This proposed change adds an explanatory Note clarifying that the provisions of Article 4.1.8.4. may not apply to sites with certain ground profiles.
Problem
The requirements of Article 4.1.8.4. of Division B of the NBC may not apply to ground profiles that differ significantly from the generic ground profiles assumed in the models that underpin the NBC provisions. Therefore, the estimation of seismic hazard in accordance with Article 4.1.8.4. may not be appropriate for sites with such non-conforming ground profiles.
The NBC does not currently alert Code users to this important precondition for the application of the requirements of Article 4.1.8.4. The application of these requirements to sites with non-conforming ground profiles may lead to incorrect and inadequate design, which may increase the risk to life safety and the risk of injury beyond the risk levels that are currently acceptable in the NBC for a design-level earthquake event.
Justification
A wide range of ground profiles are found on construction sites. The models used to generate the estimated seismic hazard values for the NBC are based on generic ground profiles. Therefore, these estimates are not valid for sites with ground profiles that are significantly different from the generic profiles, such as sites with ground profiles having strong impedance contrast and sites above deep sedimentary basins. Use of the NBC provisions to calculate the seismic hazard for such sites would be inappropriate and may lead to incorrect results. Code users must be alerted to the limitations in the scope of Article 4.1.8.4.
Since it is not possible to codify all variations of ground profiles, an explanatory Note is proposed to inform Code users that certain ground profiles are not covered by the NBC. This information will prevent any increase (beyond the currently acceptable level in the NBC) in the risk to life safety and the risk of injury from the application of Code requirements to non-conforming ground profiles. A few examples of non-conforming ground profiles are provided in the Note. Additional guidance is proposed to be included in the Commentary entitled Design for Seismic Effects in the "Structural Commentaries (User's Guide – NBC 2025: Part 4 of Division B)."
PROPOSED CHANGE
[4.1.8.4.] 4.1.8.4.Site Properties
(See Note 4.1.8.4.)
[1] 1)For site designation X, as determined in accordance with Sentence (2)or (3), the peak ground acceleration, PGA(X), the peak ground velocity, PGV(X), and the 5%-damped spectral acceleration values, Sa(T,X), at periods T of 0.2 s, 0.5 s, 1.0 s, 2.0 s, 5.0 s and 10.0 s shall
[a] a)except as provided in Sentence (4), be determined in accordance with Subsection 1.1.3., and
[b] b)except as provided in Article 4.1.8.23., correspond to a 2% probability of exceedance in 50 years.
[2] 2)Except as provided in Sentence (3), the site designation referred to in Sentence (1) shall be determined using the average shear wave velocity, Vs30, calculated from in situ measurements of shear wave velocity, as follows:
[a] a)for the ground profiles described in Table 4.1.8.4.-A, the site designation shall be determined in accordance with the Table, and
[b] b)for all other ground profiles, the site designation shall be XV, where V is the value of Vs30.
(See Note A-4.1.8.4.(2) and (3)PROPOSED CHANGE A-4.1.8.4.(2) and (3).)
Table [4.1.8.4.-A] 4.1.8.4.-A Exceptions for Site Designation Using Vs30 Calculated from In Situ Measurements Forming Part of Sentence [4.1.8.4.] 4.1.8.4.([2] 2)
Ground Profile Characteristics
Site Designation
Average Shear Wave Velocity in Top 30 m, Vs30, Calculated from In Situ Measurements, in m/s
Additional Characteristics
Vs30 > 760
Ground profile contains more than 3 m of softer materials between rock and the underside of footing or mat foundations
X760
Vs30 > 140
Ground profile contains more than 3 m of soil with all the following characteristics:
plasticity index, PI > 20,
moisture content, w ≥ 40%, and
undrained shear strength, su < 25 kPa
XE
Vs30 > 140
Ground profile contains
liquefiable soil, quick and highly sensitive clay, collapsible weakly cemented soil, or other soil susceptible to failure or collapse under seismic loading,
more than 3 m of peat and/or highly organic clay,
more than 8 m of highly plastic soil (with PI > 75), or
more than 30 m of soft to medium-stiff clay
XF
Vs30 ≤ 140
n/a
XF
[3] 3)Where Vs30 calculated from in situ measurements is not available, the site designation referred to in Sentence (1) shall be XS, where S is the Site Class determined using the energy-corrected average standard penetration resistance, 60, or the average undrained shear strength, , in accordance with Table 4.1.8.4.-B, 60 and being calculated based on rational analysis. (See Notes A-4.1.8.4.(3)PROPOSED CHANGE A-4.1.8.4.(3)and A-4.1.8.4.(2) and (3)PROPOSED CHANGE A-4.1.8.4.(2) and (3).)
Table [4.1.8.4.-B] 4.1.8.4.-B Site Classes, S, for Site Designation XS Forming Part of Sentence [4.1.8.4.] 4.1.8.4.([3] 3)
liquefiable soil, quick and highly sensitive clay, collapsible weakly cemented soil, or other soil susceptible to failure or collapse under seismic loading,
more than 3 m of peat and/or highly organic clay,
more than 8 m of highly plastic soil (with PI > 75), or
more than 30 m of soft to medium-stiff clay
[4] 4)Site-specific geotechnical evaluation is required to determine the values of PGA(XF), PGV(XF) and Sa(T,XF) for site designation XF.
[5] 5)Where structures on liquefiable soils have a fundamental lateral period, Ta, of 0.5 s or less, the site designation X and the corresponding values of Sa(T,X) and PGA(X) are permitted to be determined in accordance with Sentence (1) by assuming that the soils are not liquefiable.
[6] 6)The design spectral acceleration, S(T), shall be determined in accordance with Table 4.1.8.4.-C, using log–log or linear interpolation for intermediate values of T. (See Note A-4.1.8.4.(6)PROPOSED CHANGE A-4.1.8.4.(6).)
Table [4.1.8.4.-C] 4.1.8.4.-C Design Spectral Acceleration Forming Part of Sentence [4.1.8.4.] 4.1.8.4.([6] 6)
Period, T, in s
Design Spectral Acceleration, S(T)
≤ 0.2
Sa(0.2,X) or Sa(0.5,X), whichever is greater
0.5
Sa(0.5,X)
1.0
Sa(1.0,X)
2.0
Sa(2.0,X)
5.0
Sa(5.0,X)
10.0
Sa(10.0,X)
[7] 7)Where required for the application of a standard referenced in this Subsection, the acceleration-based site coefficient, Fa, for site designation X shall be taken as S(0.2)/Sa(0.2,X450) and the velocity-based site coefficient, Fv, for site designation X shall be taken as S(1.0)/Sa(1.0,X450).
Note A-4.1.8.4.Site Properties.
The provisions of Article 4.1.8.4. may not be sufficient for determining the seismic hazard values for sites with ground profiles that differ significantly from the ground profiles implicit in the ground motion models (GMMs) used to establish the NBC seismic hazard values. A few examples of such sites are sites with ground profiles having strong impedance contrast, sites above deep sedimentary basins, sites near active faults, sloping bedrock sites, sites with ground profiles that are highly variable across the building footprint, and sites with ground improvements.
Information on the ground profiles used in the GMMs, as well as general guidance for sites with ground profiles that differ from those used in the GMMs, can be found in the Commentary entitled Design for Seismic Effects in the "Structural Commentaries (User's Guide – NBC 2020: Part 4 of Division B)".
Impact analysis
The proposed change is a clarification and does not add any new requirements. The impact would be neutral in terms of cost and positive in terms of facilitating the correct application of the Code.
Enforcement implications
The proposed change is a clarification of the scope of Article 4.1.8.4. It would help enforcement staff to properly understand the requirements of this Article and their application. No difficulties are expected to result from the proposed change.
Who is affected
Owners, designers, engineers, contractors and enforcement professionals dealing with geotechnical aspects of the design of buildings for earthquake loads.
OBJECTIVE-BASED ANALYSIS OF NEW OR CHANGED PROVISIONS