Code Reference(s):
NBC25 Div.B 9.36.12. (first printing)
Subject:
Energy Efficiency for Houses
Title:
Energy Performance Tier 3 of the Prescriptive Path
Description:
This proposed change provides energy-efficiency requirements for compliance with Tier 3 of the energy performance compliance prescriptive path.
This change could potentially affect the following topic areas:

Problem

The 2020 edition of the National Building Code of Canada (NBC) introduced energy efficiency performance tiers in Section 9.36. of Division B, with increasing levels of improvement for buildings and houses, to provide authorities having jurisdiction with the option to adopt the energy performance levels most suitable to their needs.

Although performance modeling is common in the industry, many Code users have requested that prescriptive compliance paths remain in the National Model Codes to provide simplicity in achieving energy compliance.

Failure to develop a prescriptive compliance path for Tier 3 could force Code users to rely on more complicated compliance paths.

Justification

The proposed prescriptive requirements for Tier 3 would provide acceptable solutions for different components of the building to improve the total energy performance. Together with the tiered energy performance path in Subsection 9.36.7. and the tiered points-based prescriptive trade-off path in Subsection 9.36.9., the prescriptive path is one of the compliance options that provide an acceptable means of achieving the performance goal of reducing energy consumption by at least 20% and percent heat loss by at least 10% for buildings with a volume of conditioned space (or “conditioned volume”) greater than 300 m3, and by reducing energy consumption by at least 10% and percent heat loss by at least 5% for buildings with a conditioned volume less than or equal to 300 m3.

In developing the Tier 3 prescriptive solutions, many different possible solutions were considered. These possible solutions were compared against the points-based trade-off path to ensure compliance.

Building Envelope

A Tier 3 envelope package was developed for each climate zone. 240 building archetypes were modeled and categorized by volume, with 219 having a conditioned volume greater than 300 m3 and 21 having a volume of less than or equal to 300 m3.

For the applicable building volume and climate zone, two criteria were used to define acceptable Tier 3 building envelope package solutions:

  1. At least 80% of the archetypes must comply with the Tier 3 requirement for percentage heat loss reduction.
  2. On average, the archetypes must have a peak heating load less than their reference building.

There are numerous combinations of envelope measures that meet the above criteria. Therefore, additional selection criteria needed to be defined to reduce the number of prescriptive envelope package solutions to one for each climate and building volume.

The two additional criteria were as follows:

  1. Solutions should minimize incremental costs.
  2. Component performance of the building envelope must consistently increase across climate zones.

A fourth criterion was defined to ensure that, when going from a warmer to colder climate zone, the thermal performance of a building envelope component was not reduced. For example, a solution that uses 4.88 RSI for the effective thermal resistance of above-grade walls in climate zone 6 would not be used if the solution for climate zone 5 used 5.69 RSI for above-grade walls.

Airtightness

There is no mandatory airtightness level that must be met to achieve Tier 3.

HVAC and Service Water Heating System 

Heat/energy recovery ventilators (HRVs/ERVs) are considered an economical way to save energy; it was proposed that all Tier 3 houses be equipped with HRVs/ERVs with a minimum 70% sensible recovery efficiency. As HRVs/ERVs are required for the Tier 1 and Tier 2 packages, the requirement is maintained in the Tier 3 package.

For buildings with a conditioned volume less than or equal to 300 m3, no upgrades beyond Code-minimum space heating systems are required to achieve Tier 3. For buildings with a conditioned volume greater than 300 m3, upgrades are required when heating with a gas- or oil-fired furnace.

For buildings with a conditioned volume less than or equal to 300 m3, no upgrades beyond Code-minimum service water heating systems are required to achieve Tier 3. For buildings with a conditioned volume greater than 300 m3, upgrades are required when the water heater is gas- or oil-fired.

PROPOSED CHANGE

[9.36.12.] 9.36.12. Tiered Energy Performance Compliance: Tier 3 Prescriptive Path

[9.36.12.1.] ---Scope and Application

[1] --)This Subsection is concerned with achieving compliance with Energy Performance Tier 3, as specified in Table 9.36.7.2., through prescriptive requirements.
[2] --)This Subsection applies only to buildings that are equipped with a heat/energy-recovery ventilator conforming to Article 9.36.3.9. (See Note A-9.36.12.2.(1)(a).)

[9.36.12.2.] ---Compliance

[1] --)Compliance with this Subsection shall be achieved by
[a] --)designing and constructing the building envelope in accordance with Articles 9.36.2.1. to 9.36.2.5., 9.36.2.9., 9.36.2.10., and 9.36.12.3. to 9.36.12.5. (see Note A-9.36.12.2.(1)(a)),
[b] --)designing and constructing or specifying systems and equipment for heating, ventilating or air-conditioning in accordance with Article 9.36.12.6., and
[c] --)designing and constructing or specifying systems and equipment for service water heating in accordance with Article 9.36.12.7.

[9.36.12.3.] ---Above-Ground Opaque Building Assemblies

[1] --)Except as provided in Article 9.36.2.5. and Sentence 9.36.2.6.(3), the effective thermal resistance of above-ground opaque building assemblies or portions thereof shall be not less than that shown for the applicable heating degree-days of the building location in
[a] --)Table 9.36.12.3.-A, where the total volume of conditioned space within the building is less than or equal to 300 m3,
[b] --)Table 9.36.12.3.-B, where the total volume of conditioned space within the building is greater than 300 m3 or not determined, and
[i] --)the principal space-heating appliance is oil- or gas-fired or a heat pump, as specified in Table 9.36.12.6., and
[ii] --)the service water heating equipment is oil- or gas-fired or a heat pump, as specified in Table 9.36.12.7., or
[c] --)Table 9.36.12.3.-C.
Table [9.36.12.3.-A]
Tier 3 Effective Thermal Resistance of Above-Ground Opaque Building Assemblies Described in Clause 9.36.12.3.(1)(a)
Forming Part of Clause 9.36.12.3.(1)(a)
Above-Ground Opaque Building Assembly Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (1) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Minimum Effective Thermal Resistance (RSI), (m2×K)/W
Ceilings below attics 6.91 8.67 8.67 10.43 10.43 10.43
Cathedral ceilings and flat roofs 4.67 4.67 4.67 5.02 5.02 5.02
Walls 3.08 3.08 3.28 3.28 3.85 3.85
Floors over unheated spaces 4.67 4.67 4.67 5.02 5.02 5.02
Table [9.36.12.3.-B]
Tier 3 Effective Thermal Resistance of Above-Ground Opaque Building Assemblies Described in Clause 9.36.12.3.(1)(b)
Forming Part of Clause 9.36.12.3.(1)(b)
Above-Ground Opaque Building Assembly Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (1) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Minimum Effective Thermal Resistance (RSI), (m2×K)/W
Ceilings below attics 6.91 8.67 10.43 10.43 10.43 10.43
Cathedral ceilings and flat roofs 4.67 4.67 5.02 5.02 5.02 5.02
Walls 3.28 3.28 3.58 3.69 4.29 4.57
Floors over unheated spaces 4.67 4.67 4.67 5.02 5.02 5.02
Table [9.36.12.3.-C]
Tier 3 Effective Thermal Resistance of Above-Ground Opaque Building Assemblies Described in Clause 9.36.12.3.(1)(c)
Forming Part of Clause 9.36.12.3.(1)(c)
Above-Ground Opaque Building Assembly Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (1) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Minimum Effective Thermal Resistance (RSI), (m2×K)/W
Ceilings below attics 6.91 10.43 12.19 12.19 12.19 12.19
Cathedral ceilings and flat roofs 4.67 4.67 5.02 5.02 5.02 5.02
Walls 4.40 4.40 4.57 4.57 5.45 5.45
Floors over unheated spaces 4.67 4.67 4.67 5.02 5.02 5.02
[2] --)Where the top of a section of foundation wall is on average greater than or equal to 600 mm above the adjoining ground level, the effective thermal resistance of the above-ground portion of that section of wall shall be not less than that of the above-ground walls.
[3] --)Except for tubular daylighting devices, the effective thermal resistance of skylight shafts shall be not less than that of the above-ground walls.

[9.36.12.4.] ---Fenestration, Doors and Skylights

[1] --)Except as provided in Sentences (2) to (8), fenestration and doors shall have an overall thermal transmittance (U-value) not greater than, or an Energy Rating not less than, that shown in Table 9.36.12.4. for the applicable heating-degree days of the building location. (See Note A-9.36.2.7.(1) and (3)PROPOSED CHANGE A-9.36.2.7.(1) and (3).)
Table [9.36.12.4.]
Tier 3 Thermal Characteristics of Fenestration and Doors
Forming Part of Sentence 9.36.12.4.(1)
Component Thermal CharacteristicsPROPOSED CHANGE Table Footnote (1) Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Windows and doors Max. U-value, W/(m2×K) 1.44 1.22 1.22 1.22 1.05 1.05
Min. Energy Rating 29 34 34 34 40 40
[2] --)The solar heat gain coefficient of fenestration and doors shall comply with Sentence 9.36.2.7.(2).
[3] --)Skylights shall have a U-value not greater than that shown in Table 9.36.2.7.-C for the applicable heating-degree days of the building location. (See Note A-9.36.2.7.(1) and (3)PROPOSED CHANGE A-9.36.2.7.(1) and (3).)
[4] --)Glass block assemblies separating conditioned space from unconditioned space or the exterior shall have
[a] --)a U-value of not more than 2.9 W/(m2×K), and
[b] --)a total aggregate area of not more than 1.85 m2.
[5] --)One door separating a conditioned space from an unconditioned space or the exterior is permitted to have a U-value up to 2.6 W/(m2×K).
[6] --)Storm windows and storm doors need not comply with Sentence (1).
[7] --)Vehicular access doors separating a conditioned space from an unconditioned space or the exterior shall have a nominal thermal resistance of not less than 1.1 (m2×K)/W.
[8] --)Access hatches separating a conditioned space from an unconditioned space shall be insulated to a nominal thermal resistance of not less than 2.6 (m2×K)/W.

[9.36.12.5.] ---Opaque Building Assemblies Below-Grade or in Contact with the Ground

[1] --)Opaque building assemblies below-grade or in contact with the ground shall be designed and constructed in accordance with Sentences 9.36.2.8.(2) to (10) and this Article.
[2] --)Except as provided in Article 9.36.2.5., the effective thermal resistance of foundation walls shall be not less than that shown for the applicable heating degree-days of the building location in
[a] --)Table 9.36.12.5.-A, where the total volume of conditioned space within the building is less than or equal to 300 m3,
[b] --)Table 9.36.12.5.-B, where the total volume of conditioned space within the building is greater than 300 m3 or not determined, and
[i] --)the principal space-heating appliance is gas- or oil-fired or a heat pump, as specified in Table 9.36.12.6., and
[ii] --)the service water heating equipment is gas- or oil-fired or a heat pump, as specified in Table 9.36.12.7., or
[c] --)Table 9.36.12.5.-C.
Table [9.36.12.5.-A]
Tier 3 Effective Thermal Resistance of Building Assemblies Below-Grade or in Contact with the Ground Described in Clause 9.36.12.5.(2)(a)
Forming Part of Clause 9.36.12.5.(2)(a)
Building Assembly Below-Grade or in Contact with the GroundPROPOSED CHANGE Table Footnote (1) Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Minimum Effective Thermal Resistance (RSI), (m2×K)/W
Foundation walls 1.99 2.98 2.98 3.46 3.46 3.97
Unheated floorsPROPOSED CHANGE Table Footnote (3)below frost linePROPOSED CHANGE Table Footnote (4)PROPOSED CHANGE Table Footnote (5) uninsulated uninsulated uninsulated uninsulated uninsulated uninsulated
Unheated floorsPROPOSED CHANGE Table Footnote (3)above frost linePROPOSED CHANGE Table Footnote (5) 1.96 1.96 1.96 1.96 1.96 1.96
Heated and unheated floors on permafrost n/a n/a n/a n/a 4.44 4.44
Heated floorsPROPOSED CHANGE Table Footnote (6) 2.32 2.32 2.32 2.84 2.84 2.84
Slabs-on-grade with an integral footingPROPOSED CHANGE Table Footnote (6) 1.96 1.96 1.96 3.72 3.72 4.59
Table [9.36.12.5.-B]
Tier 3 Effective Thermal Resistance of Building Assemblies Below-Grade or in Contact with the Ground Described in Clause 9.36.12.5.(2)(b)
Forming Part of Clause 9.36.12.5.(2)(b)
Building Assembly Below-Grade or in Contact with the GroundPROPOSED CHANGE Table Footnote (1) Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Minimum Effective Thermal Resistance (RSI), (m2×K)/W
Foundation walls 2.98 3.46 3.46 4.78 4.78 4.78
Unheated floorsPROPOSED CHANGE Table Footnote (3)below frost linePROPOSED CHANGE Table Footnote (4)PROPOSED CHANGE Table Footnote (5) uninsulated uninsulated uninsulated uninsulated uninsulated uninsulated
Unheated floorsPROPOSED CHANGE Table Footnote (3)above frost linePROPOSED CHANGE Table Footnote (5) 1.96 1.96 1.96 1.96 1.96 1.96
Heated and unheated floors on permafrost n/a n/a n/a n/a 4.44 4.44
Heated floorsPROPOSED CHANGE Table Footnote (6) 2.32 2.32 2.32 2.84 2.84 2.84
Slabs-on-grade with an integral footingPROPOSED CHANGE Table Footnote (6) 1.96 1.96 2.84 3.72 3.72 4.59
Table [9.36.12.5.-C]
Tier 3 Effective Thermal Resistance of Building Assemblies Below-Grade or in Contact with the Ground Described in Clause 9.36.12.5.(2)(c)
Forming Part of Clause 9.36.12.5.(2)(c)
Building Assembly Below-Grade or in Contact with the GroundPROPOSED CHANGE Table Footnote (1) Heating Degree-Days of Building Location,PROPOSED CHANGE Table Footnote (2) in Celsius Degree-Days
Zone 4
< 3000
Zone 5
3000 to 3999
Zone 6
4000 to 4999
Zone 7A
5000 to 5999
Zone 7B
6000 to 6999
Zone 8
≥ 7000
Minimum Effective Thermal Resistance (RSI), (m2×K)/W
Foundation walls 3.46 3.46 3.90 4.78 4.78 5.22
Unheated floorsPROPOSED CHANGE Table Footnote (3)below frost linePROPOSED CHANGE Table Footnote (4)PROPOSED CHANGE Table Footnote (5) uninsulated uninsulated uninsulated uninsulated uninsulated uninsulated
Unheated floorsPROPOSED CHANGE Table Footnote (3)above frost linePROPOSED CHANGE Table Footnote (5) 1.96 1.96 1.96 1.96 1.96 1.96
Heated and unheated floors on permafrost n/a n/a n/a n/a 4.44 4.44
Heated floorsPROPOSED CHANGE Table Footnote (6) 2.32 2.32 2.32 2.84 2.84 2.84
Slabs-on-grade with an integral footingPROPOSED CHANGE Table Footnote (6) 1.96 1.96 3.72 3.72 4.59 4.59

[9.36.12.6.] ---HVAC Systems

[1] --)HVAC systems, equipment and installations shall be designed and constructed or specified in accordance with Articles 9.36.3.2. to 9.36.3.8. and 9.36.3.11. and this Article.
[2] --)Where HVAC systems, equipment or techniques other than those described in Articles 9.36.3.2. to 9.36.3.8. and 9.36.3.11. and this Article are used, the building shall be designed and constructed in accordance with the energy efficiency requirements of the NECB.
[3] --)Ventilation systems serving buildings to which this Subsection applies shall be equipped with a heat/energy recovery ventilator conforming to Article 9.36.3.9.
[4] --)The sensible recovery efficiency (SRE) measured at an outside air test temperature of 0°C of the heat/energy recovery ventilator described in Sentence (3) shall be not less than 70%.
[5] --)Heat pumps shall have an output capacity tested at the standard test temperature of 8.3°C that is equivalent to at least 60% of the design heat loss of the building.
[6] --)HVAC equipment and components shall comply with the performance requirements stated in
[a] --)Table 9.36.12.6., where the total volume of conditioned space within the building is greater than 300 m3 or not determined, or
[b] --)Table 9.36.3.10., where the total volume of conditioned space within the building is less than or equal to 300 m3.
Table [9.36.12.6.]
Tier 3 Performance Requirements for HVAC Equipment in Buildings Where Total Volume of Conditioned Space > 300 m3 or Not Determined
Forming Part of Clause 9.36.12.6.(6)(a)
Principal Heating SystemPROPOSED CHANGE Table Footnote (1) Performance RequirementPROPOSED CHANGE Table Footnote (2)
Gas-fired combined space- and service water heating systems (combos)PROPOSED CHANGE Table Footnote (3) TPF ≥ 0.85
Gas-fired warm-air furnacesPROPOSED CHANGE Table Footnote (3) AFUE ≥ 98%
Oil-fired appliances AFUE ≥ 87%
Heat pumps See Table 9.36.3.10.
Other space-heating appliances See Table 9.36.3.10.
[7] --)Natural gas and propane fireplaces shall comply with Sentence 9.36.3.10.(2).

[9.36.12.7.] ---Service Water Heating Equipment

[1] --)Service water heating equipment and components shall be designed and constructed or specified in accordance with Subsection 9.36.4. and this Article.
[2] --)Where service water heating equipment or techniques other than those described in Subsection 9.36.4. and this Article are used, the building shall be designed and constructed in accordance with the energy efficiency requirements of the NECB.
[3] --)Service water heating equipment and components shall comply with the performance requirements stated in
[a] --)Table 9.36.12.7., where the total volume of conditioned space within the building is greater than 300 m3 or not determined, or
[b] --)Table 9.36.4.2., where the total volume of conditioned space within the building is less than or equal to 300 m3.
Table [9.36.12.7.]
Tier 3 Performance Requirements for Service Water Heating Equipment in Buildings Where Total Volume of Conditioned Space > 300 m3 or Not Determined
Forming Part of Subclause 9.36.12.3.(1)(a)(ii) and Clause 9.36.12.7.(3)(a)
Type of EquipmentPROPOSED CHANGE Table Footnote (1) Performance RequirementPROPOSED CHANGE Table Footnote (2)
Storage type service water heaters
UEF ≥ 0.83 or EF ≥ 0.8
Oil-fired
UEF ≥ 0.83 or EF ≥ 0.8
Gas-fired combined space- and service water heating systems (combos)PROPOSED CHANGE Table Footnote (3) TPF ≥ 0.85
Other service water heating equipment See Table 9.36.4.2.

Note A-9.36.12.2.(1)(a) Other Compliance Options.

Buildings that do not comply with requirements of the Tier 3 prescriptive path set out in Subsection 9.36.12. are permitted to meet the requirements of the performance paths (Subsection 9.36.7. or 9.36.8.) or the points-based prescriptive trade-off path (Subsection 9.36.9.) to achieve the Tier 3 energy performance target provided in Table 9.36.7.2.

Impact analysis

This proposed change would improve energy performance by providing the prescriptive requirements for building envelopes, service water heating systems and HVAC systems to achieve Energy Performance Tier 3.

Buildings with a total volume of conditioned space of less than or equal to 300 m³ have the following energy performance targets: a percent improvement of ≥10%, a percent energy target of ≤90% and a percent heat loss reduction of ≥5%.

Buildings with a total volume of conditioned space of greater than 300 m³ have the following energy performance targets: a percent improvement of ≥20%, a percent energy target of ≤80% and a percent heat loss reduction of ≥10%.

The incremental costing below is derived from the specifications and detailed costing data found in the supporting document. Total costs by archetype have been rounded to the nearest $10.

 

 

Archetype A1 — Apartment/condominium unit, one bedroom

 

Table 1. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A1

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 13.93
Floor area 46.30
Insulated attic area 46.30
Window area 2.36
Conditioned Space Total Volume, m3
Conditioned space 105.45

Tier 1 and Tier 2 are identical for Archetype A1, as its conditioned volume is ≤ 300m3.

 

Table 2. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A1

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Above-grade walls –51.35* –51.35* –34.44* –34.44* 136.14 136.14
Windows and sliding glass doors 172.76 243.79 243.79 138.86 125.95 125.95
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
HVAC 0.00 0.00 0.00 0.00 0.00 0.00
SWH 0.00 0.00 0.00 0.00 0.00 0.00
Total 320 390 410 300 460 460

*See supplemental document Section 3.4.

 

Archetype A2 — Bungalow, detached without basement or garage

 

Table 3. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A2

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 126.05
Ground floor area 95.00
Slab in contact with the ground 101.7
Insulated attic area 95.00
Window area 10.75
Conditioned Space Total Volume, m3
Conditioned space 217.44

Tier 1 and Tier 2 are identical for Archetype A2, as its conditioned volume is ≤ 300m3.

 

Table 4. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A2

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 754.30 754.18 922.45 0.00 0.00
Above-grade walls –464.66* –464.66* –311.61* –311.61* 1,231.92 1,231.92
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Windows and sliding glass doors 786.95 1,110.48 1,110.48 632.53 573.73 573.73
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
HVAC 0.00 0.00 0.00 0.00 0.00 0.00
SWH 0.00 0.00 0.00 0.00 0.00 0.00
Total 520 1,600 1,750 1,440 2,010 2,010

*See supplemental document Section 3.4.


Archetype A3 — Bungalow, detached with basement and garage

 

Table 5. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A3

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 69.49
Foundation walls 46.10
Ground floor area 90.45
Insulated attic area 90.45
Window area 19.74
Conditioned Space Total Volume, m3
Conditioned space 411.36

 

Table 6. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A3 – Gas-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 718.06 1,596.34 878.28 0.00 0.00
Above-grade walls –171.79* –171.79* 5.59 422.98 1,069.67 1,335.99
Foundation walls 1,318.41 239.78 1,558.19 2,005.82 2,005.82 2,005.82
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 1,445.05 2,039.16 2,039.16 1,161.51 1,053.43 1,053.43
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Gas-fired furnace 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00
Gas-fired storage-type water heater 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00
Total 7,410 7,850 10,220 9,490 9,150 9,420

*See supplemental document Section 3.4.

 

Table 7. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A3 – Gas-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,596.44 0.00 0.00 0.00
Above-grade walls 84.37 84.37 340.71 679.14 390.53 656.85
Foundation walls 0.00 239.72 239.78 527.81 527.81 527.81
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 567.40 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Gas-fired furnace 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00
Gas-fired storage-type water heater 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00
Total 5,470 5,350 7,000 6,030 5,740 6,010

 

Table 8. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A3 – Oil-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 718.06 1,596.34 878.28 0.00 0.00
Above-grade walls –171.79* –171.79* 5.59 422.98 1,069.67 1,335.99
Foundation walls 1,318.41 239.78 1,558.19 2,005.82 2,005.82 2,005.82
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 1,445.05 2,039.16 2,039.16 1,161.51 1,053.43 1,053.43
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Oil-fired furnace 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00
Oil-fired storage-type water heater 371.00 371.00 371.00 371.00 371.00 371.00
Total 4,670 4,910 7,280 6,550 6,210 6,480

*See supplemental document Section 3.4.

 

Table 9. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A3 – Oil-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,596.44 0.00 0.00 0.00
Above-grade walls 84.37 84.37 340.71 679.14 390.53 656.85
Foundation walls 0.00 239.72 239.78 527.81 527.81 527.81
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 567.40 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Oil-fired furnace 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00
Oil-fired storage-type water heater 371.00 371.00 371.00 371.00 371.00 371.00
Total 2,730 2,400 4,060 3,090 2,800 3,070

 

Table 10. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A3 – Heat Pump

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 718.06 1,596.34 878.28 0.00 0.00
Above-grade walls –171.79* –171.79* 5.59 422.98 1,069.67 1,335.99
Foundation walls 1,318.41 239.78 1,558.19 2,005.82 2,005.82 2,005.82
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 1,445.05 2,039.16 2,039.16 1,161.51 1,053.43 1,053.43
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Heat pump 0.00 0.00 0.00 0.00 0.00 0.00
Code minimum storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 2,790 3,020 5,400 4,670 4,330 4,600

*See supplemental document Section 3.4.

 

Table 11. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A3 – Heat Pump

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,596.44 0.00 0.00 0.00
Above-grade walls 84.37 84.37 340.71 679.14 390.53 656.85
Foundation walls 0.00 239.72 239.78 527.81 527.81 527.81
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 567.40 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Heat pump 0.00 0.00 0.00 0.00 0.00 0.00
Code minimum storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 2,790 3,020 5,200 4,470 4,130 4,400

 

Table 12. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A3 – Electric Resistance

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 1,596.34 2,394.51 1,676.45 798.17 798.17
Above-grade walls 1,079.83 1,079.83 1,079.83 1,079.83 2,937.28 2,937.28
Foundation walls 2,867.95 239.72 2,796.43 2,005.82 2,005.82 2,277.52
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 1,445.05 2,039.14 2,039.16 1,161.50 1,053.52 1,053.52
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Electric resistance furnace 0.00 0.00 0.00 0.00 0.00 0.00
Electric resistance storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 5,590 5,150 8,510 6,120 6,990 7,270

 

Table 13. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A3 – Electric Resistance

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 730.85 2,394.21 798.17 797.77 797.77
Above-grade walls 1,335.99 1,335.99 1,335.99 1,335.99 2,258.14 2,258.14
Foundation walls 239.78 239.72 1,478.01 527.81 527.81 799.51
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a $0.00 0.00
Windows and sliding glass doors 567.40 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Electric resistance furnace 0.00 0.00 0.00 0.00 0.00 0.00
Electric resistance storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 2,340 2,510 5,210 2,660 3,580 3,850

Archetype A4 — 2-storey, detached

 

Table 14. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A4

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 142.78
Foundation walls 22.69
Ground floor area 57.25
Insulated attic area 70.56
Window area 15.74
Conditioned Space Total Volume, m3
Conditioned space 427.46

 

Table 15. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A4 – Gas-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 560.16 1,245.31 685.15 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –352.97* –352.97* 11.50 869.09 2,197.84 2,745.05
Foundation walls 648.91 118.02 766.93 987.25 987.25 987.25
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 1,152.23 1,625.95 1,625.95 926.15 839.97 839.97
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Gas-fired furnace 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00
Gas-fired storage-type water heater 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00
Total 6,470 6,970 8,670 8,490 9,050 9,590

*See supplemental document Section 3.4.

 

Table 16. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A4 – Gas-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,245.38 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 173.36 173.36 537.83 1,395.42 802.42 1,349.62
Foundation walls 0.00 117.99 118.02 259.78 259.78 259.78
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 452.43 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Gas-fired furnace 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00
Gas-fired storage-type water heater 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00
Total 5,650 5,310 6,720 6,480 5,880 6,430

 

Table 17. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A4 – Oil-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 560.16 1,245.31 685.15 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –352.97* –352.97* 11.50 869.09 2,197.84 2,745.05
Foundation walls 648.91 118.02 766.93 987.25 987.25 987.25
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 1,152.23 1,625.95 1,625.95 926.15 839.97 839.97
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Oil-fired furnace 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00
Oil-fired storage-type water heater 371.00 371.00 371.00 371.00 371.00 371.00
Total 3,530 4,030 5,730 5,550 6,110 6,650

*See supplemental document Section 3.4.

 

Table 18. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A4 – Oil-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,245.38 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 173.36 173.36 537.83 1,395.42 802.42 1,349.62
Foundation walls 0.00 117.99 118.02 259.78 259.78 259.78
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 452.43 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Oil-fired furnace 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00
Oil-fired storage-type water heater 371.00 371.00 371.00 371.00 371.00 371.00
Total 2,710 2,370 3,780 3,540 2,940 3,490

 

Table 19. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A4 – Heat Pump

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 560.16 1,245.31 685.15 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –352.97* –352.97* 11.50 869.09 2,197.84 2,745.05
Foundation walls 648.91 118.02 766.93 987.25 987.25 987.25
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 1,152.23 1,625.95 1,625.95 926.15 839.97 839.97
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Heat pump 0.00 0.00 0.00 0.00 0.00 0.00
Code minimum storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 1,650 2,150 3,850 3,670 4,220 4,770

*See supplemental document Section 3.4.

 

Table 20. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A4 – Heat Pump

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,245.38 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 173.36 173.36 537.83 1,395.42 802.42 1,349.62
Foundation walls 0.00 117.99 118.02 259.78 259.78 259.78
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 452.43 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Heat pump 0.00 0.00 0.00 0.00 0.00 0.00
Code minimum storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 830 490 1,900 1,650 1,060 1,610

 

Table 21. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A4 – Electric Resistance

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 1,245.31 1,867.96 1,307.80 622.65 622.65
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 2,218.71 2,218.71 2,218.71 2,218.71 6,035.18 6,035.18
Foundation walls 766.93 117.99 1,376.37 987.25 987.25 1,120.98
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 1,152.23 1,625.94 1,625.95 926.14 840.04 840.04
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Electric resistance furnace 0.00 0.00 0.00 0.00 0.00 0.00
Electric resistance storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 4,340 5,410 7,290 5,640 8,690 8,820

 

Table 22. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A4 – Electric Resistance

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 570.14 1,867.72 622.65 622.34 622.34
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 2,745.05 2,745.05 2,745.05 2,745.05 4,639.76 4,639.76
Foundation walls 118.02 117.99 727.47 259.78 259.78 393.51
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and glass doors 452.43 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Electric resistance furnace 0.00 0.00 0.00 0.00 0.00 0.00
Electric resistance storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 3,510 3,630 5,340 3,630 5,520 5,660
 
 Archetype A5 — Row house, 2-storey

 

Table 23. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A5 (Mid-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 38.44
Foundation walls 7.14
Ground floor area 54.50
Insulated attic area 74.05
Window area 12.12
Conditioned Space Total Volume, m3
Conditioned space 425.35

 

Table 24. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (Mid-Unit) – Gas-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 587.87 1,306.90 719.03 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –95.03* –95.03* 3.09 233.98 591.71 739.04
Foundation walls 204.20 37.14 241.33 310.66 310.66 310.66
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 887.24 1,252.00 1,252.00 713.14 646.79 646.79
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Gas-fired furnace 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00
Gas-fired storage-type water heater 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00
Total 6,020 6,810 7,830 7,000 6,570 6,730

*See supplemental document Section 3.4.

 

Table 25. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (Mid-Unit) – Gas-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,306.98 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 46.67 46.67 144.80 375.68 216.03 363.35
Foundation walls 0.00 37.13 37.14 81.75 81.75 81.75
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 348.38 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Gas-fired furnace 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00
Gas-fired storage-type water heater 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00
Total 5,420 5,110 6,310 5,280 5,120 5,270

 

Table 26. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (Mid-Unit) – Oil-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 587.87 1,306.90 719.03 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –95.03* –95.03* 3.09 233.98 591.71 739.04
Foundation walls 204.20 37.14 241.33 310.66 310.66 310.66
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 887.24 1,252.00 1,252.00 713.14 646.79 646.79
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Oil-fired furnace 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00
Oil-fired storage-type water heater 371.00 371.00 371.00 371.00 371.00 371.00
Total 3,080 3,870 4,890 4,060 3,630 3,780

*See supplemental document Section 3.4.

 

Table 27. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (Mid-Unit) – Oil-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,306.98 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 46.67 46.67 144.80 375.68 216.03 363.35
Foundation walls 0.00 37.13 37.14 81.75 81.75 81.75
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 348.38 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Oil-fired furnace 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00
Oil-fired storage-type water heater 371.00 371.00 371.00 371.00 371.00 371.00
Total 2,480 2,160 3,370 2,340 2,180 2,330

 

Table 28. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (Mid-Unit) – Heat Pump

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 587.87 1,306.90 719.03 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –95.03* –95.03* 3.09 233.98 591.71 739.04
Foundation walls 204.20 37.14 241.33 310.66 310.66 310.66
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 887.24 1,252.00 1,252.00 713.14 646.79 646.79
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Heat pump 0.00 0.00 0.00 0.00 0.00 0.00
Code minimum storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 1,200 1,990 3,010 2,180 1,750 1,900

*See supplemental document Section 3.4.

 

Table 29. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (Mid-Unit) – Heat Pump

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,306.98 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 46.67 46.67 144.80 375.68 216.03 363.35
Foundation walls 0.00 37.13 37.14 81.75 81.75 81.75
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 348.38 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Heat pump 0.00 0.00 0.00 0.00 0.00 0.00
Code minimum storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 590 280 1,490 460 300 440

 

Table 30. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (Mid-Unit) – Electric Resistance

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 1,306.90 1,960.35 1,372.48 653.45 653.45
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 597.33 597.33 597.33 597.33 1,624.82 1,624.82
Foundation walls 241.33 37.13 433.11 310.66 310.66 352.74
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 887.24 1,252.00 1,252.00 713.14 646.84 646.84
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Electric resistance furnace 0.00 0.00 0.00 0.00 0.00 0.00
Electric resistance storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 1,920 3,390 4,440 3,190 3,430 3,470

 

Table 31. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (Mid-Unit) – Electric Resistance

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 598.34 1,960.10 653.45 653.12 653.12
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 739.04 739.04 739.04 739.04 1,249.14 1,249.14
Foundation walls 37.14 37.13 228.92 81.75 81.75 123.83
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 348.38 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Electric resistance furnace 0.00 0.00 0.00 0.00 0.00 0.00
Electric resistance storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 1,320 1,570 2,930 1,470 1,980 2,030

 

Table 32. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A5 (End-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 90.34
Foundation walls 16.14
Ground floor area 54.50
Insulated attic area 74.05
Window area 13.59
Conditioned Space Total Volume, m3
Conditioned space 425.35

 

Table 33. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (End-Unit) – Gas-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 587.96 1,306.98 719.03 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –223.14* –223.14* 7.23 550.17 1,390.33 1,737.24
Foundation walls 461.60 83.93 545.53 702.25 702.25 702.25
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 994.79 1,403.85 1,403.85 799.64 725.30 725.30
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Gas-fired furnace 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00
Gas-fired storage-type water heater 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00
Total 6,260 6,880 8,290 7,790 7,840 8,190

*See supplemental document Section 3.4.

 

Table 34. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (End-Unit) – Gas-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,306.98 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 109.31 109.31 340.58 882.62 507.71 853.71
Foundation walls 0.00 83.93 85.54 184.80 184.80 184.80
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 390.58 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Gas-fired furnace 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00 2,300.00
Gas-fired storage-type water heater 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00 2,523.00
Total 5,520 5,220 6,560 5,890 5,510 5,860

 

Table 35. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (End-Unit) – Oil-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 587.96 1,306.98 719.03 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –223.14* –223.14* 7.23 550.17 1,390.33 1,737.24
Foundation walls 461.60 83.93 545.53 702.25 702.25 702.25
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 994.79 1,403.85 1,403.85 799.64 725.30 725.30
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Oil-fired furnace 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00
Oil-fired storage-type water heater 371.00 371.00 371.00 371.00 371.00 371.00
Total 3,310 3,930 5,340 4,850 4,900 5,250

*See supplemental document Section 3.4.

 

Table 36. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (End-Unit) – Oil-Fired

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,306.98 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 109.31 109.31 340.58 882.62 507.71 853.71
Foundation walls 0.00 83.93 85.54 184.80 184.80 184.80
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 390.58 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Oil-fired furnace 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00 1,510.00
Oil-fired storage-type water heater 371.00 371.00 371.00 371.00 371.00 371.00
Total 2,580 2,270 3,610 2,950 2,570 2,920

 

Table 37. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (End-Unit) – Heat Pump

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 587.96 1,306.98 719.03 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls –223.14* –223.14* 7.23 550.17 1,390.33 1,737.24
Foundation walls 461.60 83.93 545.53 702.25 702.25 702.25
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 994.79 1,403.85 1,403.85 799.64 725.30 725.30
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Heat pump 0.00 0.00 0.00 0.00 0.00 0.00
Code minimum storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 1,430 2,050 3,460 2,970 3,020 3,360

*See supplemental document Section 3.4.

 

Table 38. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (End-Unit) – Heat Pump

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 0.00 1,306.98 0.00 0.00 0.00
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 109.31 109.31 340.58 882.62 507.71 853.71
Foundation walls 0.00 83.93 85.54 184.80 184.80 184.80
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 390.58 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Heat pump 0.00 0.00 0.00 0.00 0.00 0.00
Code minimum storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 700 390 1,730 1,070 690 1,040

 

Table 39. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A5 (End-Unit) – Electric Resistance

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 1,306.98 1,960.10 1,372.15 653.12 653.12
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 $0.00
Above-grade walls 1,403.88 1,403.88 1,403.88 1,403.88 3,818.67 3,818.67
Foundation walls 545.53 83.93 979.05 702.25 702.25 797.32
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 994.79 1,403.85 1,403.85 799.64 725.30 725.30
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
Electric resistance furnace 0.00 0.00 0.00 0.00 0.00 0.00
Electric resistance storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 3,140 4,400 5,950 4,480 6,100 6,190

 

Table 40. Incremental Cost to Achieve Tier 3 Compared to Tier 2 in Archetype A5 (End-Unit) – Electric Resistance

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 598.32 1,960.10 653.12 653.12 653.12
Floors over unheated spaces 0.00 0.00 0.00 0.00 0.00 0.00
Above-grade walls 1,737.24 1,737.24 1,737.24 1,737.24 2,936.05 2,936.05
Foundation walls 83.93 83.93 517.45 184.80 184.80 279.87
Unheated floors below frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 390.58 0.00 0.00 0.00 0.00 0.00
HRV/ERV 200.00 200.00 0.00 0.00 0.00 0.00
Electric resistance furnace 0.00 0.00 0.00 0.00 0.00 0.00
Electric resistance storage-type water heater 0.00 0.00 0.00 0.00 0.00 0.00
Total 2,410 2,620 4,210 2,570 3,770 3,870

 

Archetype A6 — Row house, stacked 3-storey

 

Table 41. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Lower Mid-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 21.38
Foundation walls 11.28
Ground floor area 58.07
Window area 10.12
Conditioned Space Total Volume, m3
Conditioned space 279.54

Tier 1 and Tier 2 are identical for archetype A6 as its conditioned volume is ≤ 300m3.

 

Table 42. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A6 (Lower Mid-Unit)

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Above-grade walls –78.81* –78.81* –52.85* –52.85* 208.95 208.95
Foundation walls 0.00 0.00 322.60 58.67 58.67 361.65
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 740.83 1,045.40 1,045.40 595.46 540.10 540.10
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
HVAC 0.00 0.00 0.00 0.00 0.00 0.00
Service water heating equipment 0.00 0.00 0.00 0.00 0.00 0.00
Total 860 1,170 1,510 800 1,010 1,310

*See supplemental document Section 3.4.

 

Table 43. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Upper Mid-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 44.13
Ground floor area 58.07
Insulated attic area 59.85
Window area 10.80
Conditioned Space Total Volume, m3
Conditioned space 284.13

Tier 1 and Tier 2 are identical for archetype A6 as its conditioned volume is ≤ 300m3.

 

Table 44. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A6 (Upper Mid-Unit)

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 475.21 475.14 581.14 0.00 0.00
Above-grade walls –162.68* –162.68* –109.10* –109.10* 431.29 431.29
Windows and sliding glass doors 790.61 1,115.65 1,115.64 635.47 576.40 576.40
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
HVAC 0.00 0.00 0.00 0.00 0.00 0.00
Service water heating equipment 0.00 0.00 0.00 0.00 0.00 0.00
Total 830 1,630 1,680 1,310 1,210 1,210

*See supplemental document Section 3.4.

 

Table 45. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Lower End-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 50.32
Foundation walls 29.43
Ground floor area 58.07
Window area 11.91
Conditioned Space Total Volume, m3
Conditioned space 279.54

Tier 1 and Tier 2 are identical for archetype A6 as its conditioned volume is ≤ 300m3.

 

Table 46. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A6 (Lower End-Unit)

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Above-grade walls –185.50* –185.50* –124.40* –124.40* 491.79 491.79
Foundation walls 0.00 0.00 841.67 153.07 153.07 943.56
Unheated floors above frost line 0.00 0.00 0.00 0.00 n/a n/a
Heated and unheated floors on permafrost n/a n/a n/a n/a 0.00 0.00
Windows and sliding glass doors 871.86 1,230.31 1,230.30 700.78 635.64 635.64
HRV/ERV 200.00 200.00 200.00 200.00 200.00 $200.00
HVAC 0.00 0.00 0.00 0.00 0.00 0.00
Service water heating equipment 0.00 0.00 0.00 0.00 0.00 0.00
Total 890 1,240 2,150 930 1,480 2,270

*See supplemental document Section 3.4.

 

Table 47. Total Area of Building Envelope Components and Total Volume of Conditioned Space of Archetype A6 (Upper End-Unit)

Area Part of or Surrounded by Building Envelope Total Area, m2
Above-grade walls 110.07
Ground floor area 58.07
Insulated attic area 59.85
Window area 12.59
Conditioned Space Total Volume, m3
Conditioned space 284.13

Tier 1 and Tier 2 are identical for archetype A6 as its conditioned volume is ≤ 300m3.

 

Table 48. Incremental Cost to Achieve Tier 3 Compared to Tier 1 in Archetype A6 (Upper End-Unit)

Building Component Incremental Cost, $
Climate Zone
4 5 6 7A 7B 8
Ceiling below attic 0.00 475.21 475.14 581.14 0.00 0.00
Above-grade walls –405.75* –405.75* –272.11* –272.11* 1,075.74 1,075.74
Windows and sliding glass doors 921.64 1,300.56 360.06 740.80 671.93 671.93
HRV/ERV 200.00 200.00 200.00 200.00 200.00 200.00
HVAC 0.00 0.00 0.00 0.00 0.00 0.00
Service water heating equipment 0.00 0.00 0.00 0.00 0.00 0.00
Total 720 1,570 760 1,250 1,950 1,950

*See supplemental document Section 3.4.

 

 

 

Table 49. Climate Zones by Region

Degree-Days Below 18°C BC Alberta Saskatchewan and Manitoba Ontario Quebec Atlantic Canada Northern Canada
Zone 4: HDD < 3000 Yes No No No No No No
Zone 5: HDD 3000 to 3999 Yes No No Yes No Yes No
Zone 6: HDD 4000 to 4999 Yes Yes Yes Yes Yes Yes No
Zone 7A: HDD 5000 to 5999 Yes Yes Yes Yes Yes Yes No
Zone 7B: HDD 6000 to 6999 Yes Yes Yes Yes Yes Yes Yes
Zone 8: HDD ≥ 7000 Yes Yes Yes Yes Yes Yes Yes

 

Table 50. Incremental Cost to Achieve Tier 3 Compared to Tier 2 for Each Archetype by Region

Archetype Incremental Cost, $  
BC (Climate Zone 4⁠–⁠8) AB (Climate Zone 6⁠–⁠8) SK and MB (Climate Zone 6⁠–⁠8) ON (Climate Zone 5⁠–⁠8) QC (Climate Zone 6⁠–⁠8) Atlantic Canada (Climate Zone 5⁠–⁠8) Northern Canada (Climate Zone 7B⁠–⁠8)
A1 300–⁠460 300–⁠460 300–⁠460 300–⁠460 300–⁠460 300–⁠460 460
A2 520–⁠2010 1440–⁠2010 1440–⁠2010 1440–⁠2010 1440–⁠2010 1440–⁠2010 2010
A3 850–⁠7000 920–⁠7000 920–⁠7000 525–⁠7000 920–⁠7000 525–⁠7000 920–⁠6010
A4 830–⁠6720 1060–⁠6720 1060–⁠6720 490–⁠6720 1060–⁠6720 490–⁠6720 1060–⁠6430
A5 (Mid-Unit) 280–⁠6310 460–⁠6310 460–⁠6310 280–⁠6310 460–⁠6310 280–⁠6310 300–⁠5270
A5 (End-Unit) 390–⁠5860 1070–⁠5860 1070–⁠5860 390–⁠5860 1070–⁠5860 390–⁠5860 690–⁠5860
A6 (Lower Mid⁠-⁠Unit) 800–⁠1510 800–⁠1510 800–⁠1510 800–⁠1510 800–⁠1510 800–⁠1510 1010–⁠1310
A6 (Upper Mid⁠-⁠Unit) 830–⁠1680 1210–⁠1680 1210–⁠1680 1210–⁠1680 1210–⁠1680 1210–⁠1680 1210
A6 (Lower End⁠-⁠Unit) 890–⁠2270 930–⁠2270 930–⁠2270 930–⁠2270 930–⁠2270 930–⁠2270 1480–⁠2270
A6 (Upper End⁠-⁠Unit) 720–⁠1950 760–⁠1950 760–⁠1950 760–⁠1950 760–⁠1950 760–⁠1950 1950

 

Enforcement implications

This proposed change can be enforced by the infrastructure currently available to enforce the Code. 

This proposed change facilitates effective enforcement of high-performance energy solutions in jurisdictions where complying with the performance path is problematic.

Who is affected

Regulators, builders, designers, engineers, architects, contractors and consultants in provinces and territories where Energy Performance Tier 3 for housing and small buildings is adopted.

Supporting Document(s)

OBJECTIVE-BASED ANALYSIS OF NEW OR CHANGED PROVISIONS

[9.36.12.1.] -- ([1] --) no attributions
[9.36.12.1.] -- ([2] --) no attributions
[9.36.12.1.] -- ([2] --) [F95,F100-OE1.1]
[9.36.12.2.] -- ([1] --) no attributions
[9.36.12.3.] -- ([1] --) no attributions
[9.36.12.3.] -- ([1] --) [F92-OE1.1]
[9.36.12.3.] -- ([2] --) [F92-OE1.1]
[9.36.12.3.] -- ([3] --) [F92-OE1.1]
[9.36.12.4.] -- ([1] --) [F92-OE1.1]
[9.36.12.4.] -- ([2] --) [F92-OE1.1]
[9.36.12.4.] -- ([3] --) [F92-OE1.1]
[9.36.12.4.] -- ([4] --) [F92-OE1.1]
[9.36.12.4.] -- ([5] --) [F92-OE1.1]
[9.36.12.4.] -- ([6] --) no attributions
[9.36.12.4.] -- ([7] --) [F92-OE1.1]
[9.36.12.4.] -- ([8] --) [F92-OE1.1]
[9.36.12.5.] -- ([1] --) no attributions
[9.36.12.5.] -- ([1] --) no attributions
[9.36.12.5.] -- ([2] --) [F92-OE1.1]
[9.36.12.6.] -- ([1] --)
[9.36.12.6.] -- ([2] --)
[9.36.12.6.] -- ([3] --) [F95,F100-OE1.1]
[9.36.12.6.] -- ([4] --) [F95,F98,F100-OE1.1]
[9.36.12.6.] -- ([5] --) [F95,F98,F100-OE1.1]
[9.36.12.6.] -- ([6] --) [F95,F98,F99-OE1.1]
[9.36.12.6.] -- ([7] --) no attributions
[9.36.12.7.] -- ([1] --) no attributions
[9.36.12.7.] -- ([2] --) no attributions
[9.36.12.7.] -- ([3] --) no attributions