Code Reference(s):
NBC20 Div.B 3.2.2.18.(2) (first printing)
Subject:
Automatic Sprinkler System
Title:
Standardization of Terminology in NBC Sprinkler Requirements
Description:
This proposed change is one of a series of proposed changes that standardize the terminology related to sprinklers in the NBC.
This change could potentially affect the following topic areas:

Problem

Currently, various wordings and phrases are used in the National Building Code of Canada (NBC) 2020 to describe whether or not sprinklers are mandated in the space or area in question. Inconsistent use of terminology could create confusion or misunderstanding.

This proposed change standardizes Code wording to clarify where sprinklers are mandated by the NBC by using the defined term “sprinklered” and thereby eliminates any potential confusion.

Justification

As defined in the NBC, “sprinklered (as applying to a building or part thereof) means that the building or part thereof is equipped with a system of automatic sprinklers.”

In the NBC 2020 and National Fire Code of Canada (NFC) 2020, 11 different phrases are used to indicate where sprinklers are mandated, while 8 different phrases are used to indicate where sprinklers are not mandated. In all cases, the defined term “sprinklered” could be used. Not standardizing this terminology could potentially cause confusion among architects and designers as to where sprinklers are mandated. Revising the Code wording to use the defined term “sprinklered” would introduce consistency as well as eliminate any potential confusion.

Table 1 shows the different phrases used in the NBC and NFC to indicate where sprinklers are mandated, along with their frequency.

Table 1. Existing Phrases Indicating Where Sprinklers Are Mandated in the NBC and NFC
Phrase Code Number of Occurrences
“… to have an automatic sprinkler system installed throughout …” NBC 1
“… an automatic sprinkler system shall be installed in …” NBC 1
“… sprinklers shall be installed in …” NBC 2
“… sprinklers shall be provided for …”  NBC 1
“… sprinklers shall not be omitted in …” NBC 1
“… in which an automatic sprinkler system is installed …” NBC 1
“… in which a sprinkler system is installed …”  NBC 2
“… in which a sprinkler system has been installed …” NBC 1
“… area served by the sprinkler system …” NBC 1
“… sprinklers are installed in …” NBC 1
“… shall be equipped throughout with a sprinkler system …” NFC 1

Table 2 shows the different phrases used in the NBC and NFC to indicate where sprinklers are not mandated, along with their frequency.

Table 2. Existing Phrases Indicating Where Sprinklers Are Not Mandated in the NBC and NFC
Phrase Code Number of Occurrences
“… do not require the installation of an automatic sprinkler system …”  NBC 1
“… in which an automatic sprinkler system is not required to be installed …” NBC 1
“… sprinklers are not required in …” NBC 1
“… that is not protected by an automatic sprinkler system …” NBC 1
“… in which sprinklers are not installed …” NBC 2
“… where a sprinkler system is not installed …” NBC 1
“… in which an automatic sprinkler system is not installed …” NBC 2
“… need not be equipped throughout with a sprinkler system …”  NFC 2

EXISTING PROVISION

3.2.2.18.Automatic Sprinkler System Required

1)Except as permitted by Sentence (2), an automatic sprinkler system conforming to the requirements of Articles 3.2.4.7., 3.2.4.8., 3.2.4.9. and 3.2.5.12. shall be installed throughout a building regulated by one or more of Articles 3.2.2.20., 3.2.2.21., 3.2.2.22., 3.2.2.23., 3.2.2.24., 3.2.2.26., 3.2.2.27., 3.2.2.29., 3.2.2.31., 3.2.2.33., 3.2.2.36., 3.2.2.37., 3.2.2.38., 3.2.2.39., 3.2.2.40., 3.2.2.41., 3.2.2.42., 3.2.2.43., 3.2.2.44., 3.2.2.45., 3.2.2.46., 3.2.2.47., 3.2.2.48., 3.2.2.49., 3.2.2.51., 3.2.2.52., 3.2.2.55., 3.2.2.56., 3.2.2.57., 3.2.2.59., 3.2.2.60., 3.2.2.61., 3.2.2.63., 3.2.2.65., 3.2.2.66., 3.2.2.67., 3.2.2.69., 3.2.2.71., 3.2.2.72., 3.2.2.73., 3.2.2.74., 3.2.2.76., 3.2.2.77., 3.2.2.79., 3.2.2.81., 3.2.2.82., 3.2.2.84., 3.2.2.86., 3.2.2.88. and 3.2.2.90.
2)If a storey in a building or a floor area is required to have an automatic sprinkler system installed throughout in accordance with one or more of Articles 3.2.2.20. to 3.2.2.92. or Section 3.3., the automatic sprinkler system shall also be installed throughout all lower storeys in the building notwithstanding permission in Articles 3.2.2.20. to 3.2.2.92. to construct one or more of those storeys without installing automatic sprinkler protection. (See Note A-3.2.2.18.(2)EXISTING PROVISION A-3.2.2.18.(2).)

Note A-3.2.2.18.(2) Sprinkler Extent.

A literal interpretation of Article 3.2.2.6. and Sentences 3.2.2.4.(1) and (2) could require installation of an automatic sprinkler system throughout all storeys of a building regardless of options in Articles 3.2.2.20. to 3.2.2.92. to construct one or more storeys without installation of sprinklers. It is the intent of the Code that all storeys below a storey in which an automatic sprinkler system is installed should also be protected by an automatic sprinkler system to ensure that a fire in a lower storey does not incapacitate the automatic sprinkler system or overwhelm an automatic sprinkler system in an upper storey. Persons in an upper storey in which waivers or reductions of other fire safety systems are permitted would be exposed to an increased risk from a fire on a lower storey. This concept also applies to situations in which an automatic sprinkler system has been installed within a floor area in order to modify other safety requirements applying within the floor area. If the uppermost storey or storeys of a building can be constructed without the installation of an automatic sprinkler system it is not necessary that an automatic sprinkler system required in a lower storey be extended into the upper storey or storeys.

PROPOSED CHANGE

[3.2.2.18.] 3.2.2.18.Automatic Sprinkler System Required

[1] 2)If a storey in a building or a floor area is required to have an automatic sprinkler system installed throughoutto be sprinklered in accordance with one or more of Articles 3.2.2.20. to 3.2.2.92. or Section 3.3., the automatic sprinkler system shall also be installed throughout all lower storeys in the building shall also be sprinklered, notwithstanding permission in Articles 3.2.2.20. to 3.2.2.92. to constructfor one or more of those storeys without installing automatic sprinkler protectionto not be sprinklered. (See Note A-3.2.2.18.(2)PROPOSED CHANGE A-3.2.2.18.(2).)

Impact analysis

This proposed change clarifies Code language by using the defined term for consistency. This proposed change would facilitate interpretation of the Code requirements and eliminate potential confusion. As a result, it is expected that a consistent and appropriate level of safety would be provided without any confusion. No additional costs are expected.

Enforcement implications

This proposed change is intended to clarify the intent of the requirements, which should aid in the understanding and enforcement of the Code.

Who is affected

Authorities having jurisdiction, designers and contractors.

OBJECTIVE-BASED ANALYSIS OF NEW OR CHANGED PROVISIONS

[3.2.2.18.] 3.2.2.18. ([1] 2) [F02,F04-OS1.2,OS1.3]
[3.2.2.18.] 3.2.2.18. ([1] 2) [F02,F04-OP1.2,OP1.3]