The 2020 edition of the National Building Code of Canada (NBC) introduced five energy performance tiers with increasing levels of improvement for buildings and houses, providing jurisdictions with the option to regulate the energy performance level that is most suitable for their needs.
The 2020 edition also introduced a prescriptive trade-off path in Subsection 9.36.8. as a new compliance option for Code users. Although performance modeling is commonly used in the industry, further development of the prescriptive trade-off compliance path for all energy performance tiers would make it simpler to achieve energy-efficiency compliance. However, there are no minimum sums of energy conservation points provided beyond Tier 2 of the prescriptive trade-off compliance path.
Failure to develop minimum sums of energy conservation points for Tiers 3, 4 and 5 of the prescriptive trade-off compliance path restricts Code users from demonstrating compliance with energy performance tiers above Tier 2 of the prescriptive trade-off compliance path, forcing Code users to use the performance-based compliance path that requires energy modeling to meet the energy-efficiency targets.
For the 2025 Code cycle, the provinces and territories have identified as a priority the improvement of energy provisions leading to the adoption of net-zero energy ready model codes by 2030. To achieve higher levels of energy performance by 2030, it is imperative to comprehensively develop the prescriptive trade-off compliance path to provide Code users with additional options for compliance.
The prescriptive trade-off path provides acceptable solutions using different energy conservation measures to improve total energy performance. Together with the tiered energy performance path in Subsection 9.36.7. of Division B of the NBC and the prescriptive path, the prescriptive trade-off path is one of the three compliance options that provide an acceptable means of achieving the performance goal of reducing energy consumption. Currently, Subsection 9.36.8. only provides a compliance option for the trade-off path up to Tier 2, which deprives Code users following this path of the ability to demonstrate compliance with Tiers 3, 4 and 5.
Updates to the energy conservation points for the existing as well as several new energy conservation measures are proposed for inclusion in the 2025 edition of the NBC. New measures are proposed for components and equipment such as drain-water heat recovery, heat-recovery ventilators, energy-recovery ventilators, oil-fired furnaces, gas-fired furnaces, air-source heat pumps, ceilings and slabs-on-grade. Stating the minimum sum of energy conservation points in Table 9.36.8.2.-2025 based on new and updated measures that are required for compliance with Energy Performance Tiers 3, 4 and 5 would complete the development of the prescriptive trade-off compliance path in Subsection 9.36.8.
This proposed change specifies minimum airtightness levels for Energy Performance Tiers 3, 4 and 5. This proposed change also introduces a threshold for the minimum sum of energy conservation points that must be contributed from building envelope measures. This threshold has been set considering that the majority of building archetypes can obtain the threshold building envelope points to achieve the energy performance of the corresponding tiers. This threshold also ensures a balance between the contributed points from building envelope measures and from other measures to the minimum sum of energy conservation points for the building design.
Minimum Sum | Energy Performance Tiers | ||||
Tier 1 | Tier 2 | Tier 3 | Tier 4 | Tier 5 | |
Energy conservation points | PROPOSED CHANGE Table Footnote (1) | 10 | 20 | 40 | 75PROPOSED CHANGE Table Footnote (2) |
Energy conservation points from building envelope measures PROPOSED CHANGE Table Footnote (3) | – | – | 5 | 10 | 15 |
This proposed change comprehensively develops the prescriptive trade-off compliance path to provide Code users with an acceptable solution that uses different energy conservation measures to improve the total energy performance.
Detailed modeling data can be found in the supporting document.
Methodology
The impact analysis aims to determine all permutations of the energy conservation measure (ECM) combinations for the given building archetypes.
Constraints on the analysis:
Sources
Building Archetypes
Table 1 shows the packages from four building archetypes that were considered in the impact analysis.
Archetype | ERS-5213 | ERS-7972 | ERS-4943 | ERS-1605 |
---|---|---|---|---|
Type | Detached | Row house end unit | Detached | Double/semi-detached |
Volume, m3 | 664 | 451 | 112 | 193 |
Storeys | 2 | 2 | 1.5 | 1 |
Floor area, ft2 | 2 400 | 2 370 | 470 | 580 |
Foundation | Full basement | Full basement | Slab-on-grade | Slab-on-grade |
Incremental Costs
Tables 2 to 4 show the incremental costs for single detached archetype (> 300 m3) packages for various tiers in different climate zones.
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% SRE | NA | NG instantaneous | 2.97 | 40% | 3.46 | NA | 2.0 | 20.5 | 5.2 | $3,700 |
Lowest cost – no airtightness | 60% SRE | NA | NG instantaneous | 2.97 | 40% | 3.46 | NA | NA | 20.5 | 5.2 | $3,700 | |
5 | Lowest cost | 80% SRE | NA | NG instantaneous | NA | 60% | 3.09 | NA | 1.5 | 20.0 | 6.5 | $4,560 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | 50% | 3.09 | 0.94 | NA | 20.1 | 13.6 | $4,760 | |
6 | Lowest cost | 70% SRE | NA | NA | NA | 60% | NA | 1.05 | 2.0 | 20.0 | 12.3 | $4,450 |
Lowest cost – no airtightness | 70% SRE | NA | NA | NA | 60% | NA | 0.82 | NA | 20.1 | 12.4 | $4,540 | |
7A | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 1.05 | 1.5 | 20.2 | 16.5 | $4,410 |
Lowest cost – no airtightness | 70% SRE | NA | NA | NA | 60% | NA | 0.82 | NA | 20.3 | 12.6 | $4,540 | |
7B | Lowest cost | 60% SRE | NA | NA | NA | 60% | NA | NA | 1.0 | 20.2 | 12.9 | $3,800 |
Lowest cost – no airtightness | 80% SRE | NA | NA | 3.96 | 60% | 3.90 | 0.82 | NA | 20.0 | 11.6 | $4,650 | |
8 | Lowest cost | 60% SRE | NA | NA | NA | 40% | NA | NA | 1.0 | 20.4 | 14.7 | $3,600 |
Lowest cost – no airtightness | 60% SRE | NA | NG instantaneous | 3.96 | 60% | NA | 0.82 | NA | 20.0 | 10.4 | $5,320 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 70% | NA | NG instantaneous | 2.97 | 60% | 2.98 | 0.82 | 1.5 | 40 | 22.8 | $10,210 |
5 | Lowest cost | 70% | NA | NG instantaneous | 3.69 | 50% | 3.09 | 0.94 | 1 | 40 | 27.5 | $11,240 |
6 | Lowest cost | 70% | NA | NG instantaneous | 3.69 | 60% | 3.09 | 0.82 | 1 | 40 | 27.4 | $10,910 |
7A | Lowest cost | 70% | NA | NG instantaneous | 3.85 | 60% | NA | 0.82 | 1 | 40 | 29.2 | $11,310 |
7B | Lowest cost | 70% | NA | NG instantaneous | 4.84 | 60% | 3.90 | 0.82 | 1 | 40.0 | 25.8 | $11,750 |
8 | Lowest cost | 80% | NA | NG instantaneous | 4.29 | 50% | NA | 0.82 | 0.6 | 40.1 | 30.9 | $11,440 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 80% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 2.97 | 60% | 3.09 | 0.94 | 1 | 75 | 23.5 | $21,200 |
5 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 3.69 | 50% | NA | 0.82 | 1 | 75.2 | 29.1 | $22,250 |
6 | Lowest cost | 80% |
ccASHP HSPF2 V 7.6 60% load cover |
NG instantaneous | 3.69 | 60% | 3.9 | 0.82 | 1 | 75.1 | 28.7 | $23,830 |
7A | Lowest cost | 80% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 4.84 | 60% | 3.9 | 0.82 | 1 | 75.1 | 34.2 | $25,550 |
7B | Lowest cost | 80% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 4.4 | 60% | 3.9 | 0.82 | 0.6 | 70.3 | 30.3 | $23,990 |
8 | Lowest cost | 80% |
ccASHP HSPF2 V 9.6 60% load cover |
NG instantaneous | 5.45 | 70% | NA | 0.82 | 0.6 | 70.1 | 35 | $31,910 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Tables 5 to 7 show the incremental costs for row house end unit archetype (> 300 m3) packages for various tiers in different climate zones.
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% SRE | NA | NA | NA | NA | 2.98 | 0.94 | 2.5 | 20.2 | 16.9 | $1,690 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | 3.09 | 0.82 | NA | 20.0 | 16.7 | $1,710 | |
5 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 0.94 | 2.5 | 20.2 | 16.6 | $1,470 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | 3.09 | 0.82 | NA | 20.1 | 16.5 | $1,670 | |
6 | Lowest cost | 60% SRE | NA | NA | NA | NA | 3.46 | 1.05 | 2.0 | 20.1 | 16.5 | $1,260 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | 50% | 3.90 | 0.82 | NA | 20.5 | 13.9 | $1,960 | |
7A | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 1.05 | 2.0 | 20.2 | 16.5 | $1,150 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | 60% | 3.90 | 0.82 | NA | 20.5 | 13.3 | $2,010 | |
7B | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 0.94 | 2.0 | 20.4 | 16.5 | $1,070 |
Lowest cost – no airtightness | 80% SRE | NA | NA | 3.96 | 60% | 3.90 | 0.82 | NA | 20.0 | 11.6 | $2,420 | |
8 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 0.94 | 2.0 | 21.0 | 17.4 | $1,070 |
Lowest cost – no airtightness | 60% SRE | NA | NG instantaneous | 3.96 | 60% | NA | 0.82 | NA | 20.0 | 10.4 | $3,330 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% | NA | NG instantaneous | NA | 60% | 3.46 | 0.82 | 1.5 | 40.2 | 23.6 | $5,460 |
5 | Lowest cost | 70% | NA | NG instantaneous | 3.69 | NA | 3.90 | 0.82 | 1.5 | 40 | 30.4 | $6,140 |
6 | Lowest cost | 60% | NA | NG instantaneous | 3.69 | 50% | 3.90 | 0.82 | 1.5 | 40.1 | 28.6 | $6,240 |
7A | Lowest cost | 70% | NA | NG instantaneous | 3.69 | 60% | 3.90 | 0.82 | 1.5 | 40 | 29.2 | $6,490 |
7B | Lowest cost | 80% | NA | NA | 4.84 | 60% | 3.90 | 0.82 | 1.0 | 40.1 | 31.7 | $7,550 |
8 | Lowest cost | 70% | NA | NG instantaneous | 3.96 | 50% | NA | 0.82 | 1.0 | 40.0 | 30.0 | $7,260 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 2.97 | 50% | 3.46 | 0.82 | 1.5 | 75.3 | 25.6 | $15,290 |
5 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 3.69 | 50% | NA | 0.82 | 1.5 | 75.2 | 29.1 | $15,780 |
6 | Lowest cost | 70% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 4.29 | 60% | 3.90 | 0.82 | 1.5 | 75.4 | 31.5 | $17,380 |
7A | Lowest cost | 80% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 4.84 | 60% | 3.90 | 0.82 | 1.5 | 75.2 | 34.3 | $18,650 |
7B | Lowest cost | 80% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 4.29 | 50% | 3.90 | 0.82 | 1.0 | 70.0 | 30.5 | $18,200 |
8 | Lowest cost | 80% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 5.45 | 60% | NA | 0.82 | 0.6 | 70.1 | 40 | $23,730 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Tables 8 to 10 show the incremental costs for single detached archetype (≤ 300 m3) packages for various tiers in different climate zones.
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 1.22 | NA | 20.2 | 6.9 | $670 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.22 | NA | 20.2 | 6.9 | $670 | |
5 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 1.22 | NA | 20.6 | 7.0 | $350 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.22 | NA | 20.6 | 7.0 | $350 | |
6 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 22.4 | 8.8 | $610 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 22.4 | 8.8 | $610 | |
7A | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 22.6 | 8.9 | $610 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 22.6 | 8.9 | $610 | |
7B | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 20.0 | 6.1 | $420 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 20.0 | 6.1 | $420 | |
8 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 0.94 | NA | 21.5 | 7.8 | $540 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 0.94 | NA | 21.5 | 7.8 | $540 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% | NA | NG instantaneous | NA | NA | NA | 0.82 | 1.5 | 40.5 | 18.3 | $3,320 |
5 | Lowest cost | 70% | NA | NA | 3.96 | NA | NA | 0.82 | 1.5 | 40.0 | 25.8 | $2,960 |
6 | Lowest cost | 60% | NA | NA | 4.29 | NA | NA | 0.82 | 1.5 | 40.1 | 26.5 | $3,350 |
7A | Lowest cost | 70% | NA | NA | 3.96 | NA | NA | 0.82 | 1.5 | 40.2 | 26.0 | $3,090 |
7B | Lowest cost | 70% | NA | NA | 4.40 | NA | NA | 0.82 | 1.0 | 40.3 | 25.8 | $3,570 |
8 | Lowest cost | 60% | NA | NA | 4.29 | NA | NA | 0.82 | 1.0 | 40.5 | 26.8 | $3,220 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | Slab on grade | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 2.97 | NA | NA | 0.82 | 1.5 | 76.3 | 20.3 | $13,210 |
5 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NA | 3.69 | NA | 2.84 | 0.82 | 1.5 | 75.0 | 26.6 | $12,830 |
6 | Lowest cost | 60% |
ccASHP HSPF2 V 7.6 60% load cover |
NG instantaneous | 3.85 | NA | 2.84 | 0.82 | 1.5 | 75.0 | 25.2 | $14,010 |
7A | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NA | 4.40 | NA | NA | 0.82 | 1.0 | 75.0 | 31.8 | $14,110 |
7B | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NA | 4.84 | NA | NA | 0.82 | 1.0 | 70.0 | 27.6 | $13,470 |
8 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | 5.01 | NA | NA | 0.82 | 0.6 | 70.0 | 33.6 | $17,360 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Tables 11 to 13 show the incremental costs for double/semi-detached archetype (≤ 300 m3) packages for various tiers in different climate zones.
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | 1.22 | NA | 20.2 | 6.9 | $590 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.22 | NA | 20.2 | 6.9 | $590 | |
5 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | NA | 2.0 | 20.0 | 6.4 | $350 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.22 | NA | 20.6 | 7.0 | $590 | |
6 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | NA | 2.0 | 20.5 | 6.9 | $350 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 22.4 | 8.8 | $530 | |
7A | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | NA | 2.0 | 21.3 | 7.6 | $350 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 22.6 | 8.9 | $530 | |
7B | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | NA | 2.0 | 22.4 | 8.5 | $350 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 1.05 | NA | 20.0 | 6.1 | $370 | |
8 | Lowest cost | 60% SRE | NA | NA | NA | NA | NA | NA | 2.0 | 23.3 | 9.6 | $350 |
Lowest cost – no airtightness | 60% SRE | NA | NA | NA | NA | NA | 0.94 | NA | 21.5 | 7.8 | $470 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% | NA | NG instantaneous | NA | NA | NA | 0.82 | 1.5 | 40.0 | 26.7 | $3,710 |
5 | Lowest cost | 70% | NA | NA | 3.69 | NA | NA | 0.94 | 1.5 | 40.9 | 27.3 | $3,180 |
6 | Lowest cost | 60% | NA | NA | 3.69 | NA | NA | 0.82 | 1.5 | 40.7 | 27.1 | $3,080 |
7A | Lowest cost | 60% | NA | NA | 3.69 | NA | NA | 0.94 | 1.5 | 40.3 | 26.6 | $2,960 |
7B | Lowest cost | 70% | NA | NA | 4.40 | NA | NA | 0.82 | 1.5 | 40.1 | 25.7 | $3,030 |
8 | Lowest cost | 60% | NA | NA | 4.29 | NA | NA | 0.82 | 1.5 | 40.3 | 26.6 | $2,680 |
Notes to Table:
ACH = air change per hour; AG = above-ground; BG = below-ground; DWHR = drain-water heat recovery; NG = natural gas
Zone | Package | Ventilation ECM | Space Conditioning | Hot Water ECM | AG Walls RSI | DWHR | BG Walls RSI | Fenestration U-Value | ACH @ 50 PA | Total Points | Envelope Points | Incremental Cost |
---|---|---|---|---|---|---|---|---|---|---|---|---|
4 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NG instantaneous | NA | NA | NA | 0.82 | 1.5 | 76.4 | 20.4 | $13,470 |
5 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NA | 3.69 | NA | NA | 0.94 | 1.5 | 75.1 | 27.3 | $12,740 |
6 | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NA | 4.40 | NA | NA | 0.82 | 1.5 | 75.3 | 30.4 | $13,620 |
7A | Lowest cost | 60% |
ccASHP HSPF2 V 6.7 60% load cover |
NA | 4.40 | NA | NA | 0.82 | 1.5 | 75.1 | 31.9 | $13,550 |
7B | Lowest cost | 70% |
ccASHP HSPF2 V 6.7 60% load cover |
NA | 4.73 | NA | NA | 0.82 | 1.5 | 70.0 | 27.1 | $12,980 |
8 | Lowest cost | 80% |
ccASHP HSPF2 V 6.7 60% load cover |
NA | 5.45 | NA | NA | 0.82 | 1.0 | 70.0 | 35.8 | $16,430 |
Table 14 shows the climate zones by region.
Table 14. Climate Zones by Region
Table 15 shows the lowest incremental cost for single detached archetype packages by region.
Region | Tier 3 | Tier 4 | Tier 5 |
---|---|---|---|
BC | 3,600–5,320 | 8,390–11,310 | 21,200–31,910 |
AB | 3,600–5,320 | 8,390–11,310 | 22,250–31,910 |
SK and MB | 3,600–5,320 | 8,390–11,310 | 23,830–31,910 |
ON | 3,600–5,320 | 8,390–11,310 | 23,830–31,910 |
QC | 3,600–5,320 | 8,390–11,310 | 23,830–31,910 |
Atlantic Canada | 3,600–5,320 | 8,390–11,310 | 23,830–31,910 |
Northern Canada | 3,600–5,320 | 8,390–11,310 | 23,830–31,910 |
Table 16 shows the lowest incremental cost for row house end unit archetype packages by region.
Region | Tier 3 | Tier 4 | Tier 5 |
---|---|---|---|
BC | 1,070–3,330 | 4,900–6,490 | 15,290–23,730 |
AB | 1,070–3,330 | 4,900–6,490 | 15,780–23,730 |
SK and MB | 1,070–3,330 | 4,900–6,490 | 17,380–23,730 |
ON | 1,070–3,330 | 4,900–6,490 | 17,380–23,730 |
QC | 1,070–3,330 | 4,900–6,490 | 17,380–23,730 |
Atlantic Canada | 1,070–3,330 | 4,900–6,490 | 17,380–23,730 |
Northern Canada | 1,070–3,330 | 4,900–6,490 | 17,380–23,730 |
Table 17 shows the lowest incremental cost for single detached archetype packages by region.
Region | Tier 3 | Tier 4 | Tier 5 |
---|---|---|---|
BC | 350–670 | 2,960–3,570 | 12,830–17,360 |
AB | 420–610 | 3,090–3,570 | 13,470–17,360 |
SK and MB | 420–610 | 3,090–3,570 | 13,470–17,360 |
ON | 350–610 | 2,960–3,570 | 12,830–17,360 |
QC | 420–610 | 3,090–3,570 | 13,470–17,360 |
Atlantic Canada | 350–610 | 2,960–3,570 | 12,830–17,360 |
Northern Canada | 420–540 | 3,220–3,570 | 13,470–17,360 |
Table 18 shows the lowest incremental cost for double/semi-detached archetype packages by region.
Region | Tier 3 | Tier 4 | Tier 5 |
---|---|---|---|
BC | 350–590 | 2,680–3,710 | 12,740–16,430 |
AB | 350–530 | 2,680–3,080 | 12,980–16,430 |
SK and MB | 350–530 | 2,680–3,080 | 12,980–16,430 |
ON | 350–590 | 2,680–3,180 | 12,740–16,430 |
QC | 350–530 | 2,680–3,080 | 12,980–16,430 |
Atlantic Canada | 350–590 | 2,680–3,180 | 12,740–16,430 |
Northern Canada | 350–470 | 2,680–3,030 | 12,980–16,430 |
This proposed change could be enforced by the existing Code enforcement infrastructure.
Designers, engineers, architects, builders and building officials.