920 | 3,390 | 4,440 | 3,190 | 3,430 | 3,470 |
Table 31. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (Mid-Unit) – Electric Resistance
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 598.34 | 1,960.10 | 653.45 | 653.12 | 653.12 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 739.04 | 739.04 | 739.04 | 739.04 | 1,249.14 | 1,249.14 |
| Foundation walls | 37.14 | 37.13 | 228.92 | 81.75 | 81.75 | 123.83 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 348.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance furnace | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 1,320 | 1,570 | 2,930 | 1,470 | 1,980 | 2,030 |
Table 32. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A5 (End-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 90.34 |
| Foundation walls | 16.14 |
| Ground floor area | 54.50 |
| Insulated attic area | 74.05 |
| Window area | 13.59 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 425.35 |
Table 33. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (End-Unit) – Gas-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 587.96 | 1,306.98 | 719.03 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –223.14* | –223.14* | 7.23 | 550.17 | 1,390.33 | 1,737.24 |
| Foundation walls | 461.60 | 83.93 | 545.53 | 702.25 | 702.25 | 702.25 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 994.79 | 1,403.85 | 1,403.85 | 799.64 | 725.30 | 725.30 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Gas-fired furnace | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 |
| Gas-fired storage-type water heater | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 |
| Total | 6,260 | 6,880 | 8,290 | 7,790 | 7,840 | 8,190 |
*See supplemental document Section 3.4.
Table 34. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (End-Unit) – Gas-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,306.98 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 109.31 | 109.31 | 340.58 | 882.62 | 507.71 | 853.71 |
| Foundation walls | 0.00 | 83.93 | 85.54 | 184.80 | 184.80 | 184.80 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 390.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Gas-fired furnace | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 | 2,300.00 |
| Gas-fired storage-type water heater | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 | 2,523.00 |
| Total | 5,520 | 5,220 | 6,560 | 5,890 | 5,510 | 5,860 |
Table 35. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (End-Unit) – Oil-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 587.96 | 1,306.98 | 719.03 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –223.14* | –223.14* | 7.23 | 550.17 | 1,390.33 | 1,737.24 |
| Foundation walls | 461.60 | 83.93 | 545.53 | 702.25 | 702.25 | 702.25 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 994.79 | 1,403.85 | 1,403.85 | 799.64 | 725.30 | 725.30 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Oil-fired furnace | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 |
| Oil-fired storage-type water heater | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 |
| Total | 3,310 | 3,930 | 5,340 | 4,850 | 4,900 | 5,250 |
*See supplemental document Section 3.4.
Table 36. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (End-Unit) – Oil-Fired
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,306.98 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 109.31 | 109.31 | 340.58 | 882.62 | 507.71 | 853.71 |
| Foundation walls | 0.00 | 83.93 | 85.54 | 184.80 | 184.80 | 184.80 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 390.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Oil-fired furnace | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 | 1,510.00 |
| Oil-fired storage-type water heater | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 | 371.00 |
| Total | 2,580 | 2,270 | 3,610 | 2,950 | 2,570 | 2,920 |
Table 37. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (End-Unit) – Heat Pump
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 587.96 | 1,306.98 | 719.03 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | –223.14* | –223.14* | 7.23 | 550.17 | 1,390.33 | 1,737.24 |
| Foundation walls | 461.60 | 83.93 | 545.53 | 702.25 | 702.25 | 702.25 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 994.79 | 1,403.85 | 1,403.85 | 799.64 | 725.30 | 725.30 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Heat pump | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Code minimum storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 1,430 | 2,050 | 3,460 | 2,970 | 3,020 | 3,360 |
*See supplemental document Section 3.4.
Table 38. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (End-Unit) – Heat Pump
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 0.00 | 1,306.98 | 0.00 | 0.00 | 0.00 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 109.31 | 109.31 | 340.58 | 882.62 | 507.71 | 853.71 |
| Foundation walls | 0.00 | 83.93 | 85.54 | 184.80 | 184.80 | 184.80 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 390.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat pump | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Code minimum storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 700 | 390 | 1,730 | 1,070 | 690 | 1,040 |
Table 39. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (End-Unit) – Electric Resistance
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 1,306.98 | 1,960.10 | 1,372.15 | 653.12 | 653.12 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | $0.00 |
| Above-grade walls | 1,403.88 | 1,403.88 | 1,403.88 | 1,403.88 | 3,818.67 | 3,818.67 |
| Foundation walls | 545.53 | 83.93 | 979.05 | 702.25 | 702.25 | 797.32 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 994.79 | 1,403.85 | 1,403.85 | 799.64 | 725.30 | 725.30 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| Electric resistance furnace | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 3,140 | 4,400 | 5,950 | 4,480 | 6,100 | 6,190 |
Table 40. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (End-Unit) – Electric Resistance
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 598.32 | 1,960.10 | 653.12 | 653.12 | 653.12 |
| Floors over unheated spaces | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Above-grade walls | 1,737.24 | 1,737.24 | 1,737.24 | 1,737.24 | 2,936.05 | 2,936.05 |
| Foundation walls | 83.93 | 83.93 | 517.45 | 184.80 | 184.80 | 279.87 |
| Unheated floors below frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 390.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HRV/ERV | 200.00 | 200.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance furnace | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electric resistance storage-type water heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 2,410 | 2,620 | 4,210 | 2,570 | 3,770 | 3,870 |
Table 41. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Lower Mid-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 21.38 |
| Foundation walls | 11.28 |
| Ground floor area | 58.07 |
| Window area | 10.12 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 279.54 |
Tier 1 and Tier 2 are identical for archetype A6 as its conditioned volume is ≤ 300m3.
Table 42. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A6 (Lower Mid-Unit)
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Above-grade walls | –78.81* | –78.81* | –52.85* | –52.85* | 208.95 | 208.95 |
| Foundation walls | 0.00 | 0.00 | 322.60 | 58.67 | 58.67 | 361.65 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 740.83 | 1,045.40 | 1,045.40 | 595.46 | 540.10 | 540.10 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| HVAC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Service water heating equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 860 | 1,170 | 1,510 | 800 | 1,010 | 1,310 |
*See supplemental document Section 3.4.
Table 43. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Upper Mid-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 44.13 |
| Ground floor area | 58.07 |
| Insulated attic area | 59.85 |
| Window area | 10.80 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 284.13 |
Tier 1 and Tier 2 are identical for archetype A6 as its conditioned volume is ≤ 300m3.
Table 44. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A6 (Upper Mid-Unit)
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 475.21 | 475.14 | 581.14 | 0.00 | 0.00 |
| Above-grade walls | –162.68* | –162.68* | –109.10* | –109.10* | 431.29 | 431.29 |
| Windows and sliding glass doors | 790.61 | 1,115.65 | 1,115.64 | 635.47 | 576.40 | 576.40 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| HVAC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Service water heating equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 830 | 1,630 | 1,680 | 1,310 | 1,210 | 1,210 |
*See supplemental document Section 3.4.
Table 45. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Lower End-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 50.32 |
| Foundation walls | 29.43 |
| Ground floor area | 58.07 |
| Window area | 11.91 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 279.54 |
Tier 1 and Tier 2 are identical for archetype A6 as its conditioned volume is ≤ 300m3.
Table 46. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A6 (Lower End-Unit)
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Above-grade walls | –185.50* | –185.50* | –124.40* | –124.40* | 491.79 | 491.79 |
| Foundation walls | 0.00 | 0.00 | 841.67 | 153.07 | 153.07 | 943.56 |
| Unheated floors above frost line | 0.00 | 0.00 | 0.00 | 0.00 | n/a | n/a |
| Heated and unheated floors on permafrost | n/a | n/a | n/a | n/a | 0.00 | 0.00 |
| Windows and sliding glass doors | 871.86 | 1,230.31 | 1,230.30 | 700.78 | 635.64 | 635.64 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | $200.00 |
| HVAC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Service water heating equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 890 | 1,240 | 2,150 | 930 | 1,480 | 2,270 |
*See supplemental document Section 3.4.
Table 47. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Upper End-Unit)
| Area Part of or Surrounded by Building Envelope | Total Area, m2 |
| Above-grade walls | 110.07 |
| Ground floor area | 58.07 |
| Insulated attic area | 59.85 |
| Window area | 12.59 |
| Conditioned Space | Total Volume, m3 |
| Conditioned space | 284.13 |
Tier 1 and Tier 2 are identical for archetype A6 as its conditioned volume is ≤ 300m3.
Table 48. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A6 (Upper End-Unit)
| Building Component | Incremental Cost, $ | |||||
| Climate Zone | ||||||
| 4 | 5 | 6 | 7A | 7B | 8 | |
| Ceiling below attic | 0.00 | 475.21 | 475.14 | 581.14 | 0.00 | 0.00 |
| Above-grade walls | –405.75* | –405.75* | –272.11* | –272.11* | 1,075.74 | 1,075.74 |
| Windows and sliding glass doors | 921.64 | 1,300.56 | 360.06 | 740.80 | 671.93 | 671.93 |
| HRV/ERV | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 | 200.00 |
| HVAC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Service water heating equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 720 | 1,570 | 760 | 1,250 | 1,950 | 1,950 |
*See supplemental document Section 3.4.
Table 49. Climate Zones by Region
| Degree-Days Below 18°C | BC | Alberta | Saskatchewan and Manitoba | Ontario | Quebec | Atlantic Canada | Northern Canada |
| Zone 4: HDD < 3000 | Yes | No | No | No | No | No | No |
| Zone 5: HDD 3000 to 3999 | Yes | No | No | Yes | No | Yes | No |
| Zone 6: HDD 4000 to 4999 | Yes | Yes | Yes | Yes | Yes | Yes | No |
| Zone 7A: HDD 5000 to 5999 | Yes | Yes | Yes | Yes | Yes | Yes | No |
| Zone 7B: HDD 6000 to 6999 | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
| Zone 8: HDD ≥ 7000 | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Table 50. Incremental Cost to Achieve Tier 3 Compared to Tier 2 for Each Archetype by Region
| Archetype | Incremental Cost, $ | ||||||
| BC (Climate Zone 4–8) | AB (Climate Zone 6–8) | SK and MB (Climate Zone 6–8) | ON (Climate Zone 5–8) | QC (Climate Zone 6–8) | Atlantic Canada (Climate Zone 5–8) | Northern Canada (Climate Zone 7B–8) | |
| A1 | 300–460 | 300–460 | 300–460 | 300–460 | 300–460 | 300–460 | 460 |
| A2 | 520–2010 | 1440–2010 | 1440–2010 | 1440–2010 | 1440–2010 | 1440–2010 | 2010 |
| A3 | 850–7000 | 920–7000 | 920–7000 | 525–7000 | 920–7000 | 525–7000 | 920–6010 |
| A4 | 830–6720 | 1060–6720 | 1060–6720 | 490–6720 | 1060–6720 | 490–6720 | 1060–6430 |
| A5 (Mid-Unit) | 280–6310 | 460–6310 | 460–6310 | 280–6310 | 460–6310 | 280–6310 | 300–5270 |
| A5 (End-Unit) | 390–5860 | 1070–5860 | 1070–5860 | 390–5860 | 1070–5860 | 390–5860 | 690–5860 |
| A6 (Lower Mid-Unit) | 800–1510 | 800–1510 | 800–1510 | 800–1510 | 800–1510 | 800–1510 | 1010–1310 |
| A6 (Upper Mid-Unit) | 830–1680 | 1210–1680 | 1210–1680 | 1210–1680 | 1210–1680 | 1210–1680 | 1210 |
| A6 (Lower End-Unit) | 890–2270 | 930–2270 | 930–2270 | 930–2270 | 930–2270 | 930–2270 | 1480–2270 |
| A6 (Upper End-Unit) | 720–1950 | 760–1950 | 760–1950 | 760–1950 | 760–1950 | 760–1950 | 1950 |
This proposed change can be enforced by the infrastructure currently available to enforce the Code.
This proposed change facilitates effective enforcement of high-performance energy solutions in jurisdictions where complying with the performance path is problematic.
Regulators, builders, designers, engineers, architects, contractors and consultants in provinces and territories where Energy Performance Tier 3 for housing and small buildings is adopted.